TECHNICAL SPECIFICATIONS : FIRE FIGHTING : Scope of work Supply, Erection, Testing and commissioning of following Fire FIGHTING System components. Getting Approval of drawings and installation from the appropriate Authority. I. Hydrant System I. Hydrant System shall comprise of MS Heavy Grade Yard Hydrants, valves etc., II. Submitting of fabrication drawings for approval before executing and As Built drawings after completion of work REFERENCES IS 3844:1989 Code of Practice for Installation and maintenance of Internal Fire Hydrants and hose reel on premises (First Revision) (Reaffirmed November 1995) IS 901: 1988 specification for couplings, double male and double female instantaneous pattern for firefighting (third revision) IS 902: 1992 Specification for Suction hose coupling for fire hose couplings for firefighting Purposes (third revision) IS 903: 1993 Specification for Fire hose delivery Couplings, Branch pipe, nozzles and nozzle spanner (fourth revision) IS 905:1980 Specification for delivery breechings, dividing and collecting instantaneous
Where reducers are to be made in horizontal runs, eccentric reducer shall be used for the piping to drain freely. In other locations, concentric reducer may be used. Automatic air valves shall be provided at all high points in the piping system for venting. All