, NOTETHIS IS A STANDARD LEGEND SHEET, THEREFORE, SOME SYMBOLS MAYAPPEAR ON THIS SHEET THAT DO NOT APPEAR ON THE MECHANICAL ABBREVIATIONSWITHOUTWITHWATER PRESSURE DROPWATER GAUGEWIDTHVENT THROUGH ROOFVERTICALVELOCITYVOLUME DAMPERVOLTSTYPICALTOTAL STATIC PRESSURETEMPERATURESINGLE WIDTH SINGLE INLETSINGLE WALL PLENUMSTRUCTUR(E)(AL)STEELSTAINLESS STEELSQUARE INCH(ES)SQUARE FOOT(FEET)SQUARESPECIFICATIONSTATIC PRESSURESIMILARSENSIBLESECTIONSMOKE DAMPERSTANDARD CUBIC FEET PER MINUTESUPPLY AIRREVOLUTIONS PER MINUTERELATIVE HUMIDITYREVISIONRETURN AIR DAMPERRETURN AIRRADIUSPVC COATED STEELPOLYVINYL CHLORIDEPOUNDS PER SQUARE INCHPOLYPROPYLENEPHASEOUTSIDE AIRON CENTER DISTANCEOUTSIDE AIR DAMPERNORMALLY OPENNOT IN CONTRACTNORMALLY CLOSEDMOUNTEDMISCELLANEOUSMINIMUMMANUFAC TURERMECHANICALTHOUSAND BTU PER HOU

distribution, 1/2" outlet connection, time clock, solenoid valve and vacuum breaker, recessed stainless steel enclosure with door. based on: precision plumbing products primetime electronic trap primer, pts series 11 gallons acceptance volume 18 gallons tank volume based on: itt wta series gas water heater 285 cfh input, 120 gallon storage

Tags:

  Series, Steel, Valves, Solenoid, Stainless, Solenoid valves, Stainless steel

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of 2014 PIVOT ARCHITECTURE STANDARD MECHANICAL …

1 , NOTETHIS IS A STANDARD LEGEND SHEET, THEREFORE, SOME SYMBOLS MAYAPPEAR ON THIS SHEET THAT DO NOT APPEAR ON THE MECHANICAL ABBREVIATIONSWITHOUTWITHWATER PRESSURE DROPWATER GAUGEWIDTHVENT THROUGH ROOFVERTICALVELOCITYVOLUME DAMPERVOLTSTYPICALTOTAL STATIC PRESSURETEMPERATURESINGLE WIDTH SINGLE INLETSINGLE WALL PLENUMSTRUCTUR(E)(AL)STEELSTAINLESS STEELSQUARE INCH(ES)SQUARE FOOT(FEET)SQUARESPECIFICATIONSTATIC PRESSURESIMILARSENSIBLESECTIONSMOKE DAMPERSTANDARD CUBIC FEET PER MINUTESUPPLY AIRREVOLUTIONS PER MINUTERELATIVE HUMIDITYREVISIONRETURN AIR DAMPERRETURN AIRRADIUSPVC COATED STEELPOLYVINYL CHLORIDEPOUNDS PER SQUARE INCHPOLYPROPYLENEPHASEOUTSIDE AIRON CENTER DISTANCEOUTSIDE AIR DAMPERNORMALLY OPENNOT IN CONTRACTNORMALLY CLOSEDMOUNTEDMISCELLANEOUSMINIMUMMANUFAC TURERMECHANICALTHOUSAND BTU PER HOURMAXIMUMLEAVING WATER TEMPERATURELEAVING WET BULBLEAVINGLEAVING FLUID TEMPERATURELINEAR FEETLEAVING DRY

