Rpsa fire PROTECTION ENGINEERS. SCHIFILITI ASSOCIATES, INC. Box 297. Reading, Massachusetts 01867 - 0497. USA. Fax / Data Telephone Sample fire Alarm System Calculations 1. A fire Alarm manufacturer specifies a maximum allowable loop resistance of 50 1. What is the maximum allowable distance from the control unit to the last device if a #16 AWG. stranded, un-coated copper wire is used? Assume a temperature of 750C. How does this change if the temperature is 200C? Rmax = 50 1 = 2 RW 1 R. W. R W = Ru D 1 R. W. Rmax = 50 1 = 2 Ru D 1. Ru = 1/1000 ft or 1 per handout table for D=L/2. #16 AWG stranded, uncoated copper wire at 750C. Rmax 50. D= = = 5010 = 5000 ft 2 Ru 2( ). Part B If T = 200C calculate the unit resistance, Ru, at the lower temperature (it should be less since resistance is lower at lower temperatures leading to super cooled super conductors): R2 = R1 [1 + 9 (T 2 - 75)] where: 9Cu = R2 = [1 + (20 - 75)] 1/ft or R2 = [1 + (20 - 75)] 1/1000 ft R2 = 1/ft Rmax 50.
rpsa File: Sample Fire Alarm System Calculations.DOC Page 3 05 October 2000 rpsa FIRE PROTECTION ENGINEERS Loop Resistance (Loop is 2 …
Domain:
Source:
Link to this page:
Please notify us if you found a problem with this document:
{{id}} {{{paragraph}}}
Fire Alarm and Detection Systems, Fire alarm system, Of Fire Alarm Systems - Section I, Fire alarm, Fire detection and fire, System, Fire detection and fire alarm system, Fire Alarm Inspection and Testing, Inspection and Testing Requirements, Fire, BASIC FIRE ALARM TRAINING, Alarm, FireShieldTM Fire Alarm Control System, Fire Alarm FAQs, FIRE ALARM CONTROL PANELS