Vol-III(TS) E13- ISOLATORS Page 1 of 23 ODISHA POWER TRANSMISSION CORPORATION LIMITED TECHNICAL SPECIFICATION FOR ISOLATORS 400KV HCB SINGLE ISOLATOR WITH 1 EARTH SWITCH 400KV HCB SINGLE ISOLATOR WITH 2 EARTH SWITCH 220KV SINGLE ISOLATOR WITHOUT EARTH SWITCH 220KV SINGLE ISOLATOR WITHEARTH SWITCH 220 KV TANDEM ISOLATOR 132 KV DOUBLE ISOLATOR WITH EARTH SWITCH 132 KV SINGLE ISOLATOR WITH EARTH SWITCH 132 KV SINGLE ISOLATOR WITHOUT EARTH SWITCH 132 KV TANDEM ISOLATOR 33 KV DOUBLE ISOLATOR WITH EARTH
3 Applicable standard IS : 9921 / IEC-129/IEC-62271-102 4 Pole 3 pole gang operator 5 Rated voltage nominal / maximum 400/420 220/245 132/145 33/36 6 Rated frequency 50 HZ + 5% 7 System earthing effectively earthed 8 Temperature rise As per relevant IS/IEC publication 9 Insulation level impulse with stand voltage ...