Standards for the Design, Construction, Maintenance,

1 Standards for the Design, Construction, Maintenance, and Use of Laboratory Fume Hoods Document Number: Effective Date: Revision Date: 5/2006 Purpose and Applicability The intention of this document is to set a standard for the design, construction, maintenance, and use of laboratory ventilation in order to maintain acceptable air quality in the laboratory building and surrounding areas. This standard outlines criteria for stack heights, exhaust exit velocities, and design considerations that shall be addressed and implemented at the University of Massachusetts/Amherst. Together with design Standards established by Facilities & Campus Planning, this document will determine requirements for laboratory exhaust ventilation systems. These requirements do not preclude adherence to good engineering practices, the Massachusetts Building Code and Standards referenced therein.

of the fume hood, exhaust stack height, exit velocity of air being exhausted from the stack. In addition, effluent dispersal is contingent upon factors such as exhaust stack/air intake separation, stack height, stack height plus momentum, topography of the building and surrounding environment, and wind dynamics.