M2000 Electromagnetic Flow MeterMAG-UM-01272-EN-09 (February 2019)User ManualM2000 Electromagnetic Flow MeterPage ii February 2019 MAG-UM-01272-EN-09 CONTENTSS afety Precautions and Instructions ..5 System Description ..5 Unpacking and Inspection ..6 Rigging, Lifting and Moving Large Units ..6 Meter Location, Orientation and Applications ..8 Temperature Ranges ..8 Remote Amplifier Outdoor Location ..8 Pipelines and Fluid Flow ..8 Meter Orientation ..9 Vertical Placement .. 9 Horizontal Placement .. 9 Straight Pipe Requirements ..9 Pipe reducer Requirements ..10 Chemical Injection Applications .. 10 Partially-Filled Pipe Situations ..11 Meter Gaskets and Grounding .. 12 Meter/Pipeline Connection Gaskets ..12 Meter Grounding .. 12 Recommended Installation with Grounding Rings .. 12 Amplifier Mounting Configuration Options ..13 Meter Mount Configuration .. 13 Remote Mount Configuration.
With pipe reducers, a smaller meter can be mounted in larger pipelines . This arrangement may increase low-flow accuracy . There are no special requirements for standard, concentric, pipe reducers . Custom fabricated pipe reducers must have an approximate slope angle of 15 degrees to minimize flow disturbances and excessive loss of head .