CITY OF EDGEWATER 50% CONSTRUCTION DOCUMENTS FIRE STATION 55 June 14, 2010 SECTION 16060 - FIRESTOPPING FOR ELECTRICAL PENETRATIONS PART 1 - GENERAL RELATED DOCUMENTS: The Drawings, general provisions of the Contract and the requirements of SECTION 16050 apply to the Work specified in this SECTION . SUMMARY: A. Provide through- penetration firestop systems to maintain an effective barrier against the spread of flame, smoke, hot gases and water through openings made in fire-rated walls or floors to accommodate ELECTRICAL through-penetrating items such as conduit, busway, cables and cable tray. Firestop shall provide necessary Fire (F) and Temperature (T) ratings.
city of edgewater 50% construction documents fire station 55 june 14, 2010 section 16060 - firestopping for electrical penetrations
Domain:
Source:
Link to this page:
Please notify us if you found a problem with this document:
{{id}} {{{paragraph}}}
Cable Trays Technical Instructions Specifications, TECHNICAL INSTRUCTIONS, Cable, CONTENTS, Wiring and Grounding Guidelines for, Instructions, October 2013 PRODUCT DATA SHEET, SERIES INSTALLATION AND OPERATION, Series installation and operation instructions, ReadyDATA 5200 Hardware Manual, Netgear, ReadyDATA 5200. Hardware Manual