Safety Instrumented Function Verification: The Three Barriers White Paper exida 80 N. Main St. Sellersville, PA November 2017 exida White Paper Library Copyright 2018-2020 Safety Instrumented Function Verification, Copyright LLC 2018-2020 Page 2 excellence in dependable automationAbstract The Three constraints (systematic capability constraint, architectural constraint, and probabilistic performance metric constraint) that are implied by requirements per international Safety standards IEC 61511 [1] and IEC 61508 [2] to determine the Safety integrity level (SIL) of a Safety Instrumented Function (SIF) are described and discussed. Examples of their applications are presented. For low demand mode SIF operation, the importance of including numerous key variables in the computation of average probability of failure on demand (PFDavg) is noted. Introduction Many members of the functional Safety community erroneously believe that the SIL of a SIF is determined solely by the PFDavg of the SIF in low demand mode and solely by the probability of (dangerous) failure per hour (PFH) of the SIF in continuous/high demand mode.
Prior to the release of the first edition of IEC 61508, SIF were subject to prescriptive architectural requirements and standardized designs in order to achieve various SIL levels. IEC 61508 was the first IEC standard to introduce the concept of performance-based assessment and allowed for any appropriate SIF