ACDS-PRC003E-EN (04/2016): Product Catalog, Split System ...

April 2016 ACDS-PRC003E-ENSplit SystemAir-Cooled Condensers 20 to 120 TonsProduct Catalog 2016 trane All rights reservedACDS-PRC003E-ENIntroductionTTrra annee hhaass tthhee rriigghhtt you are designing a new System or replacing an existing air-cooled condenser, trane can satisfy virtually any application need. Whether coupled with anindustrial compressor, a single zone commercial self-contained unit, compressor chiller or a ColdGenerator chiller, trane has the right air-cooled condenser for the job. When teamed with anyone of a wide range of compressor-evaporator combinations, trane air-cooled condensers,available in 20 to 120 tons, are ideal for multistory office buildings, hotels, schools, municipal andindustrial document and the information in it are the property of trane , and may not be used orreproduced in whole or in part without written permission.

6 ACDS-PRC003E-EN ApplicationConsiderations Certain application constraints should be considered when sizing, selecting and installing Trane® air-cooled condensers.

Tags:

  Selecting, Trane

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of ACDS-PRC003E-EN (04/2016): Product Catalog, Split System ...

1 April 2016 ACDS-PRC003E-ENSplit SystemAir-Cooled Condensers 20 to 120 TonsProduct Catalog 2016 trane All rights reservedACDS-PRC003E-ENIntroductionTTrra annee hhaass tthhee rriigghhtt you are designing a new System or replacing an existing air-cooled condenser, trane can satisfy virtually any application need. Whether coupled with anindustrial compressor, a single zone commercial self-contained unit, compressor chiller or a ColdGenerator chiller, trane has the right air-cooled condenser for the job. When teamed with anyone of a wide range of compressor-evaporator combinations, trane air-cooled condensers,available in 20 to 120 tons, are ideal for multistory office buildings, hotels, schools, municipal andindustrial document and the information in it are the property of trane , and may not be used orreproduced in whole or in part without written permission.

2 trane reserves the right to revise thispublication at any time, and to make changes to its content without obligation to notify anyperson of such revision or trademarks referenced in this document are the trademarks of their respective History Added Corrosive Atmosphere information to Application Considerations section. Reformatted general, electrical and weight tables. Updated unit model numbers to show all option selections. Updated Mechanical Specifications to add missing information and review existing wordingfor content. Content organization reviewed and updated to meet current and 420 to 120 Ton Units.. 4 Durable Construction .. 4 Microchannel Condenser Coil.. 4 Application Considerations .. 6 Unit Location .. 6 Voltage .. 7 Effect of Altitude on Capacity .. 7 Ambient Considerations.. 7 Corrosive Atmospheres.

3 7 Selection Procedures .. 9 Model Number Description .. 12 General 13 Performance Data .. 14 Performance Adjustment Factors.. 14 Performance Data.. 16 Unit 17 Unit 31 Mechanical Specifications .. 32 Air-Cooled Condenser Model CAUJ .. 32 Options .. 32 Table of Contents4 ACDS-PRC003E-ENFeatures and Benefits20 to 120 Ton UnitsTrane 20 to 120 ton model CAUJ air-cooled condensers have an operating range of 40 F to 115 F, with a low ambient option down to 0 control panel is factory-installed and wired to prevent potential damage and to provideweathertight control panel contains: fan motor contactors fan cycling controls terminal point connection for compressor interlock 115-volt control power transformerThese standard features reduce installation costs and provide easy interface with control trane air-cooled condenser coils are an all aluminum microchannel design.

4 The 20 to 30 toncondensers are single circuit; 40 to 120 ton units are dual circuited; all feature can have optional corrosion protected condenser ConstructionTrane 20 to 120 ton condensers are built for long life. The unit frame is constructed of 14 gaugegalvanized steel. Louvered panels provide excellent coil protection while enhancing unitappearance and strength. The unit surface is phosphatized and finished with trane slate grey air-dry paint. This air dry-paint finish exceeds 672 consecutive hour salt spray resistance inaccordance with ASTM Condenser CoilMicrochannel condensing coils are all-aluminum coils with fully-brazed construction. This designreduces risk of leaks and provides increased coil rigidity making them more rugged on thejobsite. Their flat streamlined tubes with small ports and metallurgical tube-to-fin bond allow forexceptional heat transfer.

