Type 2 coordination for Premium Efficiency motor Starters TemBreak Pro Combination selections June 2021 Version June 2021 CONTACT TECHNICAL SUPPORT - POWER DISTRIBUTION / motor CONTROL 1. Type 2 coordination , 50 kA @ 415 V, Circuit Breakers For Premium Efficiency Motors Chart: Type 2, 50 kA Circuit breakers, with electronic overload FOR DIRECT ON line motor STARTING. Circuit breaker Terasaki Tembreak Pro Contactor Sprecher+Schuh CA7 / CA9. Overload relay Sprecher+Schuh CEP7 Electronic Rated operational voltage 400 / 415V AC. motor types Premium Efficiency class: IE3. Rated conditional AC current (Iq) : 50 kA (rms symetrical). coordination type (AS / NZS - 2015) Type 2 coordination COMPONENT SELECTION TABLE: C/B INSTANT TRIP AMPS &. motor CIRCUIT BREAKER CONTACTOR OVERLOAD RELAY. motor FLC. motor AMP AMPERE C/B INSTANT MINIMUM TRIP. motor MOULED CASE CONTACTOR OVERLOAD RELAY. RATINGS SETTING TRIP AMPS AMP MULTIPLE. kW CIRCUIT BREAKER TYPE (ELECTRONIC) OF motor FLC. @ 400V RANGE ( 20%).
For 3 Version – PE.Pro20.3.1 June 2021 CONTACT TECHNICAL SUPPORT - POWER DISTRIBUTION / MOTOR CONTROL FOR DIRECT ON LINE MOTOR STARTING R CH5 4. 3 2 Rated operational voltage 2, kA – t / s Circuit breaker Terasaki Tembreak Pro Contactor Sprecher+Schuh CA7 and CA9 Overload relay Allen -Bradley 193 E3 Electronic E300 w …