BUSSMANN. Technical Data 10352. Effective September 2018. Supersedes December 2015 SERIES. E-Rated medium voltage fuses for feeder circuit , switchgear and transformer protection Features and benefits Current-limiting E-Rated medium voltage fuses are defined by their melting time-current characteristic that permit their electrical interchangeability with other fuses of the same E Rating. E-Rated fuses must have a defined current response time specified by ANSI E-Rated fuse of 100 amps and below must melt in 300 seconds at an RMS current within the range of 200% to 240% of the fuse 's nameplate current rating. E-Rated fuses greater than 100 amps must melt in 600 seconds at an RMS current within the range of 220% to 264%. of the fuse 's nameplate current rating. E-Rated fuses are physically dimensioned for easy installation in existing hardware. Current-limiting fuses provide positive interruption even on low fault currents. The fuse limits the magnitude of electromechanical Description: stresses in the protected apparatus.

Technical Data 10352 Effective September 2018 Speree December 2015 BSSMANN ERIES Description: • Bussmann™ series E-Rated, current-limiting, medium voltage fuses for feeder circuit, switchgear and transformer protection.

Tags:

  Circuit, Fuse, Transformers, Switchgear, Feeder, Fuses for feeder circuit, Switchgear and transformer

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of 8.3kV E-Rated medium voltage fuses for feeder circuit ...

1 BUSSMANN. Technical Data 10352. Effective September 2018. Supersedes December 2015 SERIES. E-Rated medium voltage fuses for feeder circuit , switchgear and transformer protection Features and benefits Current-limiting E-Rated medium voltage fuses are defined by their melting time-current characteristic that permit their electrical interchangeability with other fuses of the same E Rating. E-Rated fuses must have a defined current response time specified by ANSI E-Rated fuse of 100 amps and below must melt in 300 seconds at an RMS current within the range of 200% to 240% of the fuse 's nameplate current rating. E-Rated fuses greater than 100 amps must melt in 600 seconds at an RMS current within the range of 220% to 264%. of the fuse 's nameplate current rating. E-Rated fuses are physically dimensioned for easy installation in existing hardware. Current-limiting fuses provide positive interruption even on low fault currents. The fuse limits the magnitude of electromechanical Description: stresses in the protected apparatus.

2 Bussmann series E-Rated , current-limiting, Constructions available in ferrule, bolt-on medium voltage fuses for feeder circuit , and clip lock, and specialty mount fuses for switchgear and transformer protection. AMPGARD motor starters. Outdoor rating available on select catalog numbers (requires installation in a suitable enclosure). Open fuse indicator easily integrates into automation schemes and speeds troubleshooting by providing a positive visual indication of fuse operation. Optional remote contact signaling microswitch available. 50/60Hz operating frequency for worldwide application. Mountings are available in disconnect and non- disconnect versions with porcelain or glass poly- ester insulators. Live parts and end fittings available. Typical applications: medium voltage transformer primary protection medium voltage feeder circuit protection medium voltage switches medium voltage metal-enclosed switchgear Technical Data 10352 E-Rated medium voltage fuses for Effective September 2018 feeder circuit , switchgear and transformer protection E-Rated medium voltage ferrule fuses Dimensions (see catalog number tables for values).

3 Catalog symbols: C. 8 CLE-_E-D (10-25A). 8 CLE-_E (10-350A) B. 8 HLE-_E (10-350A). Ratings*: Volts Amps 10 to 350A. Interrupting ratings 50kA RMS Sym ( ). * See catalog number tables for voltages, ampacities and interrupting ratings by B. catalog number. Agency information: A. E-Rated fuses meet the performance characteristics of ANSI Recommended fuse holders: Catalog number fuse voltage Approximate dimensions - in (mm) Mounting (including live parts, end fittings)** Live parts End fittings mounting BIL Diameter Clip center Length Porcelain Glass-polyester (including (disconnect Amp rating type* (kV) A B C insulator insulator end fittings) only). CLE. 10E-D 25E-D Non-disconnect 75 8 CLE-PNM-D 8 CLE-GNM-D CLE-NL-D . 30E 175E (76) 14 (356) (455). Single barrel Disconnect 75 8 CLE-PDM-D 8 CLE-GDM-D CLE-DL-D CLE-DF-D. 15E 25E Non-disconnect 75 8 CLE-PNM-C 8 CLE-GNM-C CLE-NL-C . (51) 14 (356) (394). Single Barrel Disconnect 75 8 CLE-PDM-C 8 CLE-GDM-C CLE-DL-C CLE-DF-C. 200E 350E Non-disconnect 75 8 CLE-PNM-E 8 CLE-GNM-E CLE-NL-E.

