Example: bankruptcy

40RS Series - beneair.com

' . 40rs Series Packed Chilled Water Air Handling Unit 72,500-503,000 BTUH. World's Air Conditioning Expert 40rs Series Only the 40rs Series offers you Versatility Full line of packaged unit tons. Choice of air discharge arrangements Free blow or with ductwork Adaptability Ceiling suspended or floor mounted Attractive appearance for use in the space Fits existing 2- or 4 pipe systems Dependable Carrier Quality Efficient coil surface Rugged modular construction Quiet, belt-drive centrifugal fans 40rs Series - The industry's most complete line of packaged chilled water air handling unit Specify Carrier 40rs Series packaged chilled water The smooth finish baked enamel cabinets are air handling units for commercial in-the-space fabricated of rugged. Heavy-gage galvanized steel. application in factories warehouses offices or stores Belt-drive centrifugal fans move large volumes of air if a source of chilled water is available, you can't quietly and efficiently may be sued with ductwork or afford to overlook the versatile packaged units of the for free blow (direct discharge) into the conditioned 40rs Series .

40RS Series Only the 40RS Series offers you Specify Carrier 40RS Series packaged chilled water air handling units for commercial in-the-space application in …

Tags:

  Series, 40rs series, 40rs

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of 40RS Series - beneair.com

1 ' . 40rs Series Packed Chilled Water Air Handling Unit 72,500-503,000 BTUH. World's Air Conditioning Expert 40rs Series Only the 40rs Series offers you Versatility Full line of packaged unit tons. Choice of air discharge arrangements Free blow or with ductwork Adaptability Ceiling suspended or floor mounted Attractive appearance for use in the space Fits existing 2- or 4 pipe systems Dependable Carrier Quality Efficient coil surface Rugged modular construction Quiet, belt-drive centrifugal fans 40rs Series - The industry's most complete line of packaged chilled water air handling unit Specify Carrier 40rs Series packaged chilled water The smooth finish baked enamel cabinets are air handling units for commercial in-the-space fabricated of rugged. Heavy-gage galvanized steel. application in factories warehouses offices or stores Belt-drive centrifugal fans move large volumes of air if a source of chilled water is available, you can't quietly and efficiently may be sued with ductwork or afford to overlook the versatile packaged units of the for free blow (direct discharge) into the conditioned 40rs Series .

2 Space. These attractive united are available in 8 popular Yes, if you're looking for the most in versatility and sizes. Covering the 2,450-14,800 Cfm range with operating performance in packaged chilled water air nominal cooling capacities from 61/2-30 tons. Floor handling units. Look to the 40rs Series . From mounted or ceiling suspended. 40rs units are real Carrier of course. space savers. Their narrow width (less than 3-ft). makes them easy to get into existing spaces. Cooling coils are constructed of copper tubes with mechanically corrugate fins. Offering efficient high heat transfer surface that's built with years of dependable service in mind. 2. Physical data Description Packaged Chilled Water Air Handling Unit Model 40RS006 40RS006S 40RS080 40RS100 40RS120 40RS140 40RS160 40RS240 40RS280 40RS340. Operating Weight kg. 73 75 204 213 262 265 371 384 560 580. Nominal Capacity** BTUH 72,500 91,000 118,800 144,200 159,000 201,000 249,000 335,000 422,000 503,000. Cooling Coil 3-13 4-13 Total Face Area sq.

3 Ft. * * * *. Upper Coil sq. ft. - - - - - - - - Lower Coil sq. ft. - - - - - - - - Air Quantity Range CFM 1600-2450 1400-2450 2320-3850 2320-3850 3150-5250 3150-5250 4880-8150 5230-8700 6580-10950 7850-13100. Fan Fan in. Shaft Dia. mm. - - 25 25 30 30 30 30 35 35. Speed Range rpm - - 600-1900 600-1900 500-1500 500-1500 400-1200 400-1200 300-1000 300-1000. Standard Speed rpm 950 950 700 795 625 700 640 720 725 725. Standard Fan Pulley - - 250-1B-25 225-1B-25 280-1B-30 250-1B-30 280-1B-30 250-1B-30 250-2B-35 250-2B-35. Standard Motor Pulley - - 125-1B-24 125-1B-24 125-1B-28 125-1B-28 125-1B-28 125-1B-28 125-2B-28 125-2B-28. Standard - - Fan Motor Range Hp. 3/4 1-3 2-5 Standard Hp. 3/4 3/4 2 2 3 3 5 5 Speed rpm 950 950 1400 1400 1400 1400 1440 1440 1450 1450. V/Ph/Hz 220/1/50 220/1/50 380/3/50 380/3/50 380/3/50 380/3/50 380/3/50 380/3/50 380/3/50 380/3/50. Starter Type Only or Star-Delta Insulation Thermal Coetificient K W/m deg K. PE. Foam Thickness mm. 10. Air Filters in. or 16x25x2 or 16x25x2 or 20x25x2 or 20x25x2.

