Self-Contained Breathing Apparatus (SCBA). Cylinder Life-Extension Study FINAL REPORT. Prepared by: CACI: David Flage David Hunter Steve Robinson Blackstone Group, LLC: Robert Ceres Digital Wave Corporation: Michael Gorman Steven Ziola Under Contract: N00024-11-C-4314. August 2012. Self-Contained Breathing Apparatus (SCBA). Cylinder Life-Extension Study Table of Contents 1 Executive Summary .. 1-1. 2 SCBA Background .. 2-1. 3 Study 3-1. Overall Approach and Study Design .. 3-1. ISO 11119-2 Tests Not Accomplished and 3-2.
Hydrostatic testing of the cylinders is accomplished by removing the valve from the cylinder, threading on a test connection, filling the cylinder with water, pressurizing the cylinder to five-thirds (5/3) of service pressure, and measuring cylinder expansion. Based on findings regarding testing-induced failures and the high hydrostatic testing ...