4 (76) 14 (356) (455). Double barrel Disconnect 75 8 CLE-PDM-E 8 CLE-GDM-E CLE-DL-E CLE-DF-E. HLE. 10E-175E Non-disconnect 75 8 HLE-PNM-D 8 HLE-GNM-D CLE-NL-D . (76) 12 (305) (404). Single barrel Disconnect 75 8 HLE-PDM-D 8 HLE-GDM-D CLE-DL-D CLE-DF-D. 200E 350E Non-disconnect 75 8 HLE-PNM-E 8 HLE-GNM-E CLE-NL-E . (76) 12 (305) (404). Double barrel Disconnect 75 8 HLE-PDM-E 8 HLE-GDM-E CLE-DL-E CLE-DF-E. * See page 4 for illustrations and dimensions ** End fittings supplied only when required. Disconnect mountings provide a means for fuse extraction only. Do not use a disconnect mounting for load switching or fuse removal while energized. Recommended fuseclips: fuse diameter - Clip dimensions - in (mm) Catalog Description in (mm) Figure A B C D E F G number Enclosed fuseclip 2 (51) 1 (95) (50) (51) (30) (115) (38) (10) A3354710*. Enclosed fuseclip 3 (76) 1 (105) (62) (76) (30) (143) (38) (10) A3354730*. Open fuseclip 3 (76) 2 See dimensions drawing 1A0065. Spring loaded open fuseclip 3 (76) 3 See dimensions drawing 9078A67G04.

5 *For single barrel applications only. Not sold in pairs. Figure 1 Figure 2 Figure 3. C. A. D. B. G. F. E. 2 E-Rated medium voltage fuses for Technical Data 10352. feeder circuit , switchgear and transformer protection Effective September 2018. CLE and HLE Type fuses Dimensions in (mm). Installation Amps Length A Diameter B Clip centers C IR RMS Sym. (kA) No. of barrels location Catalog no. CLE Long construction (Westinghouse). 10 (455) 3 (76) Indoor/outdoor 8 CLE-10E-D. 15 (394) 2 (51) Indoor 8 CLE-15E*. 15 (455) 3 (76) Indoor/outdoor 8 CLE-15E-D. 20 (394) 2 (51) Indoor 8 CLE-20E*. 20 (455) 3 (76) Indoor/outdoor 8 CLE-20E-D. 25 (394) 2 (51) Indoor 8 CLE-25E*. 25 8 CLE-25E-D. 30 8 CLE-30E. 1. 40 8 CLE-40E. 50 8 CLE-50E. 14 (356) 50. 65 8 CLE-65E. 80 8 CLE-80E. 100 8 CLE-100E. (455) 3 (76) Indoor/outdoor 125 8 CLE-125E. 150 8 CLE-150E. 175 8 CLE-175E. 200 8 CLE-200E. 250 8 CLE-250E. 2. 300 8 CLE-300E. 350 8 CLE-350E. HLE Short construction 10 8 HLE-10E. 15 8 HLE-15E. 20 8 HLE-20E. 25 8 HLE-25E.

