H:\ Technical References\Comm 10 Class IIIB Tank Page 1 of 4 Technical Requirements For Aboveground Storage tanks (ASTs) Storing Class IIIB Liquids References: Comm 10 / NFPA 30 2003 EDITION ITEM DESCRIPTION Comm 10 / NFPA FLASH POINT NFPA 30 Combustible Liquid, Class IIIB Any liquid that has a flash point at or above 200 degree F. Flash point identified on the Material Safety Data Sheet (MSDS) is the reference. DEFINED AND REGULATED AS A COMM 10 TANK Comm 10 effective July 2002 Exempt: UST less than 60 gal. AST less than 110 gal. Significant Changes - Effective Date of Pending Code Revision PLAN REVIEW Requirements Required for all USTs and ASTs larger than 1,100 gallon capacity.
H:\Technical References\Comm 10 Class IIIB Tank Requirements.doc Page 1 of 4 Technical Requirements For Aboveground Storage Tanks …
Domain:
Source:
Link to this page:
Please notify us if you found a problem with this document:
{{id}} {{{paragraph}}}
Smoke, and Combination Fire Smoke Dampers, NFPA, Series heavy duty nfpa tie rod cylinders, Technical Requirements for Aboveground Storage, NFPA 1041 Instructor 2 Pre-Test, NFPA 72, 2008: Basic Requirements for Storage, 2008: Basic Requirements for Storage Tanks, Its Implications on Electrical Inspections