30 mm Push Button Specifications Technical Data

Technical DataOriginal Instructions30 mm Push Button SpecificationsBulletin Numbers 800T, 800 HTo p i cP a g eSpecifications3 Assembled Stations6 Emergency Stop Devices (Trigger Action)7 Push Button Devices9 Selector Switch Devices13 Pilot Light Devices22 Push-pull and Push-pull/Twist Release Devices24 Specialty Devices28 Custom-Built Stations/Enclosures38 Accessories40 Approximate Dimensions62800H General-purpose Enclosures752 Rockwell Automation Publication 800-TD009D-EN-P - July 2020 Summary of ChangesThis publication contains the following new or updated information.

Electrical design lifecycles: 1,000,000 (at max rated load) Explosion-protected Contacts • Maximum thermal continuous current Ith = 10 A • Minimum low-energy switching load: 17V DC, 5 mA • Electrical design lifecycles: 1,000,000 (24V DC, 25 mA) • Vibration: 5 g, 0.7 mm peak-to-peak displacement, sine sweep 10…2000 Hz / IEC 60068-2-6

Tags:

  Design

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of 30 mm Push Button Specifications Technical Data

1 Technical DataOriginal Instructions30 mm Push Button SpecificationsBulletin Numbers 800T, 800 HTo p i cP a g eSpecifications3 Assembled Stations6 Emergency Stop Devices (Trigger Action)7 Push Button Devices9 Selector Switch Devices13 Pilot Light Devices22 Push-pull and Push-pull/Twist Release Devices24 Specialty Devices28 Custom-Built Stations/Enclosures38 Accessories40 Approximate Dimensions62800H General-purpose Enclosures752 Rockwell Automation Publication 800-TD009D-EN-P - July 2020 Summary of ChangesThis publication contains the following new or updated information.

2 This list includes substantive updates only and is not intended to reflect all p i cP a g eUpdated Custom-Built Stations/Enclosures section38 Updated Contact Blocks section40 Added Contact Block Code Descriptions Traditional Type41 Added Contact Block Code Descriptions Modular Type43 Added descriptive text under Universal LED Module heading44 Updated 800T/H Pilot Light Color Caps table 45 Updated Push Button Color Caps, Non-Illuminated table 46 Updated Miscellaneous table50 Updated Table 33 and Table 3454 Updated Table 3454 Updated Specialty Legend Plates table56 Updated Contact Blocks (Bulletin 800T Only) and Contact Blocks (Bulletin 800H Only)65 Updated Pilot Light and Illuminated Devices (Bulletin 800T Only) dimension table68 Updated Enclosures (Bulletin 800T Only)

3 Section, Table 41, and Table 4372 Rockwell Automation Publication 800-TD009D-EN-P - July 20203 SpecificationsIMPORTANTP erformance data that is given in this publication is provided only as a guide for you to determine suitability and do not constitute a performance warranty of any kind. Such data may represent the results of accelerated testing at elevated stress levels, and you are responsible for correlating the data to actual application requirements. ALL WARRANTIES AS TO ACTUAL PERFORMANCE, WHETHER EXPRESS OR IMPLIED, ARE EXPRESSLY 1 - Electrical RatingsAttributeBulletin 800T and 800 HContact ratingsSee the contact ratings tables on page strength2200V for 1 minute, 1300V for 1 minute (Logic Reed)Table 2 - Mechanical RatingsAttributeBulletin 800T and Hz, in.

4 ( mm) displacement (peak-to-peak) max/10 G max (except Logic Reed)Shock1/2 cycle sine-wave for 11 ms 25 g (contact fragility) and no damage at 100 gDegree of protectionType 1/4/12/13 (800T); Type 1/4/4X/12/13 (800H); EN/IEC 60529 IP66/65 Mechanical design lifecycles, minPush buttonsMomentary, non-illuminated, flush, and extended head10,000,000 Momentary, illuminated250,000 Push-pull/twist-to-release250,000 (1)(1)Illuminated trigger action E-stops are rated for 150,000 minimum mechanical operations when using Cat. No. 800TC-XD4S self-monitoring contact blocks (SMCBs).

5 Selector switchesNon-illuminated1,000,000 Illuminated, key-operated200,000 Potentiometers25,000 All other devices200,000 Contact block operationShallow, mini, and low-voltageSlow, double make and breakLogic reed and sealed switchSingle break magneticWire gauge/terminal screw torque# AWG (# MaxDuty) / lb inTypical Operating ForcesOperators without Contact Blocks Flush, extended Button , standard mushroom, jumbo plastic mushroom: 2 lb max Jumbo and extended aluminum mushroom head: lb max Maintained selector switch: in lb maxSpring-return Selector in lb to stop, in lb to returnIlluminated Push Buttons and Push-to-test Pilot Lights5 lb max2-position lb max push or pull3-position Push-pull8 lb max push to in position or pull to center position (15 lb max pull to out position)Twist-to-release or Push-pull9 lb max push or pull 30 in oz max twist, 6 in oz min returnPotentiometerRotational torque in oz; stopping torque 12 in lb (min)Contact BlocksStandard1 lbLogic Reed and Stackable Sealed Switch1 lb maxSealed Switch3 lb max at in.