2 BULBPOUNDLEAVING AIR TEMPLENGTHKILOWATT HOURKILOWATTISOLAT(OR)(ION)INSULATIONINC H(ES)INVERT ELEVATIONHEATINGHORSEPOWERHORIZONTALHEIG HTGALLONS PER MINUTEGALLONS PER HOURGLYCOLGALVANIZEDGALLONGAGE/GAUGEFACE VELOCITYFUTUREFIXTURE UNITFEET/FOOTFEET PER SECONDFEET PER MINUTEFLUID PRESSURE DROPFLEXIBLEFILTERFIGUREFORWARD CURVEDDEGREES FAHRENHEITEXPANSIONEXISTINGEXHAUSTEXTRAC TORENTERING WATER TEMPERATUREENTERING WET BULBEXTERNAL STATIC PRESSUREEQUIPMENTEQUALENGINEERELEVATIONE LECTRIC(AL)ENTERING FLUID TEMPERATUREEFFICIENCYENTERING DRY BULBENTERING AIR TEMPERATUREEXHAUST AIR DAMPEREXHAUST AIRDRAWINGDOUBLE WIDTH DOUBLE INLETDEW POINTDOWNDEFLECTIONDIRECT DIGITAL CONTROLCENTERLINECONTINUE(ED)(UATION)CON NECT(ION)CONCRETECEILING OR COOLINGCUBIC FEET PER SECONDCUBIC FEET PER MINUTECUBIC FEET PER HOURBRITISH THERMAL UNITS PER HOURBRITISH THERMAL UNITBASEMENTBUILDINGBACKWARD INCLINEDBACKDRAFT DAMPERAUTOMATICARCHITECT(URAL)

3 APPROXIMATELYAIR PRESSURE DROPALUMINUMALTERNATIVEAPPARATUS HOUSING PLENUMABOVE FINISHED FLOORAIRFOILW/OW/WPDWGWVTRVERTVELVDVTYPT SPTEMPSWSISWPSTRUCTSTLSSSQ INSFSQSPECSPSIMSENSSECTSDSCFMSARPMRHREVR ADRAR (RAD)PVSPVCPSIPPPHOSAOCOADNONICNCMTDMISC MINMFRMECHMBHMAXLWTLWBLVGLFTLFLDBLBLATLK WHKWISOLINSULINIEHTGHPHORIZHGPMGPHGLYGAL VGALGAFVFUTFUFTFPSFPMFPDFLEXFILTFIGFCFEX PEXISTEXHEXEWTEWBESPEQUIPEQENGRELEVELECE FTEFFEDBEATEADEADWGDWDIDPDNDEFLDDCCLCONT CONNCONCCLGCFSCFMCFHBTUHBTUBSMTBLDGBIBDD AUTOARCHAPPROXAPDALALTAHPAFFAFVFDVARIABL E FREQUENCY DRIVEFTRFINNED TUBE RADIATORINSIDE(DIAMETER/DIMENSION)IDWATE R TEMPERATURE RISEWATER TEMPERATURE DROPWTRWTDMISC.

4 valves & COCKSDCVADOUBLE CHECK VALVE ASSEMBLYGROUND HYDRANTGHGSHUT-OFF VALVEGLOBE VALVESHUT-OFF VALVE W/ TAMPER SWITCHTRIPLE DUTY VALVECHECK VALVE2-WAY CONTROL VALVE3-WAY CONTROL VALVEPRESSURE REDUCING VALVEBALANCING VALVEFLOW CONTROL VALVESOLENOID VALVERELIEF VALVEAIR VENT (MANUAL/AUTOMATIC)STRAINERSTRAINER W/ BLOWDOWNDRAIN VALVEWALL HYDRANTSTEAM TRAPPRESSURE GAUGEPRESSURE/TEMPERATURE TEST PLUGTHERMOMETERFLOW SWITCHTEMPERATURE TRANSMITTERSHOCK ARRESTORVACUUM BREAKERWATER FLOW METERREDUCED PRESSURE BACKFLOW ASSEMBLYDOUBLE CHECK DETECTOR ASSEMBLYBACKWATER VALVEUNDERGROUND GATE VALVE W/BOXUNDERGROUND GATE W/POST INDICATOROUTSIDE SCREW & YOKEY PATTERN BOILER BLOWDOWN VALVENON-RETURN STOP VALVEQUICK OPENING BOILER BLOWDOWN VALVEDVAAVMAVSFCSHOSE BIBBHBWHFT(SIZE)

