SPECIFICATIONS FOR FIRE HYDRANT & SPRINKLET SYSTEM.

1 SPECIFICATIONS FOR fire HYDRANT & SPRINKLET system . 1. General. Work under this subhead is time-bound and has t be completed within the time limit set in the tender. Work shall be executed in accordance with an agreed schedule which shall be submitted by the tenderers along with offer and agreed to by owners. Scope of work. The scope of work in this subhead shall consist of furnishing all labour, materials, equipment and appliances necessary and required to completely do all work relating to the supply, installation, testing & commissioning of fire Fighting system as described herein after and shown on the drawings. The scope of work in general shall included the following. i) fire Fighting Pumps & Accessories and related electrical works. ii) External & Internal fire HYDRANT system . iii) sprinkler system in entire building.

An overhead tank 20000 litres capacity will be connected to the fire hydrant system. 1.8.10 Sprinkler system shall be distributed entire building so as to cover 12-12 sq.m area with one sprinkler Sprinkler risers shall be provided with instantaneous control valve with alarm gang.