4 Connection 1 each 2 each Water Supply Pipe in. 1 FPT 1 FPT 1 1/4 MPT 1 1/4 MPT 1 1/4 MPT 1 1/4 MPT 1 1/2 MPT 1 1/2 MPT 1 1/2 MPT 1 1/2 MPT. Water Return Pipe in. 1 FPT 1 FPT 1 1/4 MPT 1 1/4 MPT 1 1/4 MPT 1 1/4 MPT 1 1/2 MPT 1 1/2 MPT 1 1/2 MPT 1 1/2 MPT. Condensate Pipe in. 3/4 FPT 3/4 FPT 3/4 MPT 3/4 MPT 3/4 MPT 3/4 MPT 1 MPT 1 MPT 1 1/4 MPT 1 1/4 MPT. FPT - Female Pipe Thread * Two seperate coils assembled as one unit, face split into an upper and lower section. MPT - Male Pipe Thread ** Nominal capacity base on air ent 80 Fdb-67 Fwb, ent-lvg water temp. 44/54 F, MAR. AIRFLOW. 3. Coil connection / . (RH) . / . (RH).. (Return Air) (Return Air). 1" ' .. Water pressure drop 40RS006 40RS006S 40RS080 40RS100 40RS120 40RS140 40RS160 40RS240 40RS280 40RS340. GPM FT GPM FT GPM FT GPM FT GPM FT GPM FT GPM FT GPM FT GPM FT GPM FT. 6 8 10 16 17 16 24 32 35 45 7 9 12 18 19 18 27 36 40 50 8 10 14 20 21 20 30 40 45 55 9 11 16 22 23 22 33 44 50 60 10 12 18 24 25 24 36 48 55 65 11 13 20 26 27 26 39 52 60 70 12 14 22 28 29 28 42 56 65 75 13 15 24 30 31 30 45 60 70 80 14 16 26 32 33 32 48 64 75 85 15 17 28 34 35 34 51 68 80 90 16 18 30 36 37 36 54 72 85 95 17 19 32 38 39 38 57 76 90 100 18 20 34 40 41 40 60 80 95 105 Unit dimensions Model : 40RS006.

5 25. 41. 11. 2 .7. 56 .0 38. 31. 38..0. 81. 10. 67 37. 4. Unit dimensions Model : 40RS080-100 Vertical & Horizontal Type SUPPLY SUPPLY. DRAIN. AIR VNET VALVE SERVICE. CONNECTION PIPE. RETURN. WATER OUT. WATER IN (SUCTION). (SUCTION). AIR VNET VALVE SERVICE. DRAIN. RETURN. Model : 40RS120, 140 Vertical & Horizontal Type SUPPLY SUPPLY. RETURN. DRAIN. AIR VNET VALVE SERVICE. CONNECTION PIPE. WATER OUT. WATER IN (SUCTION). (SUCTION). AIR VNET VALVE SERVICE. DRAIN. RETURN. 5. Unit dimensions Model : 40RS160-240 Vertical Type SUPPLY SUPPLY. CONNECTION PIPE. RETURN. WATER OUT. (SUCTION). WATER IN. (SUCTION). DRAIN DRAIN Model : 40RS160, 240 Horizontal Type SUPPLY. WATER OUT. (SUCTION). RETURN. CONNECTION PIPE. WATER IN. (SUCTION). DRAIN DRAIN. 6. Unit dimensions Model : 40RS280, 340 Vertical Type SUPPLY SUPPLY. WATER OUT 1. RETURN. WATER IN 1. WATER OUT 2. WATER IN 2. DRAIN DRAIN. Model : 40RS280, 340 Horizontal Type SUPPLY. WATER OUT 1. RETURN. WATER IN 1. WATER OUT 2. WATER IN 2. DRAIN. DRAIN.