5 SVWFMRPBADCDABWVUGPIVF&T/IBSPECIALTY PIPINGNPWNPWNON-POTABLE WATERMISC. FITTINGS & SYMBOLSMCMECHANICAL COUPLINGBALL JOINTFLEXIBLE CONNECTIONTEE DOWNTEE UPELBOW DOWNELBOW UPRISERPLUG OR BLIND FLANGECAPFLANGED CONNECTIONUNIONJOINT OR COUPLING POINTCROSSTEEELBOW (45 )ELBOW (90 )ANCHORREDUCERPIPE SLEEVEDIRECTION OF SLOPEDIRECTION OF FLOWHORIZONTAL TEEPIPING CONNECTIONSPLUMBING PIPING(ABOVE GRADE OR FLOOR)(BELOW GRADE OR FLOOR)(ABOVE GRADE OR FLOOR)(BELOW GRADE OR FLOOR)(ABOVE GRADE OR FLOOR)(BELOW GRADE OR FLOOR)PUMPED WASTESTORM DRAINOVERFLOW DRAIN(BELOW GRADE OR FLOOR)WASTE(ABOVE GRADE OR FLOOR)

6 ICWGVMGGWWRHTWRTWHTWPWPWSDSDODODHTWRTWRH TWWWGMGODODSDSDPWPWDGVICWRHWCWVHWDWWGAS VENTNATURAL GAS (MEDIUM PRESSURE)NATURAL GAS (LOW PRESSURE)INDUSTRIAL COLD WATERWELL WATERRECIRCULATING TEMPERED WATER140 RECIRCULATING HOT WATER140 HOT WATERRECIRCULATING HOT WATERCOLD WATERVENTHOT WATEROVERFLOW DRAINDRAIN (CONDENSATE/INDIRECT)STORM DRAINPUMPED WASTEWASTEWWPLUMBING SYMBOLSTRENCH DRAINOVERFLOW DRAINROOF DRAINFLOOR SINKCATCH BASINAREA DRAINFLOOR DRAINCLEANOUT TO GRADEFLOOR CLEANOUTWALL CLEANOUTCLEANOUTTHRUST BLOCKCOTBWCOFCOCTGFDADCBFSRDODTDSYMBOLSR ELOCATE EXISTINGREMOVE EXISTINGCONNECT TO EXISTINGCAP EXISTING / CAP FOR FUTURENOTEEXISTING TO REMAINACCESS PANELBELOW GRADE / FLOORABCEKRX1(ABOVE GRADE OR FLOOR)(BELOW GRADE OR FLOOR)GREASE WASTEGWGWGWGWGREASE WASTEPROPPROPPROPANE GAS(SEE SPECS FOR TYPE REQUIRED)REVISIONS:CHECKED:PROJECT #:ISSUE DATE:DRAWN.

7 PRINTED ON:2014 PIVOT ARCHITECTUREFROM FILE:C9/12/2014 4:22:26 PMC:\Revit Local Files\13-1532_HES MEP14\13-1532_HES , LEGENDS ANDABBREVIATIONS - PLUMBINGEUGENE SCHOOL DISTRICTBUILDING AND SITE CONSTRUCTION DOCUMENTSHOWARD ELEMENTARY SCHOOL133609/23/2014P001 TJLCJB700 HOWARD AVE, EUGENE, OREGON 97404 PLUMBING EQUIPMENT SCHEDULEHWCWVWITEMDESCRIPTIONROUGH-IN SIZE (INCHES)NOTESELECTRICALITEMDESCRIPTIONNP WNOTESROUGH-IN SIZE (INCHES)DESCRIPTIONITEMWCWHWGNOTES:PLUMB ING FIXTURE SCHEDULEPLUMBING DESIGN CRITERIAKITCHEN EQUIPMENT CONNECTION SCHEDULEWC-1 WATER CLOSET42-1-1/4 BASED ON: LEONARD NEW GENERATION MIXING VALVE120 F OUTLET TEMPERATURE23 GPM FLOW RATE, WITH 5 PSI LOSSMASTER MIXING VALVE140 F INLET TEMPERATUREMMV-101 RHWP-101 RECIRCULATING HOT WATER PUMPIN-LINE CENTRIFUGAL PUMP5 GPM @ 25 FT HEAD1/6 HP120 V, 1 PH-DET-101 DOMESTIC WATER EXPANSION TANK-BASED ON.

