Electric Service Standards 11 -27 18 - Florida Power & Light
- Customer to stub out ducts as specified beyond the building foundation, as shown on specifications vault drawing (fiber, plastic, or transite ducts shall be enclosed in concrete. Ells shall have a minimum radius of 36 inches); - in grade level vaults, Customer will provide 1-1/4 inch plastic conduit sleeves at specified