15.5kV E-Rated medium voltage fuses for feeder circuit ...

Technical Data 10353 Effective December 2015 Supersedes April 2015 BUSSMANNSERIESD escription: The Bussmann series of E-Rated , current-limiting, medium voltage fuses are for feeder circuit , switchgear and transformer and benefits: Current-limiting E-Rated medium voltage fuses are defined by their melting time-current characteristic that permit their electrical interchangeability with other fuses of the same E Rating. E-Rated fuses must have a defined current response time specified by ANSI E-Rated fuse of 100 amps and below must melt in 300 seconds at an RMS current within the range of 200% to 240% of the fuse s nameplate current rating. E-Rated fuses greater than 100 amps must melt in 600 seconds at an RMS current within the range of 220% to 264% of the fuse s nameplate current rating. E-Rated fuses are physically dimensioned for easy installation in existing hardware. Current-limiting fuses provide positive interruption even on low fault currents.

Technical Data 10353 Effective September 2018 Supersedes July 2018 BSSMANN ERIES Description: • Bussmann™ series of E-Rated, current-limiting, medium voltage fuses are for feeder circuit, switchgear and transformer protection.

Tags:

  Circuit, Voltage, Fuse, Transformers, Feeder, Voltage fuses for feeder circuit

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of 15.5kV E-Rated medium voltage fuses for feeder circuit ...

1 Technical Data 10353 Effective December 2015 Supersedes April 2015 BUSSMANNSERIESD escription: The Bussmann series of E-Rated , current-limiting, medium voltage fuses are for feeder circuit , switchgear and transformer and benefits: Current-limiting E-Rated medium voltage fuses are defined by their melting time-current characteristic that permit their electrical interchangeability with other fuses of the same E Rating. E-Rated fuses must have a defined current response time specified by ANSI E-Rated fuse of 100 amps and below must melt in 300 seconds at an RMS current within the range of 200% to 240% of the fuse s nameplate current rating. E-Rated fuses greater than 100 amps must melt in 600 seconds at an RMS current within the range of 220% to 264% of the fuse s nameplate current rating. E-Rated fuses are physically dimensioned for easy installation in existing hardware. Current-limiting fuses provide positive interruption even on low fault currents.

2 The fuse limits the magnitude of electromechanical stresses in the protected apparatus. Constructions available in ferrule, bolt-on and clip-lock, and specialty mount fuses for AMPGARD motor starters Outdoor rating available on select catalog numbers (requires installation in a suitable enclosure). Open fuse indicator easily integrates into automation schemes and speeds troubleshooting by providing a positive visual indication of fuse operation. 50/60Hz operating frequency for worldwide application. Mountings are available in disconnect and non-disconnect versions with porcelain or glass polyester insulators. Live parts and end fittings applications: medium voltage transformer primary protection medium voltage feeder circuit protection medium voltage switches medium voltage metal-enclosed E-Rated medium voltage fuses for feeder circuit , switchgear and transformer protection2 Technical Data 10353 Effective December E-Rated medium voltage fuses for feeder circuit , switchgear and transformer medium voltage ferrule fusesCatalog symbols: General purpose 15 CLE-_E-D (long construction, 10-25A) 15 CLE-_E (long construction, 15-300A) 15 HLE-_E (short construction, 10-250A) 15 LHLE-_E (intermediate construction, 65-300A) Full range (per ANSI ) MV155F_Ratings*: Volts Amps 10 to 300A Interrupting ratings to 63kA RMS Sym.

3 * See catalog number tables for voltages, ampacities and interrupting ratings by catalog information: E-Rated fuses meet the performance characteristics of ANSI UL Listed, Guide JEEG, File E240398. See catalog (see catalog number tables for values) ( ) A A B CRecommended fuseclips and holders:Amp ratingFuse mounting type* voltage BIL (kV)Approximate dimensions - in (mm)Catalog numberMounting (including live parts, end fittings)**Live parts (including end fittings)End fittings (disconnect only)DiameterClip centerLengthPorcelain insulatorGlass-polyester insulatorCLE15E 25 ESingle barrelNon-disconnect 952 (51)20 (508) (546)15 CLE-PNM-C15 CLE-GNM-C CLE-NL-C 110 15 CLE-HPNM-C CLE-NL-C Disconnect 9515 CLE-PDM-C15 CLE-GDM-CCLE-DL-CCLE-DF-C11015 CLE-HPDM-C CLE-DL-CCLE-DF-C10E-D 25E-D 30E 150E Single barrelNon-disconnect 95 3 (76) 20 (508) (607)15 CLE-PNM-D15 CLE-GNM-DCLE-NL-D 110 15 CLE-HPM-D CLE-NL-D Disconnect 9515 CLE-PDM-D15 CLE-GNM-DCLE-DL-DCLE-DF-D11015 CLE-HPDM-D CLE-DL-DCLE-DF-D175E 300E Double barrelNon-disconnect110 3 (76)20 (508) (607)15 CLE-PNM-E CLE-NL-E Disconnect 110 15 CLE-PDM-E CLE-DL-ECLE-DF-EHLE10E-125E Single barrelNon-disconnect953 (76)15 (381) (480)

