copiers, door openers, and elevator systems). 3.2 Size . The MDF room must be a minimum of 150 sq. ft. (minimum width 10'), which provides a 32" clearance on each side of a loaded 19” equipment rack, on which power outlets are normally mounted. This room size will provide service to approximately 20,000 square feet of building. 3.3 Risers