4. Siemens AG 2016. Residual Current Protective Devices / Arc Fault Detection Devices (AFDDs). 4/2 Introduction 4/4 5SV RCCBs 4/10 5SM3 RCCBs 4/13 SIQUENCE 5SM3/5SU1. universal Current -sensitive RCCBs, type B and type B+. 4/18 Additional components 4. 4/22 5SM2 RC units 4/30 5SU1 RCBOs 4/38 5SM6 AFD units 4/41 5SM6 AFD units for PV applications 4/42 5ST busbars for modular installation Devices 4/45 5SM1 and 5SZ9 RCCB socket outlets 4/46 Accessories 4/47 Configuration For further technical product information: Configuration Manual Residual Current Protective Devices /. Direct reference to the products in the Arc Fault Detection Devices (AFDDs). Industry Mall from the selection and Article No.: 3ZW1012-5SM33-0AC1. ordering data tables: Siemens Industry Online Support: Article No. Paper catalog: To get more product information support , product? Article No. enter the Web Entry type: address plus Application example Article No.

Devices with a rated residual current of maximum 300 mA are used as preventive fire protection in case of insulation faults. RCCBs with a rated residual current of 100 mA are primarily used outside Europe. Benefits † Instantaneous residual current operated circuit breakers with the N connection on the left or right-hand side enable simple

Tags:

  Current, Circuit, Residual, Residual current

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of © Siemens AG 2016 Residual Current Protective Devices / Arc ...

1 4. Siemens AG 2016. Residual Current Protective Devices / Arc Fault Detection Devices (AFDDs). 4/2 Introduction 4/4 5SV RCCBs 4/10 5SM3 RCCBs 4/13 SIQUENCE 5SM3/5SU1. universal Current -sensitive RCCBs, type B and type B+. 4/18 Additional components 4. 4/22 5SM2 RC units 4/30 5SU1 RCBOs 4/38 5SM6 AFD units 4/41 5SM6 AFD units for PV applications 4/42 5ST busbars for modular installation Devices 4/45 5SM1 and 5SZ9 RCCB socket outlets 4/46 Accessories 4/47 Configuration For further technical product information: Configuration Manual Residual Current Protective Devices /. Direct reference to the products in the Arc Fault Detection Devices (AFDDs). Industry Mall from the selection and Article No.: 3ZW1012-5SM33-0AC1. ordering data tables: Siemens Industry Online Support: Article No. Paper catalog: To get more product information support , product? Article No. enter the Web Entry type: address plus Application example Article No.

2 3VA2025-5HL36-0AA0 Certificate PDF catalog: Characteristic Get more product information Download with just a mouse click. FAQ. Manual Product note Software archive Technical data Siemens LV 10 2016/2017. Siemens AG 2016. Residual Current Protective Devices / Arc Fault Detection Devices (AFDDs). Introduction Overview Devices Page Application Standards Used in Non-residential Residential buildings buildings Industry 5SV RCCBs 4/4 Personnel, material and fire protection, as well IEC/EN 61008 . as protection against direct contact. 4. IEC/EN 62423. SIGRES with active condensation protection for use in harsh environments. Super resistant and selective versions 5SM3 RCCBs 4/10 Personnel, material and fire protection, as well IEC/EN 61008 . as protection against direct contact IEC/EN 62423. SIQUENCE 5SM3/5SU1 4/13 SIQUENCE, the technology of universal VDE 0664-100 -- . universal Current -sensitive Current -sensitive Residual Current Protective VDE 0664-200.

3 RCCBs, type B and type B+ Devices VDE V 0664-110. Additional components 4/18 Remote controlled mechanisms, auxiliary IEC/EN 62019 -- . switches for all Residual Current operated circuit breakers Leakage Current measurement device for fault locating and the optimum selection of RCCBs 5SM2 RC units 4/22 The freely selectable combination of RC units IEC/EN 61009 -- . with miniature circuit breakers permits the flexible configuration of RCBO combinations 5SU1 RCBOs 4/30 The ideal protection combination for all IEC/EN 61009 . electrical circuits due to the compact device versions of RCCBs and miniature circuit breakers in a single device 5SM6 AFD units 4/38 Enhanced fire protection through the detection IEC/EN 62606 -- and isolation of arcing faults 5ST busbars for modular 4/42 Busbars in 10 mm2 and 16 mm2 save space in -- . installation Devices the distribution board and time during mounting 5SM1 and 5SZ9 RCCB socket 4/45 For retrofitting in existing installations VDE 0664.

4 Outlets Accessories 4/46 Locking Devices , covers everything you need -- . for mounting 5SV8 Residual Current monitors Ch. 12 For monitoring of Residual currents in electrical IEC 62020 -- . plants with indication if a specified limit value is EN 62020. exceeded, see chapter "Monitoring Devices ". > Monitoring Devices for electrical values > Residual Current monitors". 4/2 Siemens LV 10 2016/2017. Siemens AG 2016. Residual Current Protective Devices / Arc Fault Detection Devices (AFDDs). Introduction SIGRES. Design Selection SIGRES RCCBs were developed for use in harsh ambient criterion conditions, such as swimming baths as protection against chlorine and ozone, in the agricultural sector (ammonia), on RCCB RCBO RC unit building sites and in the chemical industry (nitrogen oxide, sulfur dioxide, solvents), in the food processing industry (hydrogen sulfide) and in unheated rooms (dampness). The patented active condensation protection requires a continuous power Type Equipment, circuit , supply and bottom infeed if the RCCB is switched off.

