TIMBER QUEENSLAND LIMITED TECHNICAL DATA SHEET 18 TIMBER FLOORS RECOMMENDED INSTALLATION Revised March 2014 Page 1 This information SHEET outlines the recommended practices for laying TIMBER strip floors over TIMBER and engineered TIMBER joists (it does not include steel joists), structural sub-floors such as plywood, particleboard and over concrete, but does not include direct adhesive fix to slabs. When laying a TIMBER strip floor over joists, either directly on the joists or on SHEET flooring fixed to joists, adequate sub-floor ventilation is essential for the satisfactory performance of the floor. Sub-floor ventilation recommendations are therefore included in this data SHEET . SUB-FLOOR VENTILATIONWhen the lower surface of TIMBER floors or structural sub-floors (over which a TIMBER floor is laid) are exposed to the ground and the space is enclosed (by brickwork etc.), the sub-floor space must be adequately ventilated with permanent vents installed in the masonry during construction.
flooring is being used. Refer Figure 2 for details. FLOOR LAYING PRACTICES The moisture content, size and profile of the flooring should be checked (Data Sheet 17 – Pre-installation assessment) prior to laying. If it is identified that the moisture content is not correct or the boards do not fit together properly, or are otherwise considered