4 15 HLE-PNM-D15 HLE-GNM-DCLE-NL-D Disconnect 9515 HLE-PDM-D15 HLE-GDM-DCLE-DL-DCLE-DF-D150E 250E Double barrelNon-disconnect953 (76)15 (381) (480)15 HLE-PNM-E CLE-NL-E Disconnect 9515 HLE-PDM-E CLE-DL-ECLE-DF-ELHLE65E 150E Single barrelNon-disconnect 3 (76)18 (457) (521)Not availableNot availableCLE-NL-D Disconnect Not availableNot availableCLE-DL-DCLE-DF-D175E 300E Double barrelNon-disconnect 3 (76) 18 (457) (521)Not availableNot availableCLE-NL-E Disconnect Not availableNot availableCLE-DL-E CLE-DF-E* See page 10 for illustrations and dimensions** End fittings supplied only when required. Disconnect mountings provide a means for fuse extraction only. Do not use a disconnect mounting for load switching or fuse removal while B C3 Technical Data 10353 Effective December E-Rated medium voltage fuses for feeder circuit , switchgear and transformer , HLE and LHLE type general purpose fusesAmp ratingDimensions - in (mm)Interrupting rating kA (RMS Sym.)

5 Number of barrelsInstallation locationCatalog numberLength ADiameter BClip centers CCLE Long (607)3 (76)20 (508)631 (546)2 (51)20 (508) * (607)3 (76)20 (508)631 (546)2 (51)20 (508) * (607)3 (76)20 (508)631 (546)2 (51)20 (508) * (607)3 (76)20 (508)631 (607)3 (76)20 (508)631 (607)3 (76)20 (508)631 Indoor/outdoor15 CLE-40E (607)3 (76)20 (508)631 Indoor/outdoor15 CLE-50E (607)3 (76)20 (508)631 Indoor/outdoor15 CLE-65E (607)3 (76)20 (508)631 Indoor/outdoor15 CLE-80E 10 (607)3 (76)20 (508)631 Indoor/outdoor15 CLE-100E (607)3 (76)20 (508)631 Indoor/outdoor15 CLE-125E (607)3 (76)20 (508)631 Indoor/outdoor15 CLE-150E (607)3 (76)20 (508)632 Indoor/outdoor15 CLE-175E (607)3 (76)20 (508)632 Indoor/outdoor15 CLE-200E (607)3 (76)20 (508)632 Indoor/outdoor15 CLE-250E (607)3 (76)20 (508)632 Indoor/outdoor15 CLE-300E HLE Short (480)3 (76)15 (381)631 (480)3 (76)15 (381)631 (480)3 (76)15 (381)631 (480)3 (76)15 (381)631 (480)3 (76)15 (381)631 (480)3 (76)15 (381)631 Indoor/outdoor15 HLE-40E (480)3 (76)15 (381)631 Indoor/outdoor15 HLE-50E (480)3 (76)15 (381)631 Indoor/outdoor15 HLE-65E (480)3 (76)15 (381)631 Indoor/outdoor15 HLE-80E 10 (480)3 (76)15 (381)631 Indoor/outdoor15 HLE-100E (480)3 (76)15 (381)631 Indoor/outdoor15 HLE-125E (480)3 (76)15 (381)632 Indoor/outdoor15 HLE-150E (480)3 (76)15 (381)632 Indoor/outdoor15 HLE-175E (480)3 (76)15 (381)632 Indoor/outdoor15 HLE-200E (480)3 (76)15 (381)632 Indoor/outdoor15 HLE-250E (521)3 (76)18 (457)501 (521)3 (76)18 (457)501 Indoor/outdoor15 LHLE-80E10 (521)3 (76)18 (457)501 (521)3 (76)18 (457)501 (521)3 (76)18 (457)501 (521)3 (76)18 (457)502 (521)3 (76)18 (457)502 (521)3 (76)18 (457)502 (521)3 (76)18 (457)502 Indoor/outdoor15 LHLE-300E* fuses conform to dimensional standards established by Westinghouse.

