T6861 Series Large LCD Digital Thermostat 110/220 VAC. 2-pipe/4-pipe fan coil control Data sheet Features S uper modern appearance design, suitable for office, hotel and residential building Horizontal and vertical model available for variant application Slim design, direct installation on 86 size box Stylish and elegant blue/green backlight with blue/. green colour ring 2-pipe/4-pipe integrated into one unit with easy configuration Application Big LCD display with English and icons T6861 Digital thermostats are designed for Easy to install and set-up application of 3-speed fan and valves in fan coil Time on/off function system.

T6861 Series Large LCD Digital Thermostat 110/220 VAC 2-pipe/4-pipe fan coil control Data sheet Features • Super modern appearance design, suitable for

Tags:

  Series, Large, Digital, Thermostats, Series large lcd digital thermostat 110

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of T6861 Series Large LCD Digital Thermostat 110/220 VAC 2 ...

1 T6861 Series Large LCD Digital Thermostat 110/220 VAC. 2-pipe/4-pipe fan coil control Data sheet Features S uper modern appearance design, suitable for office, hotel and residential building Horizontal and vertical model available for variant application Slim design, direct installation on 86 size box Stylish and elegant blue/green backlight with blue/. green colour ring 2-pipe/4-pipe integrated into one unit with easy configuration Application Big LCD display with English and icons T6861 Digital thermostats are designed for Easy to install and set-up application of 3-speed fan and valves in fan coil Time on/off function system.

2 Selectable room temperature or setpoint display Including: Manual or automatic fan speed selection Remote temperature sensor 2-pipe cool only/heat only/manual changeover and Energy saving mode activation by button press or 4-pipe manual or automatic changeover dry contact (key card). Ventilation mode Cycle per Hour (CPH) function Manual or automatic 3-speed fan control Adjustment of display room temperature Water valve control Temperature unit either oC or oF. User setting can be kept when power off Fan speed can be selected to automatic or manual Freezing protection function available 3-speed control mode.

3 Lock or unlock keys or part of keys in Installer Set- In ventilation mode, fan only support manual speed up control. Heat and cool setpoint limitation for energy saving Model summary Power Manual/. Horizontal/ Backlight/ Time 2-pipe/ Energy Remote Model supply Ventilation Automatic Vertical Color Ring on/off 4-pipe Saving Sensor V Fan T6861H2BB Horizontal Blue Y 2/4 220 Y Y Y Y. T6861V2BB Vertical Blue Y 2/4 220 Y Y Y Y. T6861H2GG Horizontal Green Y 2/4 220 Y Y Y Y. T6861V2GG Vertical Green Y 2/4 220 Y Y Y Y.

4 T6861H1BB Horizontal Blue Y 2/4 110 Y Y Y Y. T6861V1BB Vertical Blue Y 2/4 110 Y Y Y Y. T6861H1GG Horizontal Green Y 2/4 110 Y Y Y Y. T6861V1GG Vertical Green Y 2/4 110 Y Y Y Y. Note: Horizontal models are taken as samples for display, operation and installation pictures shown in below parts. APH07CH04 - R2001EN.. Mechanical design Fan can be selected as manual or automatic 3-speed operation. In Manual mode, the fan Thermostat appearnce is switched to the selected speed via control Digital DISPLAY output Gh, Gm, Gl.

5 While in automatic mode, fan speed depends on the difference between room temperature and setpoint. When room temperature FAN BUTTON. UP BUTTON reaches setpoint, valve will be closed and POWER BUTTON. meanwhile, fan will be closed either. MODE BUTTON DOWN BUTTON. Fan speed is high or off Difference between RT and SP. COOL. 4F. Fan speed is medium or off LCD display 2F. INDICATES THE SETPOINT. INDICATES ROOM TEMPERATURE Fan speed is low or off INDICATES INSTALLER SETUP. Setpoint Fan speed is low or off CURRENT FAN SETTING I N D I C AT E S T H E H E AT / C O O L -2F.

6 SETPOINT. INDICATES INSTALLER TEST. INDICATES THE LENGTH. Fan speed is medium or off INDICATES Thermostat IS. OF TIME ON/OFF. -4F. HEAT. OFF INDICATES Thermostat IS. "CALLING" FOR HEAT OR COOL. Fan speed is high or off CURRENT. MODE SETTING. INDICATES WHETHER. INDICATES Thermostat Thermostat IS IN OCCUPIED. IS SET TO TIME ON/OFF OR NOT. INDICATES THE KEYPAD INDICATES Thermostat IS Fan speed ramping control algorithm IS ENTIRELY OR PARTLY IN FREEZING PROTECTION MODE. LOCKED. Four-pipe application System will have a fixed deadband set in ISU.

7 Function between heating and cooling setpoints for Automatic Valve control Change Over (ACO) configured Thermostat acquires the room temperature via its the heating and cooling set points determine the integrated sensor or external temperature sensor dead band. and maintains the setpoint by delivering on/off valve control commands output. If the difference between heating and cooling set points is less than the dead band set in ISU, then the dead band set in ISU is enforced. When adjusting the cooling set point, conflicts will be resolved by moving the heating set point out of the way of the cooling set point (heating set point=cooling set point dead band set in ISU).

8 When adjusting the heating setpoint, conflicts will be resolved by moving the cooling set point out of the way of the heating set point (cooling set point=heating set point +dead band set in ISU). PRESS THE MODE BUTTON TO SELECT. HEAT, COOL, AUTO OR VENT Heating and Cooling range stops will determine the maximum heating setpoint setting and minimum Fan Operation cooling setpoint setting. +1/2 Deadband Cooling Setpoint Dead band -1/2 Deadband Heating Setpoint 4 pipes auto change over setpoint algorithm The last system control mode used will determine PRESS THE FAN BUTTON TO SELECT LOW, MED, HIGH OR AUTO the mode in ACO when in the deadband.

9 APH07CH04 - R2001EN.. Temperature display Operating modes The displayed temperature can be set to acquired The following operating modes are available: room temperature or setpoint. The setting can be made during Installer Set-Up process. Comfort mode Room temperature and scetornt can be displayed In comfort mode, the setpoint can be changed by simultaneously. pressing up and down button. Different applications include cool only, heat only and manual heat/cool Cycle per hour (CPH) changeover. In order to get a more accurate temperature control, CPH function may enable the Thermostat to open TEMPERATURE.

10 The valve for several times per hour even the SETTING. PRESS THIS BUTTON TO. temperature is close to setpoint (difference less RAISE THE TEMPERATURE. than P-band). The default value is 4 for heating SETTING. and 3 for cooling and can be changed in Installer Set-Up process. Time on/off If the Thermostat is off, hold power button for 3 PRESS THIS BUTTON TO. seconds, system will be time on mode. If the LOWER THE TEMPERATURE. SETTING. Thermostat is on, hold power button for 3 seconds, system will be time off mode.