External static pressure drop through the air distribution system has been calculated to be 0.77 inches of water gauge. From Table PD-35 static pres-sure drop through the electric heater is 0.12 inches of water (0.77 + 0.12 = .89 in.) Enter Table PD-19 for TWE090A4 at 3000 cfm and .90 static pressure. The standard motor at 790 RPM will give