Close the alarm control valve or alarm valve. Slowly open the main drain fully and allow water flow to stabilize. Record the residual water supply pressure while water is flowing from the 2” main drain as indicated on gauge in psi. Close the main drain (slowly). Record the restored static pressure. Compare current flow pressure to previous