6 UL Listed, Guide JEEG, File Data 10353 Effective December E-Rated medium voltage fuses for feeder circuit , switchgear and transformer full rangeAmp ratingDimensions - in (mm)Interrupting rating kA (RMS Sym.)Number of barrelsInstallation locationCatalog numberLength ADiameter BClip centers (475)2 (51)15 (381) (475)2 (51)15 (381) (475)2 (51)15 (381) (475)3 (76)15 (381) (475)2 (51)15 (381) (475)3 (76)15 (381) (475)2 (51)15 (381) (475)3 (76)15 (381) (475)2 (51)15 (381) (475)3 (76)15 (381) (475)2 (51)15 (381) (475)3 (76)15 (381) (475)3 (76)15 (381) (475)3 (76)15 (381) (475)3 (76)15 (381) (551)3 (76)18 (457) (475)3 (76)15 (381) (551)3 (76)18 (457)501 IndoorMV155F1 DCX80E10 (475)3 (76)15 (381)501 IndoorMV155F1 DBX100E10 (551)3 (76)18 (457) (475)3 (76)15 (381) (551)3 (76)18 (457) (475)3 (76)15 (381) (551)3 (76)18 (457) (475)3 (76)15 (381) (551)3 (76)18 (457) (475)3 (76)15 (381) (551)3 (76)18 (457)502 IndoorMV155F2 DCX200 ERecommended MV155 fuseclips.

7 DescriptionFuse diameter - in (mm)FigureClip dimensions - in (mm) A B C D E F GCatalog numberEnclosed fuseclip2 (51) (95) (50) (51) (30) (115) (38) (10)A3354710*Enclosed fuseclip3 (76) (105) (62) (76) (30) (143) (38) (10)A3354730*Open fuseclip3 (76)2 See dimensions drawing1A0065 Spring loaded open fuse -clip3 (76)3 See dimensions drawing9078A67G04*For single barrel applications only. Not sold in 2 Figure 3 Figure 15 Technical Data 10353 Effective December E-Rated medium voltage fuses for feeder circuit , switchgear and transformer Time-current curves minimum melt for MV155 2 inch diameter fusesTIME IN SECONDSAMPERERATING1,0007,00010010 CURRENT IN (2 inch diameter)Current in amperesTime in secondsAmperes ratings6 Technical Data 10353 Effective December E-Rated medium voltage fuses for feeder circuit , switchgear and transformer time-current curves total clear for MV155_ 2 inch diameter fusesTIME IN ,0007,00010010 CURRENT IN AMPERESMV155_ (2 inch diameter)CURRENT IN AMPERESC urrent in amperesTime in secondsAmperes ratings7 Technical Data 10353 Effective December E-Rated medium voltage fuses for feeder circuit , switchgear and transformer time-current curves minimum melt for MV155_ 3 inch diameter fusesMV155_ (3 inch diameter).

8 IN SECONDSCURRENT IN AMPERES10A15A20A25A30A40A50A65A80A100A12 5A150A175A200 ACurrent in amperesTime in seconds8 Technical Data 10353 Effective December E-Rated medium voltage fuses for feeder circuit , switchgear and transformer time-current curves total clear for MV155_ 3 inch diameter fusesMV155_ (3 inch diameter)TIME IN SECONDSCURRENT IN in amperesTime in seconds9 Technical Data 10353 Effective December E-Rated medium voltage fuses for feeder circuit , switchgear and transformer peak let-through for MV155_ 2 and 3 inch diameter fusesMV155_ (2 and 3 inch diameter)1 AVAILABLE CURRENT IN KILOAMPERES (RMS Symmetrical)MAXIMUM LET-THROUGH (Peak Kiloamperes) current in kilo-amperes (RMS symmetrical)Maxium left-through (peak kilo-amperes)10 Technical Data 10353 Effective December E-Rated medium voltage fuses for feeder circuit , switchgear and transformer time-current curves minimum melt for 15 LHLE_ 3 inch diameter fusesTIME IN SECONDSCURRENT IN AMPERES15 LHLE_ (3 inch diameter)Curve TC66703203 April 2011 Current in amperesTime in seconds11 Technical Data 10353 Effective December E-Rated medium voltage fuses for feeder circuit , switchgear and transformer time-current curves total clear for 15 LHLE_ 3 inch diameter fusesTIME IN SECONDSCURRENT IN AMPERES15 LHLE_ (3 inch diameter)Curve TC66703303 April 2011 Current in amperesTime in seconds12 Technical Data 10353 Effective December E-Rated medium voltage fuses for feeder circuit , switchgear and transformer peak let-through for 15 LHLE_ 3 inch diameter fusesPeak Instantaneous Let-Through Current in Kilo-amperiesCURRENT IN AMPERES15 LHLE_ (3 inch diameter)

