DEP-SOP-001/01 FS 1000 General Sampling Procedures TABLE FS1000-4 40 CFR part 136 TABLE II: Required Containers, preservation Techniques, and holding Times* Applicable to all Non-Potable Water Samples (includes wastewater, surface water, and groundwater) Page 1 of 23 Revision Date: March 1, 2014 Parameter (refers to parameter number on Tables IA,B, C, D,E, F, G & H as noted) Container1 Preservation2, 3 Maximum holding time4 TABLE IA Bacterial Tests: 1 5. Coliform, total, fecal, and E. coli PA, G Cool, <10 C, Na2S2O35 8 hours 22 , 23 6. Fecal streptococci PA, G Cool, <10 C, Na2S2O35 8 hours 22 7. Enterococci PA, G Cool, <10 C, Na2S2O35 8 hours 22 8. Salmonella PA, G Cool, <10 C, Na2S2O35 8 hours 22 TABLE IA Aquatic Toxicity Tests: 9 12. Toxicity, acute and chronic P, FP, G Cool, 6 C 16 36 hours TABLE lB Inorganic Tests: 1. Acidity P, FP, G Cool, 6 C18 14 days 2. Alkalinity P, FP, G Cool, 6 C18 14 days 4. Ammonia P, FP, G Cool, 6 C18, H2SO4 to pH<2 28 days 9.