Transcription of Fuji Duo SC-E Series Contactors - AutomationDirect
1 Fuji Duo Series SC-E ContactorsSC-E Series Contactors Specifications - UL and CSAPart NumberPriceNominal Coil VoltageRated Capacity (HP)Rated AC-3 current (A) [note 1]Rated AC-1 Thermal current (A) [note 2]SCCR Ratings (KA)Rated Insulation Voltage (V)Frame Width (mm)3-Phase Motor1-Phase Motor200V220 to 240V440 to 480V550 to 600V100 to 120V 220 to 240 VSC-E02P-24 VAC$ 22551/31920569043SC-E02P-110 VAC$ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ CONTINUED NEXT PAGEN otes: 1. AC3 type loads consist of squirrel cage three-phase motors; occasional, limited jogging duty. 2. AC1 non-inductive or slightly inductive loads. Typically resistive loads ( furnaces, ovens, etc.)
2 SC-E2 SSC-E7 Features 5 to 100 hp at 480 VAC cULus and CSA approval, CE mark, meets JIS and IEC standards. Models SC-E02-xxx to SC-E4-xxx have 3-pole main circuits and come in three sizes with widths of 43mm, 54mm, and 67mm. Models SC-E1-xxx to SC-E7-xxx employ a box terminal structure; allowing wires to be connected directly to the main circuit. Has a finger-protection terminal structure that prevents the exposure of live parts. Models SC-E5-xxx to SC-E7-xxx use a SUPERMAGNETTM (AC-input/DC-output operation) for high operating reliability and requires no surge Size SC-E02-xxx to E05-xxx: 43mm wide SC-E1-xxx to E2S-xxx: 54mm wide SC-E3-xxx, E4-xxx: 67mm wide SC-E5-xxx: 88mm wideSafety Terminals with finger-touch protection (DIN 57106/VDE 0106 Teil100)Utility Box lug terminal construction Long electrical life Easy to wireEnvironmental Low power consumption Recycled thermoplastic resin used for plastic parts.
3 The names of materials are indicated on all major parts to facilitate recyclingStandards & Approvals UL listed, file E42419, Standard UL 508 cUL listed, file E42419, Standard CSA C VDE 0660 JIS C 8201-4-1 IEC 60947-4-1 / EN 60947-4-1 CE compliantOptional accessories Auxiliary contact blocks Coil surge suppression ControlstMRC-28 For the latest prices, please check Series Contactors Specifications - UL and CSAM odelPriceNominal Coil VoltageRated Capacity (HP)Rated AC-3 current (A) [note 1]Rated AC-1 Thermal current (A) [note 2]SCCR Ratings (KA)Rated Insulation Voltage (V)Frame Width (mm)3-Phase Motor1-Phase Motor200V220 240V440 480V550 600V100 20V 220 240 VSC-E1-24 VAC$ $ $ $ $ $ $ 10153030354060SC-E2-110 VAC$ $ $ $ $ 152030303105065SC-E2S-110 VAC$ $ $ $ $ $ 202550505156510067SC-E3-110 VAC$ $ $ $ $ 2530505051580105SC-E4-110 VAC$ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ $ : 1.
4 AC3 type loads consist of squirrel cage three-phase motors; occasional, limited jogging duty. 2. AC1 non-inductive or slightly inductive loads. Typically resistive loads ( furnaces, ovens, etc.)Fuji Duo Series SC-E ControlstMRC-29 For the latest prices, please check Series Contactors Specifications - IECC ontactor Type Rated Capacity (kW)Rated Operating current (A)RatedThermalCurrent (A)Internal Auxilliary Contact Arrangement3-Phase motor AC-3 / AC-43-Phase motor AC-3 / AC-4 Resistive Load AC-1200-240V380-440V500-550V600-690V200- 240V380-440V500-550V600-690V200-240V380- 440 VSC-E02(G) / / 44 / NA4 / NA9 / 99 / 97 / NA5 / NA202020-SC-E03(G)-xxx3 / / / NA / NA12 / 1212 / 129 / NA 7 / NA20 20 20 -SC-E04(G)-xxx4 / / / / NA18 / 1818 / 1813 / NA9 / NA25 25 25 -SC-E05(G)
5 / 411 / / / NA25 / 18 25 / 1817 / NA9 / NA32 32 32 -SC-E1(G) / / 1515 / NA11 / NA32 / 3232 / 3224 / NA15 / NA50 50 50 -SC-E2(G)-xxx11 / / / NA15 / NA40 / 4040 / 4029 / NA19 / NA60 60 60 -SC-E2S(G)-xxx15 / 1122 / / NA22 / NA50 / 4050 / 4038 / NA26 / NA65 65 65 -SC-E3(G) / / 3037 / NA30 / NA68 / 6865 / 6560 / NA38 / NA100 100 100 -SC-E4(G)-xxx22 / / 3037 / NA37 / NA80 / 6880 / 6560 / NA44 / NA105 105 105 -SC-E5-xxx30 / 3055 / 555 5/ NA55 / NA105 / 105105 / 10585 / NA64 / NA1501501502NO+2 NCSC-E6-xxx37 / 3760 / 60 6 0 / NA60 / NA125 / 125125 / 12590 / NA72 / NA150 150 150 2NO+2NC SC-E7-xxx45 / 4575 / 7575 / NA90 / NA150 / 150150 / 150120 / NA103 / NA200 200 200 2NO+2NC Internal Auxiliary Contact Ratings - UL and CSAF rame Size ( note 1 )Rated Insulation Voltage (V)NEMA ICS 5-2000 Ratings ( note 2 )AC RatingsDC RatingsDesignationMaking VABreaking VADesignationMaking/Breaking VAE5 to E7-xxx690A6007200720Q30069 Notes: 1.