6 30 8 HLE-30E. 40 8 HLE-40E. 50 1 8 HLE-50E. 65 8 HLE-65E. 80 (404) 3 (76) 12 (305) 50 Indoor/outdoor 8 HLE-80E. 100 8 HLE-100E. 125 8 HLE-125E. 150 8 HLE-150E. 175 8 HLE-175E. 200 8 HLE-200E. 250 8 HLE-250E. 2. 300 8 HLE-300E. 350 8 HLE-350E. * fuses conform to dimensional standards established by Westinghouse. 3. Technical Data 10352 E-Rated medium voltage fuses for Effective September 2018 feeder circuit , switchgear and transformer protection CLE and HLE Type mountings - in (mm). Overall Contact Overall Catalog Hole centers length Hole Inset Hole centers height height BIL. number A B C D E F G kV. Disconnect single barrel . 8 CLE-GDM-C ( ) 6 ( ) 28 ( ) (19) ( ) 7 ( ) ( ) 75. 8 CLE-GDM-D ( ) 6 ( ) 25 ( ) ( ) ( ) 7 ( ) ( ) 75. 8 CLE-PDM-C ( ) 6 ( ) 28 ( ) (19) ( ) 7 ( ) ( ) 75. 8 CLE-PDM-C ( ) 6 ( ) 25 ( ) ( ) ( ) 7 ( ) ( ) 75. 8 HLE-GDM-D ( ) 6 ( ) 23 ( ) ( ) ( ) 7 ( ) ( ) 75. 8 HLE-PDM-D ( ) 6 ( ) 23 ( ) ( ) ( ) 7 ( ) ( ) 75. Disconnect double barrel . 8 CLE-GDM-E ( ) 6 ( ) 25 ( ) ( ) ( ) 7 ( ) ( ) 75.

7 8 CLE-PDM-E ( ) 6 ( ) 25 ( ) ( ) ( ) 7 ( ) ( ) 75. 8 HLE-GDM-E ( ) 6 ( ) 23 ( ) ( ) ( ) 7 ( ) ( ) 75. 8 HLE-PDM-E ( ) 6 ( ) 23 ( ) ( ) ( ) 7 ( ) ( ) 75. Non-disconnect single barrel 8 CLE-GNM-C ( ) 6 ( ) ( ) (19) ( ) 7 ( ) ( ) 75. 8 CLE-PNM-C ( ) 6 ( ) ( ) (19) ( ) 7 ( ) ( ) 75. 8 CLE-GNM-D ( ) 6 ( ) 25 (635) ( ) ( ) 7 ( ) ( ) 75. 8 CLE-PNM-D ( ) 6 ( ) 25 (635) ( ) ( ) 7 ( ) ( ) 75. 8 HLE-GNM-D ( ) 6 ( ) 23 ( ) ( ) ( ) 7 ( ) ( ) 75. 8 HLE-PNM-D ( ) 6 ( ) 23 ( ) ( ) ( ) 7 ( ) ( ) 75. Non-disconnect double barrel 8 CLE-GNM-E ( ) 6 ( ) 25 (635) ( ) ( ) 7 ( ) ( ) 75. 8 CLE-PNM-E ( ) 6 ( ) 25 (635) ( ) ( ) 7 ( ) ( ) 75. 8 HLE-GNM-E ( ) 6 ( ) 23 ( ) ( ) ( ) 7 ( ) ( ) 75. 8 HLE-PNM-E ( ) 6 ( ) 23 ( ) ( ) ( ) 7 ( ) ( ) 75. CLE and HLE Type disconnect mounting CLE and HLE Type non-disconnect mounting G G. D F D F. E E. A C A C. E E. D B D B. Disconnect mountings provide a means for fuse extraction only. Do not use a disconnect mounting for load switching or fuse removal while energized. 4 E-Rated medium voltage fuses for Technical Data 10352.

