PDF4PRO ⚡AMP

Modern search engine that looking for books and documents around the web

Example: bankruptcy

Steel Stud Perimeter Fire Containment System

ENCLOSURE SOLUTIONS Technical Bulletin SS-04. Steel Stud Perimeter fire Containment System ASTM E2307. Perimeter fire Containment Perimeter fire Containment systems are designed to prevent time period at least equal to the fire resistance rating of the floor/. fire and hot gases from entering the room above the room of ceiling assembly. Perimeter fire Containment systems will serve origin through voids that exist at the intersection of a rated floor any typical building situation with an F-rating of up to two hours. assembly and a non-rated exterior wall. An unprotected void at the edge of the slab potentially creates a pathway for fire and/or Even when the floor/ceiling assembly is not required to be fire smoke to spread from floor to floor in a building. Although such resistance rated, Section still requires that the joint be joints are often small, 2"-3" wide, consider that for a building with sealed with an approved material or System such as owens a floor plate size of 200' 200', 800 lineal feet, an unprotected corning Thermafiber Safing and FireSpan Insulations to retard.

Technical ulletin SS-04 ECLOSURE SOUTIOS Owens Corning ® Enclosure Solutions for Steel Stud Perimeter Fire Containment System with Thermafiber ® ASTM E2307 intermediate scale, multi-story, test furnace and the test wall ASTM E2307 room and exterior window burner fire exposure frame used to hold the test wall and perimeter fire containment

Tags:

  System, Fire, Steel, Containment, Owens, Owens corning, Corning, Dust, Perimeter, Steel stud perimeter fire containment system, Perimeter fire containment

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Spam in document Broken preview Other abuse

Transcription of Steel Stud Perimeter Fire Containment System

Related search queries