6 7. Fan performance data Total Static Pressure (in. wg). Unit APD. CFM Model RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW. 40RS006 1680 616 715 816 911 - - - - - - - - - - 1920 647 733 825 913 - - - - - - - - - - 2160 684 760 841 923 - - - - - - - - - - 2400 730 794 866 - - - - - - - - - - - - 40RS006S 1660 616 715 816 911 - - - - - - - - - - 1920 647 733 825 913 - - - - - - - - - - 2160 664 760 841 923 - - - - - - - - - - 2400 730 794 866 - - - - - - - - - - - - 40RS080 2350 599 726 859 - - - - - - - - - - - - 2700 608 730 838 954 - - - - - - - - - - 3050 623 736 841 937 1039 - - - - - - - - 3400 643 748 848 940 1025 1116 - - - - - - 3650 673 769 861 949 1034 1108 1185 1265 - - 40RS100 2350 599 726 859 - - - - - - - - - - - - 2700 608 730 838 954 - - - - - - - - - - 3050 623 736 841 937 1039 - - - - - - - - 3400 643 748 848 940 1025 1116 - - - - - - 3850 673 769 861 949 1034 1108 1185 1265 - - 40RS120 3200 516 651 - - - - - - - - - - - - - - 3750 522 631 747 - - - - - - - - - - - - 4300 528 637 728 828 - - - - - - - - - - 4850 539 641 734 814 900 997 - - - - - - 5250 551 647 738 818 892 972 1061.

7 - 8. Fan performance data Total Static Pressure (in. wg). Unit APD. CFM Model RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW. 40RS140 3200 516 651 - - - - - - - - - - - - - - 3750 522 631 747 - - - - - - - - - - - - 4300 528 637 728 828 - - - - - - - - - - 4850 539 641 734 814 900 997 - - - - - - 5250 551 647 738 818 892 972 1061 - - - - 40RS160 5150 451 549 636 720 - - - - - - - - - - 5900 455 549 634 709 784 - - - - - - - - 6650 465 554 634 708 776 842 908 - - - - 7400 498 558 639 708 776 838 896 957 1016 8150 536 569 642 713 776 838 896 951 1005 40RS240 5200 451 549 635 719 - - - - - - - - - - 6000 455 550 634 709 782 - - - - - - - - 6800 470 555 634 708 776 841 905 - - - - 7700 513 559 640 710 776 838 896 954 1010 8600 559 588 645 715 779 838 896 950 - - 40RS280 6500 374 461 - - - - - - - - - - - - - - 7550 380 456 528 - - - - - - - - - - - - 8600 386 461 527 591 - - - - - - - - - - 9650 398 466 532 589 645 711 - - - - - - 10700 419 474 538 594 646 696 751 814 - - 40RS340 7800 380 458 527 - - - - - - - - - - - - 9050 390 463 529 588 655 - - - - - - - - 10300 410 471 534 592 644 698 761 - - - - 11650

8 440 485 542 597 650 698 744 792 847 13000 470 510 554 606 655 704 749 791 831 9. Performance data Ent/Lvg Water Temp 44/54 F Capacity Ent Air db/wb F 76/63 78/65 80/67 82/69. Model CFM Total Sensible gpm Total Sensible gpm Total Sensible gpm Total Sensible gpm 40RS006 1800 2100 2400 40RS006S 1800 2100 2400 40RS080 2320 3090 3850 40RS100 2320 3090 3850 40RS120 3150 4200 5250 40RS140 3150 4200 5250 40RS160 4880 6510 8140 40RS240 5230 6970 8700 40RS280 6580 8770 10950 40RS340 7850 10470 13080 10. Performance data Ent/Lvg Water Temp 45/55 F Capacity Ent Air db/wb F 76/63 78/65 80/67 82/69. Model CFM Total Sensible gpm Total Sensible gpm Total Sensible gpm Total Sensible gpm 40RS006 1800 2100 2400 40RS006S 1800 2100 2400 40RS080 2320 3090 3850 40RS100 2320 3090 3850 40RS120 3150 4200 5250 40RS140 3150 4200 5250 40RS160 4880 6510 8140 40RS240 5230 6970 8700 40RS280 6580 8770 10950 40RS340 7850 10470 13080 11. YOUR CARRIER MAN : 40rs /01/07.