TECHNICAL SPECIFICATION FOR CURRENT …

VOL-II (TS) E12- CURRENT TRANSFORMER- Page 1 of 35 ODISHA POWER TRANSMISSION CORPORATION LIMITED TECHNICAL SPECIFICATION FOR CURRENT TRANSFORMERS I: - 33KV CT a) RATIO-400-200A-100/1-1-1A b) RATIO-800-400-200A/1-1-1A &1-1-1-1A II: - 132 KV CT a) RATIO-800-400-200A/1-1-1-1A b) RATIO-600-300-150A/1-1-1-1A c) RATIO-400-200A-100/1-1-1-1A d) RATIO-200-100/1-1-1-1A III: - 220 KV CT RATIO-1200-600-300A/1-1-1-1-1A IV:- 400 KV CT RATIO:2000-1000-500/1-1-1-1-1A VOL-II (TS) E12- CURRENT TRANSFORMER- Page 2 of 35 TECHNICAL SPECIFICATION FOR 33KV, 132KV, 220 KV & 400 KV CURRENT TRANSFORMERS WITH METERING CORES O

VOL-II (TS) E12 -CURRENT TRANSFORMER Page 4 of 35 3.0 CLIMATIC & SERVICE CONDITIONS : 3.1 The current Transformers are required to operate satisfactorily under the