Sudden Pressure Protection for Transformers

1 Sudden Pressure Protection for Transformers A report to the Substation Protection Subcommittee of the Power System Relaying Committee of the IEEE Power and Energy Society Prepared by the K6 Working Group December 2014 Assignment: To complete a technical report to the Substation Protection Subcommittee on the application of Sudden Pressure relaying in power Transformers . Members of the Working Group: Randy Crellin (Chair) Don Lukach (Vice Chair) Pat Carroll Mark Carpenter Arvind Chaudhary Steve Conrad Dominick Fontana Rafael Garcia Bill Gordon Gene Henneberg Barry Jackson James Platt Elmo Price Mark Schroeder Greg Sessler

The basic principles of operation for each are described below: 3.1 Pressure Sensing One method is where the sudden pressure sensing relay is located on the top of the transformer such that the sensing connection is located in the gas space of a pressurized transformer. This is known as an “In Gas” sudden pressure relay.