8 BELL & GOSSETT PL SERIESTP-1 ELECTRONIC TRAP PRIMER1-20 OPENING MANIFOLD CALIBRATED FOR EQUAL WATERDISTRIBUTION, 1/2" OUTLET CONNECTION, TIME CLOCK, SOLENOIDVALVE AND VACUUM BREAKER, RECESSED stainless STEELENCLOSURE WITH ON: PRECISION PLUMBING PRODUCTS PRIMETIMEELECTRONIC TRAP PRIMER, PTS SERIES11 GALLONS ACCEPTANCE VOLUME18 GALLONS TANK VOLUMEBASED ON: iTT WTA SERIESGAS WATER HEATER285 CFH INPUT, 120 GALLON STORAGEBASED ON: LOCHINVAR SHIELDGWH-101332 GPH RECOVERY @ 100 F RISETHRURHTWP-101 RECIRCULATING HOT WATER PUMPIN-LINE CENTRIFUGAL GPM @ 20 FT HEADBASED ON: BELL & GOSSETT PL SERIES1/12 HP120 V, 1 PH120 V, 1 PH120 V, 1 PHSECTION C402 "PIPE SIZING".

9 EQUIVALENT LENGTH OF PIPE: FT (MPG), FT (G)BASIS OF DESIGN: 2010 OREGON MECHANICAL SPECIALTY CODE, APPENDIX C, "FUEL GAS",NATURAL GAS SYSTEMNOTED AND A RAINFALL RATE OF " PER DRAIN PIPING SIZED AT 1/8" PER FT SLOPE UNLESS OTHERWISEBASIS OF DESIGN: 2011 OREGON PLUMBING SPECIALTY CODE, CHAPTER 11 "STORM DRAINAGE".ROOF DRAIN/STORM DRAIN PIPING SYSTEMSALL WASTE PIPING SIZED AT %%1331/4" PER HR UNLESS OTHERWISE OF DESIGN: 2011 OREGON PLUMBING SPECIALTY CODE, CHAPTER 7 "SANITARY DRAINAGE".WASTE AND VENT PIPING SYSTEMBASIS OF DESIGN: 2011 OREGON PLUMBING SPECIALTY CODE, APPENDIX A "RECOMMENDED RULES FORDOMESTIC WATER PIPING SYSTEMSIZING THE WATER SUPPLY SYSTEM".

10 PIPING SIZED ON 3 PSI/100 FT. DROP, VELOCITIES NOT TO EXCEED8 FT/SEC. (COLD WATER) AND NOT TO EXCEED 5 FT/SEC. (HOT WATER).-TP-11(DOMESTICSYSTEM)(DOMESTICSY STEM)(DOMESTICSYSTEM)(DOMESTICSYSTEM)(KI TCHENSYSTEM)340 GPM @ 13 PSIG LOSSDOUBLE CHECK VALVE ASSEMBLYBASED ON: FEBCO XXX (4")DCVA-1(BUILDINGSUPPLY)-20 GPM @ 12 PSIG LOSSREDUCED PRESSURE BACKFLOW ASSEMBLYBASED ON: FEBCO 860 (1-1/4")RPBA-3(RWSSYSTEM)-RWTS-101 RAINWATER PUMP/FILTER SKID SYSTEM:PREPACKAGED SKID BASED ON FLOW THERM MODEL FTSS-RW-UVVIBRATION ISOLATION: TYPE 5, 2"MIN. CONNECTIONS AND CONTROLS BY WATER RECLAMATION STORAGE TANK540 GALLON CAPACITY48"DIAMETER x 86-1/2"TALL,17"DIAMETER ACCESS WAYBASED ON: POLYPROCESSING-RWTS-101 RAIN WATER HYPO TREATMENT:DUPLEX CHEMICAL FEED PUMPSSIMPLEX MAGNETIC DRIVE RECIRCULATION PUMP WITH NEMA 4 OF DESIGN: WATER CONTROL CORP.