PDF4PRO ⚡AMP

Modern search engine that looking for books and documents around the web

Example: marketing

Specifications and Installation Guide

Specifications and Installation Guide for Underground Service to Residential Developments June 2010 Western Massachusetts Electric TABLE OF CONTENTS I. II. General a. , 5 b. Code c. Environmental d. Customer III. Division Responsibility a. The b. WMECO IV. Construction V. Construction Requirements a. Layout and b. , 7 c. VI. VII. VIII. Single-Phase mounted Transformer IX. Secondary Vault (Hand hole)..9, 10 X. Riser XI. XII. Street XIII. Other Reviewed and Updated June 2010 2 Required Lead Times The following lead times should be adhered to in order to facilitate timely completion of your proposed project Design lead time: 8 weeks After the Company receives all required materials (town approved plot plan, loads, easement information, street light layout, etc.) Inspection: 3 working days This is the time required to schedule a company inspector to check the construction.

electrical grade schedule 40 as per NEMA TC2-1990. c. Sweeps used at house or pole risers shall have a minimum radius of 24 inches, with 36 inches preferred. Minimum 48-inch radius sweeps are required within the conduit run. d. Reverse bends shall not be allowed within the conduit run. e. Conduit shall enter concrete vault perpendicular to the ...