PDF4PRO ⚡AMP

Modern search engine that looking for books and documents around the web

Example: bachelor of science

Thermocouple Selection Guide - RS Components

Thermocouple Selection (UK) (International)HeaderDiscover more Thermocouple Thermometry - At a Glance 60584-1 : 2013 / BS EN 60584-1 : 20131 for t < 1100 C,[1 + 0,003 x (t - 1100)] for t > 1100 CDiscover more of Sensor Types Thermocouple Platinum Resistance Thermometer Thermistor Sensor Thermoelement, two dissimilar metals/alloys Platinum-wire wound or flat-film resistor Ceramic (metal oxides) Accuracy (typical values) to C to C to C Long term Stability Variable, Prone to ageing Excellent Good Temperature range -200 to1750 C -200 to 650 C -100 to 300 C Thermal response Sheathed slow Exposed tip fast to 10 secs typical Wirewound slow Film faster 1-50 secs typical generally fast to secs typical Excitation None Constant current required None Characteristic Thermovoltage PTC resistance NTC resistance (some are PTC)

Discover more at www.rs-online.com 3 Comparison of Sensor Types Thermocouple Platinum Resistance Thermometer Thermistor Sensor Thermoelement, two dissimilar metals/alloys Platinum-wire wound or flat-film resistor Ceramic (metal oxides) Accuracy (typical values) 0.5 to 5.0°C 0.1 to 1.0°C 0.1 to 1.5°C

Loading..

Tags:

  Component, Thermocouple, Rs components

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Spam in document Broken preview Other abuse

Transcription of Thermocouple Selection Guide - RS Components

Related search queries