2014 Standard for Performance Rating of Variable ...

AHRI Standard 1230 with Addendum 1. 2014 Standard for Performance Rating of Variable Refrigerant Flow (VRF) Multi-split Air-conditioning and Heat Pump Equipment AHRI Standard 1230-2014 WITH. ADDENDUM 1, Performance Rating of Variable Refrigerant Flow (VRF). Multi-split Air-conditioning and Heat Pump Equipment September 2017. Addendum 1 (dated June 2017) of AHRI Standard 1230-2014, changes AHRI Standard 1230-2014 as follows. Changes have been incorporated (additions are shown by shading and deletions are shown by strikethroughs) into the already published version of ANSI/AHRI Standard 1230-2010 with Addenda 1 and 2 that is now designated AHRI Standard 1230- 2014.

3.14.6 A cooling mode expansion device 3.14.7 External cabinetry 3.15 Indoor Unit Model Family.A model family constituting exclusively of the following types of Non-ducted Indoor Units. 3.15.1 Ceiling suspended.A non-ducted indoor unit that is totally encased and is suspended below the ceiling.

Tags:

  Unit, Ducted

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of 2014 Standard for Performance Rating of Variable ...

1 AHRI Standard 1230 with Addendum 1. 2014 Standard for Performance Rating of Variable Refrigerant Flow (VRF) Multi-split Air-conditioning and Heat Pump Equipment AHRI Standard 1230-2014 WITH. ADDENDUM 1, Performance Rating of Variable Refrigerant Flow (VRF). Multi-split Air-conditioning and Heat Pump Equipment September 2017. Addendum 1 (dated June 2017) of AHRI Standard 1230-2014, changes AHRI Standard 1230-2014 as follows. Changes have been incorporated (additions are shown by shading and deletions are shown by strikethroughs) into the already published version of ANSI/AHRI Standard 1230-2010 with Addenda 1 and 2 that is now designated AHRI Standard 1230- 2014.

2 The changes are to the inside front cover, scope of the VRF certification program, and sections listed below. Section 3. Definitions All terms in this document shall follow the Standard industry definitions established in the current edition of ASHRAE. Terminology of Heating, Ventilation, Air Conditioning and Refrigeration, unless otherwise defined in this section. All terms in this document will follow the Standard industry definitions in the ASHRAE Terminology website ( ) unless otherwise defined in this section. Standard Air. Air weighing lb/ft3 [ kg/m3] which approximates dry air at 70 F [21 C] and at a barometric pressure of in Hg [ kPa]. Airflow Setting(s).

3 Programmed or wired control system configurations that control a fan to achieve discrete, differing ranges of airflow often designated for performing a specific function ( , cooling, heating, or constant circulation) without manual adjustment other than interaction with a user-operable control ( , a thermostat) that meets the manufacturer specifications for installed-use. For the purposes of this Standard , manufacturer specifications for installed-use are those found in the product literature shipped with the unit . Multi-Split Air-Conditioner. An encased, factory-made assembly or assemblies designed to be used as permanently installed equipment to provide conditioned air to an enclosed space(s).

4 It includes a prime source of refrigeration for cooling and dehumidification and may optionally include other means for heating, humidifying, circulating and cleaning the air. It normally includes multiple evaporator(s), compressor(s), and condenser(s). Such equipment may be provided in more than one assembly, the separated assemblies of which are intended to be used together. Nominal Capacity. The capacity value of the outdoor units published by the manufacturer in their catalogue or Engineering Data. Nominal Capacity may be referred to using the following terms: Nominal Cooling Capacity. The Nominal Cooling Capacity shall not be more that 105% of the rated cooling capacity.

5 The Nominal Cooling Capacity of each Indoor unit shall be the published capacity when the ratings are first established, and shall not be changed upon subsequent publications. Nominal Heating Capacity. Nominal Capacity in heating mode. Rated Capacity. The capacity achieved at the Standard Rating Conditions in Btu/h. ducted Systems. A multi-split air conditioner or Heat Pump system with only Indoor Units designed to be permanently installed and deliver all conditioned air through ductwork. Ground-Water Heat Pump. Water-to-air heat pump using water pumped from a well, lake, or stream functioning as a heat source/heat sink. The temperature of the water is related to the climatic conditions and may vary from 41 to 77 F [5 to 25 C] for deep wells.

6 Ground-Loop Heat Pump. Brine-to-air heat pump using a brine solution circulating through a subsurface piping loop functioning as a heat source/heat sink. The heat exchange loop may be placed in horizontal trenches, vertical bores, or be submerged in a body of surface water. (ANSI/ARI/ASHRAE ISO Standard 13256-1:1998) The temperature of the brine is related to the climatic conditions and may vary from 23 to 104 F [ 5 to 40 C]. Multi-Split Heat Pump. One or more factory-made assemblies designed to be used as permanently installed equipment to take heat from a heat source and deliver it to the conditioned space when heating is desired. It may be constructed to remove heat from the conditioned space and discharge it to a heat sink if cooling and dehumidification are desired from the same equipment.

7 It normally includes multiple indoor conditioning coils, compressor(s), and outdoor coil(s). Such equipment may be provided in more than one assembly, the separated assemblies of which are intended to be used together. The equipment may also provide the functions of cleaning, circulating and humidifying the air. Heat Pump. A kind of central air conditioner that utilizes an indoor conditioning coil, compressor, and refrigerant-to- outdoor air heat exchanger to provide air heating, and may also provide air cooling, air dehumidifying, air humidifying, air circulating, and air cleaning. Heating Coefficient of Performance (COPH). A ratio of the Heating Capacity in watts to the power input values in watts at any given set of Rating Conditions expressed in W/W.

8 For heating COP, supplementary resistance heat shall be excluded. Heating unit . A component of a VRF Multi-Split System air conditioner or heat pump that is designed to transfer heat between the refrigerant and the indoor air, and which consists of an indoor coil, a cooling mode expansion device, an air moving device, and a temperature sensing device. Mini-Split Air-Conditioners and Heat Pumps. Systems that have a single outdoor section and one or more indoor sections. The indoor sections cycle on and off in unison in response to a single indoor thermostat (As defined by DOE, See Appendix C, Paragraph ). Multiple-Split Air-Conditioners and Heat Pumps [ .Multi-Split Air Conditioners and Heat Pumps].

9 Systems that have two or more indoor sections. The indoor sections operate independently and can be used to condition multiple zones in response to multiple indoor thermostats (As defined by DOE, See Appendix C, Paragraph ). Indoor unit . A separate assembly of a Split System (a service coil is not an Indoor unit ) that includes the features listed in Sections , , , and ; and may or may not include the features listed in Sections , , and An arrangement of refrigerant-to-air heat transfer coil(s) for transfer of heat between the refrigerant and the indoor air A condensate drain pan An air temperature sensing device An integrated indoor blower ( a device to move air including its associated motor).

10 A separate designated air mover that may be a furnace or a modular blower may be considered to be part of the Indoor unit . Sheet metal or plastic parts not part of external cabinetry to direct/route airflow over the coil(s). A cooling mode expansion device External cabinetry Indoor unit Model Family. A model family constituting exclusively of the following types of Non- ducted Indoor Units. Ceiling suspended. A non- ducted indoor unit that is totally encased and is suspended below the ceiling. Floor-mounted. A non- ducted Indoor unit intended for being installed at floor level either enclosed in the wall space in an uncased configuration or extended out from the wall in a cased configuration.