Transcription of Telecommunications Design Standards
{{id}} {{{paragraph}}}
1 Telecommunications Design Standards Revision October 4, 2017 Colorado State University 2 Table of Contents Chapter 1: Introduction .. 3 1. Departments Involved in Design Process .. 3 2. Applicable Standards .. 3 3. General Guidelines .. 4 4. Equipment and Materials Specifications .. 4 Chapter 2: Horizontal Infrastructure .. 6 Chapter 3: Communications Rooms .. 9 1. Main Distribution Room MDF .. 9 2. Intermediate Distribution Room (IDF) .. 11 3. Campus Room Types .. 13 4. Grounding and Bonding .. 14 Chapter 4: Riser/Building Backbone Infrastructure .. 17 Chapter 5: Building Entrance Infrastructure .. 19 1. General .. 19 2. University Policy Governing Entrance Infrastructure.
shall be tested using a calibrated Fluke Series DSX -5000 Tester or higher version in accordance with the latest EIA/TIA 568 standards, and the results recorded on a separate USB stick for each building and provided to Telecommunications. The Telecommunications contact from Table 1 shall be notified prior to any testing