6 E02(G) to E4(G) do not have internal auxiliary contact. 2. NEMA ICS 5-2000. For more information, refer to Control Circuit Contact Electrical Ratings, see page Auxiliary Contact Ratings - IEC, JISB ased on IEC 60974-4-1, EN 60947-4-1, JIS C 8201-4-1 Frame Size( note 1 )Rated Insulation Voltage (V)Rated Thermal current (A)Making and Breaking Capacity (A)Rated Operational current (A)Minimum Operating Voltage and CurrentAC VoltageAmpsAC VoltageAC-15 (Ind. load)DC VoltageDC-13 (Ind. load)E5 to E7-xxx69010120V60120V624V35 VDC, 1: E02(G) to E4(G) do not have internal auxiliary Duo Series SC-E ContactorsInternal Auxiliary Contact ControlstMRC-30 For the latest prices, please check Duo Series SC-E ContactorsDC Coil CharacteristicsFrame SizePower Consumption (W)Pick-Up Voltage (V)Drop-Out Voltage (V)Operating Time (ms)
7 InrushSealedCoil ON to Contact ONCoil OFF to Contact OFFE02G to - x rated coil - x rated coil voltage45-4910-26E1G to - x rated coil - x rated coil voltage40-508-17E3G, - x rated coil - x rated coil - x rated coil - x rated coil voltage35-4126-32E6, - x rated coil - x rated coil voltage28-3427-33AC Coil Characteristics Frame SizePower Consumption (VA)Power Loss (W)Pick-Up Voltage (V)Drop-Out Voltage (V)Operating Time (ms)Inrush Sealed 50Hz60 HzCoil ON to Contact ONCoil OFF to Contact OFF50/60Hz50/60 HzE02 to E05-xxx90/959 - x rated coil - x rated coil voltage9-205-16E1 to E2S-xxx120 - x rated coil - x rated coil voltage10-176-13E3, E4-xxx180 - x rated coil - x rated coil voltage10-188-18E5-xxx80/954 - x rated coil - x rated coil voltage39-4527-33E6, E7-xxx190 - x rated coil - x rated coil voltage31-3730-36 Operating CoilAC Coil.
8 SC-E02-xxx to SC-E4-xxxVoltage CodeCoil Operating Voltage / Frequency24 VAC24 VAC 50Hz / 24-26 VAC 60Hz110 VAC100-110 VAC 50Hz / 110-120 VAC 60Hz220 VAC200-220 VAC 50Hz / 220-240 VAC 60Hz440 VAC415-440 VAC 50Hz / 440-480 VAC 60Hz500 VAC480-500 VAC 50Hz / 500-550 VAC 60 HzOperating CoilDC Coil, SC-E02G-xxx to SC-E4G-xxxVoltage CodeCoil Operating Voltage 24 VDC24 VDCO perating CoilAC/DC Coil (SUPERMAGNET), SC-E5-xxx to SC-E7-xxxVoltage CodeCoil Operating Voltage/Frequency24V24-25 VAC 50/60Hz; 24 VDC100V100-127 VAC 50/60Hz; 100-120 VDC200V200-250 VAC 50/60Hz; 200-240 VDC400V380-450 VAC 50/60Hz500V460-575 VAC 50/60 HzCoil CharacteristicsFrame sizeMaking current (A)Breaking current (A)Operating cyclesDurability (operations)
9 220V440V220V440 Vper hourElectricalMechanicalSC-E021081089090 18002 million10 million10 million10 million10 million10 million10 million10 million 5 millionSC-E481680068065012001 million 5 millionSC-E5126012601050105012001 million 5 millionSC-E6150015001250125012001 million 5 millionSC-E7180018001500150012001 million 5 millionPerformance ControlstMRC-31 For the latest prices, please check Duo Series SC-E ContactorsStandard operating conditionsThe magnetic Contactors are manufactured for use in the standard operating conditions given in the Sizes, Tightening Torques - Control CircuitSolid or Stranded Wire (mm2) to (1 to mm diameter) to (1 to mm diameter)Stranded WireFlexible Stranded Wire [in] to [ to ]AWG18 to 14 Ring Terminal [SC-E0x(P) only] [in] [ ]AWGOne18 to 14 Two18 to 14 Insulation Stripping Length 10 mm inFork TerminalMax.
10 WideTerminal Screw screwdriver, H-type, No. 2 (ISO 8764); ADC part number TW-SD-VPH-1 or TW-SD-VPH-2 Flat-blade screwdriver, 1 x x L-type, B (ISO 2830); ADC part number TW-SD-VSL-4 Tightening Torque ( ) to 1 Standard Operating ConditionsAmbient TemperatureOperating: -5 to 55 C [23 to 131 F]No sudden temperature changes resulting in condensation or icing (The average temperature over a 24-hour period must not exceed 35 C [95 F) Storage: -40 to 65 C [-40 to 149 F]Humidity45 to 85%RHAltitude2000m or lowerAtmosphereNo excessive dust, smoke, corrosive gases, flammable gases, steam, or saltVibration10 to 55Hz 15m/s2 Shock50m/s2 Mounting35mm IEC DIN rail mounting (SC-E02 to SC-E4), screw mountingMounting Angle30 30 30 30 StandardIEC 947-4-1, EN 60947-4-1, VDE 0660 JIS C 8201-4-1, JEM 1038UL 508, file E42419.]