Technical Specification for Main 415V Switchboard 1. GENERAL

Technical Specification for Main 415V Switchboard 1. GENERAL

Back to document page

EN 60947-2 and shall have integral with built-in micrologic control unit. The Air Circuit Breakers shall be rated to carry continuously, the full load current currents of their respective circuits. The minimum rated short time fault capacity shall not be less than 75 kA for 1 second to EN 60947-2. The main contacts shall be of the double break ...

  Micrologic