5 Load Current , AC A F B. Residual Current When used in ambient conditions as defined in product 4. B+. standard EN 61008-1, the operation interval for pressing the test button can be extended to once a year. Version System, equipment, Super resistant ambient conditions K S SIGRES 500 V 50- 400 Hz Super resistant (short-time delayed) RCCBs meet the maximum permissible break times for instantaneous Devices . However, by implementing a short-time delay they prevent unnecessary Number of poles tripping operations, and thus plant faults, when pulse-shaped Equipment 1+N 2 3 3+N 4. leakage currents occur as is the case when capacitors are switched on. Rated Residual Current I n Selective protection objective Installation Can be used as upstream group switch for selective tripping Residual Current regulation contrary to downstream, instantaneous or short-time delayed protection VDE 0100-410. I n > 30mA Fire -530.

6 RCCBs. Additional -7xx protection Trip conditions protection Note: limited I n I n 300 mA -482. I n 30 mA VDS 3501. You will find further information on the subject of Residual Current Protective Devices in the technology primer " Residual Current Protective Devices ", Article No.: E10003-E38-2B-G0090-7600 Rated Current In Equipment and in the Configuration Manual " Residual Current Protective Devices /Arc Fault Detection Devices (AFDDs)" at: Only with RCBOs with Trip conditions acc. MCB characteristic to VDE 0100-410. B C D Equipment I201_15509b Selection aid for finding the appropriate Residual Current Protective device Siemens LV 10 2016/2017 4/3. Siemens AG 2016. Residual Current Protective Devices / Arc Fault Detection Devices (AFDDs). 5SV RCCBs Overview Benefits RCCBs are used in all systems up to 240/415 V AC. Devices of Instantaneous Residual Current operated circuit breakers with type AC trip in the event of sinusoidal AC Residual currents, the N connection on the left or right-hand side enable simple type A also trips in the event of pulsating DC Residual currents.

7 Bus mounting with standard pin busbars with miniature circuit breakers installed on the right-hand side. In addition, RCCBs type F also detect Residual currents with mixed frequencies up to 1 kHz. Instantaneous type A Devices have a surge Current withstand capability with Current waveform 8/20 s of more than 1 kA, RCCBs with a rated Residual Current of maximum 30 mA are super resistant of more than 3 kA and selective of more than used for personnel, material and fire protection, as well as for 5 kA. This ensures safe operation. 4. protection against direct contact. RCCBs with a rated Residual SIGRES has an extremely long service life due to a patented Current of 10 mA are primarily used in areas that represent an active condensation protection and identical dimensions increased risk for personnel. enable the quick and easy replacement of existing instanta- Since the introduction of DIN VDE 0100-410, all socket outlet neous RCCBs.

8 Current circuits up to 20 A must also be fitted with Residual Super resistant Devices increase system availability, as Current Protective Devices with a rated Residual Current of max. unnecessary tripping is prevented in power supply systems 30 mA. This also applies to outdoor electrical circuits up to 32 A with short-time glitches. for the connection of portable equipment. Selective RCCBs increase system availability as a staggered Devices with a rated Residual Current of maximum 300 mA are tripping time enables the selective tripping of RCCBs used as preventive fire protection in case of insulation faults. connected in series in the event of a fault. RCCBs with a rated Residual Current of 100 mA are primarily Auxiliary switches, fault signal contacts, undervoltage used outside Europe. releases or shunt trips are also available as additional components. By means of internal contacts, effective touch protection is provided when grasping and manually operating the latching slide.

9 To facilitate entry of pin busbars with connection cables up to 35 mm , the Devices are equipped with rectangular terminals for the accommodation of funnel-shaped cable entries. By means of standardized clearances of the terminals in modular width dimensions, the RCCBs and MCBs can be optionally connected to busbars on the top or on the bottom. 4/4 Siemens LV 10 2016/2017. Siemens AG 2016. Residual Current Protective Devices / Arc Fault Detection Devices (AFDDs). 5SV RCCBs Technical specifications Instantaneous SIGRES Super resistant Selective Standards IEC/EN 61008-1 (VDE 0664-10); IEC/EN 61008-2-1 (VDE 0664-11);. IEC/EN 61543 (VDE 0664-30); IEC/EN 62423 (VDE 0664-40). Surge Current withstand capability Type A Acc. to EN 60060-2 (VDE 0432-2) kA >1 >3 >5. with Current waveform 8/20 s Type F Acc. to EN 60060-2 (VDE 0432-2) kA -- -- >3 -- with Current waveform 8/20 s Minimum operational voltage for test function operation 30-mA Devices V AC 195.

10 4. Non-30-mA Devices V AC 100. 24 V Devices V AC 20. Test cycles 1/2 year 1 year 1/2 year Insulation coordination Overvoltage category III. Pollution degree 2. Terminal conductor cross-sections 1-wire - Solid ( 10 mm2) / stranded ( 16 mm2) mm2 .. 35. - Finely stranded with non-insulated end sleeve mm2 .. 25. - Finely stranded with insulated end sleeve mm2 .. 25. - Finely stranded without end sleeve mm2 1 .. 35. 2-wire, same cross-section, same conductor type - Solid ( 10 mm2) / stranded ( 16 mm2) mm2 .. 10. - Finely stranded with non-insulated end sleeve mm2 .. 4. - Finely stranded with insulated end sleeve mm2 .. 4. - Finely stranded without end sleeve mm2 1 .. 4. 1-wire + busbar (pin thickness mm). - Solid ( 10 mm2) / stranded ( 16 mm2) mm2 10 .. 25. - Finely stranded with non-insulated end sleeve mm2 6 .. 25. - Finely stranded with insulated end sleeve mm2 6 .. 16. Terminal tightening torque Up to In 80 A Nm At In = 100 A, 125 A Nm.