Transcription of Typical Specifications For Dynaforce® Hydronic Heating ...
{{id}} {{{paragraph}}}
Typical Specifications ForDynaforce Hydronic Heating BoilersModels DR(H) 0300 DR(H) 500099-0129 Rev 06 The Heating boiler shall be a CAMUSD ynaforce model _____ having an input rating of _____ Btu (kW) /hr. and_____Btu (kW)/hr output for Hydronic Hydronic Heating boiler shall be design certified by CSA International and shall meet the requirements of ANSI , and The Heating boiler shall be vented as a Category II or IV condensing Overview:-Boiler shall operate up to99%thermalefficiency-Heat exchangershall bea fully condensingverticalcylindrical counter-flow water tube design with 439gradetubes and 316 Lgrade headers ofstainlesssteel constructionand allwelded design with constantallowablesystem returntemperatures tuned combustion premix providing homogeneo
Typical Specifications For Dynaforce® Hydronic Heating Boilers Models DR(H) 0300 – DR(H) 5000 99-0129 Rev 06 Controls: Standard controls include a SOLA electronic proportional integrated combination ignition limit/operator control accurate to 10F (0.50C) having a 4-20 mA output signal suitable for control of a variable frequency motor drive or a pulse width modulation signal output for