A Honeywell Company Oil Burner Safety Control - Satronic

1A Honeywell CompanyFor 1- or 2-stage oil power burners up to 30kg/h capacity and intermittent detection:- Photoresistor MZ 770 S- Infrared-flicker detector IRD 1010- UV solid state sensor UVD 970 Oil Burner Safety ControlTF / DATAO perating voltage220/240 V ( +10%)50 Hz (40-60Hz)Fuse rating10 A fast, 6 A slowPower consumptionca. 5 VAMax. load per output- terminal A, cos terminal A, cos terminal A, cos terminal A, cos terminal A, cos A, cos timeca. 12 timeca. 12 timeTF 20 2-5 secDelay time to oil valve 240 sec. (TF )Lockout Safety time10 time from lockoutca. 90 secFlame detector:MZ 770 Sside-on and end-on viewingLight sensitivity MZ 770 S> 6 LuxIRD 1010side-on or end-on viewingUVD 970end-on viewingSensor operating currentmin.

1 A Honeywell Company For 1- or 2-stage oil power burners up to 30kg/ h capacity and intermittent operations. Flame detection: - Photoresistor MZ 770 S

Tags:

  Company, Control, Safety, Burner, Honeywell, A honeywell company oil burner safety control, A honeywell company

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of A Honeywell Company Oil Burner Safety Control - Satronic

1 1A Honeywell CompanyFor 1- or 2-stage oil power burners up to 30kg/h capacity and intermittent detection:- Photoresistor MZ 770 S- Infrared-flicker detector IRD 1010- UV solid state sensor UVD 970 Oil Burner Safety ControlTF / DATAO perating voltage220/240 V ( +10%)50 Hz (40-60Hz)Fuse rating10 A fast, 6 A slowPower consumptionca. 5 VAMax. load per output- terminal A, cos terminal A, cos terminal A, cos terminal A, cos terminal A, cos A, cos timeca. 12 timeca. 12 timeTF 20 2-5 secDelay time to oil valve 240 sec. (TF )Lockout Safety time10 time from lockoutca. 90 secFlame detector:MZ 770 Sside-on and end-on viewingLight sensitivity MZ 770 S> 6 LuxIRD 1010side-on or end-on viewingUVD 970end-on viewingSensor operating currentmin.

2 30 AWeight incl. wiring kgMounting positionanyProtection classIP44 Recommended ambient operatingtemperature for Control andflame detector0 +60 Capproved and certified accordingto European standardsEN 230 APPLICATION RANGEThe TF or TF oil Burner Safety Control boxesare suitable to Control and monitor oil power Burner up to30 kg/h capacity (approved and certified according toEN230).TYPES AVAILABETF operationpost-ignition time ca. 20 voltage protection according to EN230TF operationpost-ignition time 2-5 voltage protection according to EN230 CONSTRUCTIONAL FEATURESThe Control box circuitry is protected by a flame resistant,transparent plastic housing. It incorporates the thermo-mechanical, temperature compensated timer, flame checkand reset reset from lockout is provided by a push button withan integrated lockout signal lamp.

3 A central fixing screwlocks the Control box to the wiring base. The wiring base andcontrol box have a positive plug-in arrangement, making itimpossible to achieve an incorrect connection between thetwo parts. A variety of cable entry points provides utmostflexibility of electrical TF is fully compatible with the TF 730,730-1 and TF 832. The flame detector IRD 911must be replaced by its compatible type IRD optional extension button (item no. 70601)compensates for height AND ROUTINE CHECKS1. Important notes The controls must be installed by qualified personnelonly. The relevant national regulations have to beobserved. On commissioning the wiring has to be carefully checkedaccording the appropriate diagram, Incorrect wiring candamage the unit and endanger the installation.

4 The fuse rating has to ensure that the limits specified inTECHNICAL DATA will not be exceed. If these precautionsare not observed, the effect of a short circuit can causesevere damage to the Control and installation. For Safety reasons a minimum of one Control shut-downper 24 hours has to be observed. Disconnect the mains before the Control box is pluggedin or out! The Control box is a Safety device and must not beopened!2. Function controlFor Safety reasons the flame detection system should betested on commissioning the installation as well as after aservice or longer ) Start-up with covered flame detector After lock-out Safety time is over the unit has to go into lockout mode!b) Start-up with exposed flame detector: After 20 sec.

