9.3.10.3.1* With the EPS running at rated load, ventilation airflow shall be provided to limit the maximum air temperature in the EPS room to the maximum ambient air temperature required by the EPS manufacturer. [110:7.7.1] 9.3.10.3.1.1 Consideration shall be given to all the heat emitted to the EPS equipment room by the energy converter, uninsulated or