8 feeder circuit , switchgear and transformer ( ) protection Effective September 2018. A. B. E-Rated medium voltage specialty mount fuses Dimensions for HCL - in (mm). x Catalog symbols: Slots ( ) Dia. Hole A. ( x ) Indicator 8 AHLE-_E (special dimension fuses for use with rated, 800 amp AMPGARD C motor starting assemblies) ( ). 8 BHLE-_E (bolt-on version). ( ). 8 HCL-_E (clip-lock version) ( ) ( ). Ratings*: Volts ( ) ( ) B. Amps 10 to 350A. Interrupting ratings 50kA RMS Sym * See catalog number tables for voltages, ampacities and interrupting ratings by catalog number. Agency information: ( ). ( ). E-Rated fuses meet the performance characteristics of ANSI Recommended live parts for clip-lock fuses Catalog number HCL-NL-1 ( ). Dimensions for BHLE - in (mm) ( ) ( ). ( ). ( ). Indicator ( ). B C. * Flush with surface in untripped position, trip force is 2 lb ( ). A. Indicator to be located here ( ). B C. ( ) A. Indicator to be located here ( ). ( ). B C. ( ) A. 5. Technical Data 10352 E-Rated medium voltage fuses for Effective September 2018 feeder circuit , switchgear and transformer protection AHLE Type fuses Special dimension fuses for use with kV rated, 800 amp AMPGARD motor starting assemblies.

9 Amps IR RMS Sym. (kA) No. of barrels Catalog no. 10 8 AHLE-10E. 15 8 AHLE-15E. 20 8 AHLE-20E. 25 8 AHLE-25E. 30 8 AHLE-30E. 40 8 AHLE-40E. 50 1 8 AHLE-50E. 65 8 AHLE-65E. 80 50 8 AHLE-80E. 100 8 AHLE-100E. 125 8 AHLE-125E. 150 8 AHLE-150E. 175 8 AHLE-175E. 200 8 AHLE-200E. 250 8 AHLE-250E. 2. 300 8 AHLE-300E. 350 8 AHLE-350E. BHLE bolt-on versions Dimensions in (mm) IR RMS Sym. Installation Amps Overall length Diameter Hole centers (kA) No. of barrels location Catalog no. 10 8 BHLE-10E. 15 8 BHLE-15E. 20 8 BHLE-20E. 25 8 BHLE-25E. 30 8 BHLE-30E. 40 8 BHLE-40E. 50 1 8 BHLE-50E. 65 8 BHLE-65E. 80 ( ) 3 ( ) ( ) 50 Indoor 8 BHLE-80E. 100 8 BHLE-100E. 125 8 BHLE-125E. 150 8 BHLE-150E. 175 8 BHLE-175E. 200 8 BHLE-200E. 250 8 BHLE-250E. 2. 300 8 BHLE-300E. 350 8 BHLE-350E. HCL Clip lock versions Dimensions in (mm) Installation Amps Overall length Diameter Hole centers IR RMS Sym. (kA) No. of barrels location Catalog no. 65 8 HCL-65E. 80 8 HCL-80E. 100 8 HCL-100E. 1. 125 8 HCL-125E. 150 8 HCL-150E.

10 ( ) 3 ( ) N/A 50 Indoor/outdoor 175 8 HCL-175E. 200 8 HCL-200E. 250 8 HCL-250E. 2. 300 8 HCL-300E. 350 8 HCL-350E. 6 E-Rated medium voltage fuses for Technical Data 10352. feeder circuit , switchgear and transformer protection Effective September 2018. Time-current curves minimum melt for 8 CLE-_E and 8 CLE-_-D. Curve 70548501 Curve 70546201 Curve 70546401. April 16, 1999 April 1999 April 1999. 8 CLE-_ Reference # 563532 Reference # 705462 Reference # 705464. 7. Technical Data 10352 E-Rated medium voltage fuses for Effective September 2018 feeder circuit , switchgear and transformer protection Time-current curves total clear for 8 CLE-_E and 8 CLE-_-D. Curve 70548601 Curve 70546301 Curve 70546501. April 16, 1999 April 1999 April 1999. 8 CLE-_ Reference # 563533 Reference # 705463 Reference # 705465. 8 E-Rated medium voltage fuses for Technical Data 10352. feeder circuit , switchgear and transformer protection Effective September 2018. Peak let-through for 8 CLE-_E and 8 CLE-_-D. Curve 70548801 Curve 70547301.