5 Pre-purge time the unit has to go intolockout mode!c) Normal start-up with Burner in the normal position, coverup the flame detector: After start-up, and end of lock-out Safety time the unithas to go into lockout mode!3. Fault findingsBurner is not working: thermostat circuit open faulty electrical wiring mains voltage too lowBurner starts, but the flame does not establish, a lock outoccurs: stray light on flame detector no ignition or no fuel mains voltage more than -15% below nominal starts, the flame establishes, but after the safetytime, a lock out occurs: dirty or faulty flame detector insufficient light on detector sensitivity adjustment too low on a quick and safe diagnosis use the Satronic UP 940burner test NOTES1. Flame controlThe following detectors can be used for flame Control : For yellow oil flame: photoresistor MZ 770 S for blue or yellow flame: infrared-flicker detector typeIRD 1010 or as alternative the UV solid state sensor the photo resistor MZ 770 S, the no flame signal isgenerated at light levels below 3 Lux with respect to theoperating cycle of the Control .

6 According to EN 230 straylight Safety level has to be established in conjunction withthe accompanying the IRD 1010 or the UVD 970, the correct wiringhas to be Burner controlFor burners without an oil solenoid valve, the Burner motorhas to be connected to terminal Low-voltage protectionThe start up of the Burner can only take place if the mainsvoltage is higher than a limit which is 15% below nominalvalue. If the voltage drops below 160V, a start-up is preventedor without allowing to release the fuel the Control boxgoes into lock out SafetyThe design and Control sequence of the TF andTF Control boxes comply with the currently applicableEuropean standards and Mounting and electrical wiringWiring base: 3 earth terminals with additional terminal for burnerearthing 3 neutral terminals with internal permanent connectionto neutral terminal (terminal 8) 2 spare auxiliary terminals 2 slide in plates and 2 easy-knockout holes (PG 11thread), plus 2 easy-knockout holes in the bottom of thebase facilitate the : The Control box can be mounted in any position.

7 Theprotection class is IP44 (water spray tight). Neither thecontrol box nor the flame detector should be subjectedTF UVD CONNECTION blueblackbrownterm. 2term. 1term. 9 IRD 1010 UVD 970 IRD-OR UVD CONNECTION blueblackbrownterm. 2term. 1term. 9 IRD 1010 UVD 970 CIRCUIT AND TIMING DIAGRAM AND TIMING DIAGRAM TF DIAGRAMM TF DIAGRAMM TF ' V1 SAmax. 10 A fast6 A slowPhHSRTSTtv1 tstnHSMains switchSTLimit thermostatRTControl thermostatFFlame detector MZ 770 S(IRD 1010, UVD 970 see separate diagram)ZIgnitionMBurner motor( Burner with solenoid valve)M Burner motor( Burner without solenoid valve)V1 Oil solenoid valve, 1st-stageSAExternal lock-out signaltv1 Pre-ignition time with or without pre-purgetsLock-out Safety timetnPost-ignition timeblueblackmax.

8 10 A fast6 A slowPhHSRTST blueblackNZMM' V1 SAV2tv1 tstn tv2 HSMains switchSTLimit thermostatRTControl thermostatFFlame detector MZ 770 S(IRD 1010, UVD 970 see separate diagram)ZIgnitionMBurner motor( Burner with solenoid valve)M Burner motor( Burner without solenoid valve)V1 Oil solenoid valve, 1st-stageV2 Oil solenoid valve, 2nd stageSAExternal lock-out signaltv1 Pre-ignition time with or without pre-purgetsLock-out Safety timetnPost-ignition timetv2 Delay 2nd stageF12345678912345 6 7 8 9HS Mains switchST Limit thermostatRT Control thermostatSA Lock-out signal indicatorFFlame detector MZ 770 S, IRD 1010 or UVD 970 VValvesZIgnitionM Burner motorRF Flame relayrllow voltage relayB Thermomechanical timerRV Resistor4A Honeywell CompanySatronic AGHoneywell-Platz 1 Postfach 324CH-8157 DielsdorfTF 83X AND SOCKETTF / ,54,538.

9 52486 Slide-in platePG 116024303044M4 EarthReset button253530 Underdsite cableentry 16 mm1657-60 ORDERING INFORMATIONITEMDESIGNATIONITEM boxType TF boxType TF 701 ABEN70001 Insert platePG-Plate70502optionalCable entry plate70501 Flame detectorMZ 770 S50001optionalMZ 770 S mounted in shaft51001optionalIRD 1010 right16501optionalIRD 1010 end-on16502optionalIRD 1010 left16503optionalUVD 97016702 Support for flame detectorHolder for MZ59101optionalHolder M 74 for IRD, UVD59074 Connectioncable IRD/UVDPlug type, 3 core cable, m, with tag wire ends7236001 Connectioncable MZPlug type, 2 core cable, m, with tag wire ends7225001 The above ordering information refers to the standard versions are also included in our product subject to change without noticeUVD 970 IRD 1010 VARIATION IRD2950rightUVD = 29 IRD = 4421,8 13,5leftaxialUVD = 89 IRD = 1042921,8 14353 20484,5264 HOLDER MZ 770 MZ 770 S 35 18 8 SHAFT MZ 770 SHOLDER M 74 FOR IRD OR UVD12,314 18