Application TechniqueSafety Function: Light Curtain with Muting (Two sensor L-type) and Configurable Safety RelayProducts: Guardmaster 440C-CR30 Configurable Safety Relay, 440L GuardShield Light Curtain , 42EF RightSight Photoelectric Sensors, 100S-C Safety ContactorsSafety Rating: CAT. 4, PLe to ISO 13849-1: 2008To picPa geImportant User Information2 General Safety Information3 Introduction4 Safety Function Realization: Risk Assessment4 Light Curtain with Muting (two- sensor L-type) Safety Function5 Safety Function Requirements5 Functional Safety Description6 Bill of Material7 Setup and Wiring7 Configuration15 Calculation of the Performance Level37 Verification and Validation Plan40 Verification of the Configuration49 Additional Resources522 Rockwell Automation Publication Safety -AT136C-EN-P - January 2016 Safety Function: Light Curtain with Muting (Two sensor L-type) and Configurable Safety RelayImportant User InformationRead this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product.
means, for example, when the presence of a loaded pallet on a conveyor prevents access to the hazardous zone by personnel. Refer to IEC/TS 62046 for additional considerations when applying muting. Position the reset button outside of the hazardous area where it is possible to view the entire hazardous area.