5 Microchannel all-aluminum construction provides several additionalbenefits: Light weight (simplifies coil handling) Easy to recycle Minimize galvanic corrosionACDS-PRC003E-EN5 Slit Fins and Braze Contactfor Improved Heat Transfer and StrengthAir Condenser InletAir Condenser OutletMicrochannelsfor RefrigerantFFeeaattuurreess aanndd BBeenneeffiittss6 ACDS-PRC003E-ENApplication ConsiderationsCertain application constraints should be considered when sizing, selecting and installing trane air-cooled condensers. Unit reliability is dependent upon these considerations. Where yourapplication varies from the guidelines presented, it should be reviewed with the local trane LocationFoundationA base or foundation is not required if the selected unit location is level and strong enough tosupport the unit s operating and Sound EmissionSince the environment in which a sound source is located affects sound pressure, unit placementmust be carefully evaluated.

6 The most effective form of noise isolation is proper unit should be placed away from noise sensitive transmitted sound can be reduced by using isolators, which are recommended forsound sensitive installations. For maximum isolation effect, the refrigeration lines and electricalconduit should also be isolated and flexible electrical conduit acoustical engineer should always be consulted on critical and local codes on sound emissions should always be Flow ConsiderationsUnobstructed flow of condenser air is essential for maintaining capacity and operating determining unit placement, careful consideration must be given to assure proper air flowacross the condenser heat transfer surface. Inadequate air flow will result in warm airrecirculation and coil air flow starvation. Warm air recirculation occurs when discharge air from the condenser fans is recycled back atthe condenser coil inlet.

7 Coil starvation occurs when free air flow to the condenser is warm air recirculation and coil starvation cause reductions in unit efficiency and capacity. Inmore severe cases, nuisance unit shutdowns will result from excessive head pressures. Accurateestimates of the degree of efficiency and capacity reduction are not possible due to theunpredictable effect of varying hot gas bypass is used, reduced head pressure increases the minimum ambient conditionfor proper operation. In addition, wind tends to further reduce head pressure. Therefore, it isadvisable to protect the air-cooled condensing unit from continuous direct winds exceeding 10miles per , trash, supplies, etc., should not be allowed to accumulate in the vicinity of the air-cooledcondenser. Supply air movement may draw debris between coil fins and cause coil consideration should be given to units operating in low ambient coils and fan discharge must be kept free of snow and other obstructions to permitadequate air flow for satisfactory unit service clearance is required for unit access and maintenance.

8 See Dimensions chapterfor service clearance recommendations. Local code requirements may take condenser air discharge must be unobstructed. While it is difficult to predict the degree ofwarm air recirculation, a unit installed with a ceiling or other obstruction above it will losecapacity and the maximum ambient operation will be reduced. Nuisance high head pressuretrips may also inlet to the coil must also be unobstructed. A unit installed closer than the minimumrecommended distance to a wall or other vertical riser may experience a combination of coilACDS-PRC003E-EN7starvation and warm air recirculation, resulting in unit capacity and efficiency reductions, as wellas possible excessive head pressures. The recommended lateral distances are listed in theDimensional Data voltage is the nameplate rating voltage.

9 The actual range of line voltages at which theequipment can satisfactorily operate is given below:Table 1. Voltage rangeNominalVoltageVoltageUtilizationRan ge200/230(a)180-220 or 208-254460416-508575520-635(a)Units ratedfor 200/230-voltsship from the factory set foroperation in the 180 through leads onunit transformers,the unit will operatein the 208 through of Altitude on CapacityCapacities given in the performance data tables are at sea level. At elevations substantially abovesea level, the decreased air density will decrease condenser capacity. The adjustment factorsshown in can be applied directly to the catalog performance data to determine the unit sadjusted ConsiderationsTrane condensers are designed for year-around applications in ambients from 0 F through 115 operation below 0 F or above 115 F, contact the local trane sales and operation at lower ambients requires sufficient head pressure be maintained forproper operation.

10 Minimum operating ambient temperatures for standard unit selections andunits with hot gas bypass are shown in the General Data section. These temperatures are basedon still conditions (winds not exceeding five mph.) Greater wind velocities will result in a drop inhead pressure, therefore, increasing the minimum starting and operating ambient with the low ambient option are capable of starting and operating in ambients down to 0 F,10 F with hot gas bypass. Optional low ambient units use a condenser fan damper arrangementthat controls condenser capacity by modulating in response to head cataloged ambient temperature operation of a standard condenser is 115 F. Operationat design ambients above 115 F can result in excessive head proper operation outside these recommendations, contact the local trane sales AtmospheresTrane's large condensers are designed and built to industrial standards and will perform to thosestandards for an extended period depending on the hours of use, the quality of maintenanceperformed, and the regularity of that maintenance.