Transcription of Water Tanks & System Distribution
{{id}} {{{paragraph}}}
US Army Corps of Engineers Afghanistan Engineer District AED Design Requirements: Water Tanks & System Distribution Various Locations, Afghanistan SEPTEMBER 2009 Version AED Design Requirements Water Tanks & System Distribution TABLE OF CONTENTS. AED DESIGN REQUIREMENTS. FOR. Water Tanks . VARIOUS LOCATIONS, AFGHANISTAN. Section Page 1. General 1. 2. Water Tanks 1. 3. Distribution System Requirements 1. 4. Types of Storage 5. 5. Water Requirements 7. 6. Capacity of Water Supply System 8. 7. Storage Requirements 8. 8. Amount of Water Available Under Emergency Conditions 9. 9. Elevated Storage Capacity 9. 10. Water Distribution System Capacity Analysis 10. 11. Shop Submittals As-Builts 11. 12. References 12. Figures Figure 1. Effects of Elevated Storage 4. Figure 2. Conventional Elevated Storage Tank 6. Figure 3. Single Pedestal Elevated Storage Tank 6. i AED Design Requirements Water Tanks & System Distribution Tables Table 1.
The pump station forces water into the service main, through which it is carried to three load areas: A, B, and C. Since all loads on the system are met without the use of elevated storage, the pump station must be capable of supplying the peak rates of water use