6 ( mm) plunger travelMaxDuty and PenTUFF lb lb4 Rockwell Automation Publication 800-TD009D-EN-P - July 2020 SpecificationsStandards Compliance and CertificationsContact RatingsUse the following tables to verify that the ratings meet the needs of your Contacts Minimum: 24V, 24 mA Maximum thermal continuous current Ith 10 A A DC. Bulletin 800T units with 800T-XA contacts have ratings as follows:Electrical design lifecycles: 1,000,000 (at max rated load)Explosion-protected Contacts Maximum thermal continuous current Ith = 10 A Minimum low-energy switching load: 17V DC, 5 mA Electrical design lifecycles: 1,000,000 (24V DC, 25 mA) Vibration: 5 g, mm peak-to-peak displacement, sine sweep Hz / IEC 60068-2-6 Shock: 15 g (800H-TFRX_ trigger action E-stops), 50 g (all other devices) / IEC 60068-2-27 Bulletin 800T units with 800TC-XAF contacts have ratings as follows:Sealed Switch Contacts Minimum.

7 5V, 1 mA Maximum continuous current Ith 5 A. Bulletin 800T units with sealed switch contact blocks have ratings as follows:Table 3 - Environmental RatingsAttributeBulletin 800T and 800 HTemperature RangeOperating (1) +131 F ( +55 C) +185 F ( +85 C) RH from F ( C) per Procedure IV of MIL-STD-810C, Method cycling test(1)Operating temperatures below freezing are based on the absence of moisture and liquids. Consult your local Rockwell Automation sales office or Allen-Bradley distributor for use in lower temperature 4 - Materials Used in Bulletin 800H Type 4X OperatorsMaterialWhere UsedThermoplastic Polyester(Fiberglass Reinforced)Bushings, mounting rings, and socketsTransparent Amorphous NylonPilot light lens cap and illuminated Button capsMineral-filled NylonTrim washerThermoplastic PolyesterNon-illuminated Button capsGlass-filled Crystalline NylonThrust washerNitrile (Synthetic Rubber)

8 Gaskets and internal sealsStandards ComplianceUL 508, CCCC ertifications UL Listed (File No. E14840, E10314 Guide No. NKCR, NOIV, NISD) CSA Certified (File No. LR1234, LR11924) CSA , No. 14 CE Marked (EN/IEC 60947-5-1, EN/IEC 60947-5-5, EN ISO 13850)Max Operational Volts UeUtilization CategoryRated Operating CurrentsIECNEMAV olts UeMakeBreakAC A60 A720VA720VA10 ADC (1)(1)For applications below 17V/5 mA, PenTUFF or Logic Reed contacts are AMax Operational Volts UeUtilization CategoryRated Operating CurrentsIECNEMAV olts UeMakeBreakAC A60 A720VA720VA10 ADC AMax Operational Volts UeUtilization CategoryRated Operating CurrentsIECNEMAV olts UeMakeBreakAC A360VA3 ADC ARockwell Automation Publication 800-TD009D-EN-P - July 20205 SpecificationsStackable Sealed Switch Contacts Minimum: 5V, 10 mA (digital); 24V, 1 mA (analog) Maximum continuous current Ith A.

9 Bulletin 800T units with stackable sealed switch contact blocks have ratings as follows:Logic Reed Contacts Minimum DC: 5V, 1 mA Maximum DC: 30V, A, AC: 150V, A Only used with resistive loads. Electrical design lifecycles: 200,000 (at max rated load)PenTUFF (Low Voltage) Contacts Minimum DC: 5V, 1 mA Maximum thermal continuous current Ith A A DC. Bulletin 800T units with 800T-XAV contacts have ratings as follows:Snap Action ContactsBulletin 800T units with snap action contact blocks have ratings as follows:MaxDuty Contact Ratings Maximum thermal continuous current Ith 24 A.

10 Pilot Duty 120V AC, 12 A; 24V DC, 10 A Motor Ratings 120V AC, Hp; 240V AC, 3 Hp; 24V DC, 10 A FLA/60 A LRATime Delay ContactsBulletin 800T units with time delay contact blocks have ratings as follows:Adjustment range: s 25% Ith = 5 AMax Operational Volts UeUtilization CategoryRated Operating CurrentsIECNEMAV olts UeMakeBreakAC ADC AMax Operational Volts UeUtilization CategoryRated Operating CurrentsIECNEMAV olts UeMakeBreakAC ADC AMax Operational Volts UeContact Rating DesignationRated Operating CurrentsVolts UeMakeBreakAC A720VA10 ADC 250 AIMPORTANTThis device is not rated for DC Operational Volts UeContact Rating DesignationRated Operating CurrentsVolts UeMakeBreakAC 120B1501203600VA360VA6 Rockwell Automation Publication 800-TD009D-EN-P - July 2020