Transcription of SECTION F - Price Industries
{{id}} {{{paragraph}}}
Engineering GuideTerminal UnitsSECTION FF-2 All Metric dimensions ( ) are soft conversion. Copyright Price Industries Limited 2014. Imperial dimensions are converted to metric and rounded to the nearest millimetre. ENGINEERING GUIDE - TERMINAL UNITSF igure 1: Single Duct TerminalSingle Duct TerminalA single duct terminal consists of an air inlet assembly, housing with an insulation liner and a discharge outlet. Typical accessories for this unit include a variety of liners, discharge attenuators, access doors and multiple outlets plenums. Low profile configurations can be used to suit applications where plenum space is restricted.
operation may or may not have an actuator, flow sensor and controls. If the unit does not have an actuator it is typically supplied with a manually locking quadrant allowing the damper blade to be locked into a single position. Variable Volume Single Duct A variable volume single duct will have a flow sensor, an actuator and some type of controls.
Domain:
Source:
Link to this page:
Please notify us if you found a problem with this document:
{{id}} {{{paragraph}}}