PVI Industries, LLC Fort Worth, Texas WATER HEATER SIZING GUIDE FOR ENGINEERS commercial INSTITUTIONAL INDUSTRIAL SIZING GUARANTEE PVI SIZING methods are guaranteed to be correct when used in accordance with the instructions as printed, as long as PVI equipment, with its unique performance characteristics, is used. If an installation should not have an adequate amount of hot WATER after proper use of the GUIDE , PVI will, at its cost, correct the installation to the engineer s satisfaction. COMMON FACTORS All calculated loads are converted to GPH (Gallons per Hour) 40 F to 140 F, or an 100 F rise. Appropriate conversion factors will be found near each formula. All BTU output calculations are based on RD (Recovery Demand) Requirement.
2. Some convention-type hotels are being designed to accommodate three or four people per room, using roll-away beds. In such cases, in addition to eliminating the Diversity Factor, we recommend increasing the Adjustment Factor by multiplying the Recovery Demand by 1.25. 3. Hotels designed primarily for commercial trade