9 Curve TC70547404 April 2011 Current in amperesMaxium left-through (peak kilo-amperes)13 Technical Data 10353 Effective December E-Rated medium voltage fuses for feeder circuit , switchgear and transformer and HLE type mountings - in (mm)Catalog numberHole centersOverall lengthHole InsetHole centersContact heightOverall heightBIL kV A B C D E F GDisconnect single barrel ( )6 ( )34 ( ) ( ) ( )7 ( ) ( ) ( )6 ( )31 ( ) ( ) ( )7 ( ) ( ) ( )6 ( )34 ( ) ( ) ( )7 ( ) ( ) ( )6 ( )31 ( ) ( ) ( )7 ( ) ( ) ( )6 ( )34 ( ) ( ) ( ) ( ) ( ) ( )6 ( )31 ( ) ( ) ( ) ( ) ( ) ( )6 ( )25 ( ) ( ) ( )7 ( ) ( ) ( )6 ( )25 ( ) ( ) ( )7 ( ) ( )95 Disconnect double barrel ( )6 ( )31 ( ) ( ) ( ) ( ) ( ) ( )6 ( )25 (635) ( ) ( )7 ( ) ( ) ( )6 ( )25 (635) ( ) ( )7 ( ) ( )95 Non-disconnect single ( )6 ( ) ( ) ( ) ( )7 ( ) ( ) ( )6 ( ) ( ) ( ) ( )7 ( ) ( ) ( )6 ( ) ( ) ( ) ( ) ( ) ( ) ( )6 ( )31 ( ) ( ) ( )7 ( ) ( ) ( )6 ( )31 ( ) ( ) ( )7 ( ) ( ) ( )6 ( )31 ( ) ( ) ( ) ( ) ( ) ( )6 ( )25 (635) ( ) ( )7 ( ) ( ) ( )6 ( )25 (635) ( ) ( )7 ( ) ( )95 Non-disconnect double ( )6 ( )31 ( ) ( ) ( ) ( ) ( ) ( )6 ( )25 (635) ( ) ( )7 ( ) ( ) ( )6 ( )25 (635) ( ) ( )7 ( ) ( )95 CLE and HLE type disconnect mounting CLE and HLE type non-disconnect mountingDDEEACBGFDDEEABCGF Disconnect mountings provide a means for fuse extraction only.

10 Do not use a disconnect mounting for load switching or fuse removal while Data 10353 Effective December E-Rated medium voltage fuses for feeder circuit , switchgear and transformer medium voltage specialty mount fusesCatalog symbols: 15 BHLE-_E (bolt-on version) 15 HCL-_E (clip-lock version)Ratings*: Volts Amps 10 to 300A Interrupting ratings 50 to 63kA RMS Sym* See catalog number tables for voltages, ampacities and interrupting ratings by catalog information: E-Rated fuses meet the performance characteristics of ANSI live parts for clip-lock fuses Catalog number ( ) C AIndicator to belocated ( ) ( ) C AIndicator to belocated ( ) ( ) C ( )HCLD imensions - in (mm)BHLE ( )BAIndicator* ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( ) ( )Indicator* x ( x ) SlotsC ( ) Dia. ( )B* Flush with surface in untripped position, trip force is 2lb ( ) ( ) ( )15 Technical Data 10353 Effective December E-Rated medium voltage fuses for feeder circuit , switchgear and transformer , BHLE and HCL Type fusesAmp ratingDimensions - in (mm)Interrupting rating kA (RMS Sym.)