Section 2 ARCHITECTURAL DESIGN REQUIREMENTS ARCHITECTURAL DESIGN Criteria : Section 2 June 2015 Section 2 of ARCHITECTURAL DESIGN Criteria Revision A3 Page-1/31 ARCHITECTURAL DESIGN REQUIREMENTS CONTENTS 1 OBJECTIVES 4 General 4 ARCHITECTURAL aims 4 Clarity and simplicity 4 Buildability 4 Integration with commercial or other facilities 4 Existing Infrastructure 4 Future Expansion 4 Legislation 4 2 ACCESSIBILITY 5 Pedestrian Access 5 Congestion 5 General
Doors astride the tactile route shall be automatic or permanently fixed open. Automatic doors shall be sliding in preference to swing doors. All doors accessed by the public shall require a maximum force of 22N to open or close. Any straight portion of an underground paid link between two MRT Stations which is 75m or greater in