1 RXYQ-P9 EEDEN11-200 Air ConditionersVRV III heat pump, small footprint combinationTechnical data RXYQ-P9 EEDEN11-200 Air ConditionersVRV III heat pump, small footprint combinationTechnical data VRV Systems Outdoor Unit1 Outdoor Unit VRV III heat pump, small footprint combination RXYQ-P9 TABLE OF CONTENTSRXYQ-P91 Specifications .. 2 Technical Specifications .. 2 Electrical Specifications .. 62 Electrical data .. 9 Electrical data .. 93 Options .. 10 Options .. 104 Combination table .. 11 Combination Table .. 115 Capacity tables .. 12 Cooling Capacity Tables .. 12 Heating Capacity Tables .. 62 Integrated Heating Capacity Correction Factor .. 112 Capacity Correction Factor .. 1136 Dimensional drawings .. 126 Dimensional Drawings .. 126 Dimensional Drawings with Accessories .. 1287 Centre of gravity.. 130 Centre of Gravity .. 1308 Piping diagrams .. 132 Piping Diagrams .. 1329 Wiring diagrams.
2 136 Wiring Diagrams - Three Phase .. 13610 External connection diagrams .. 140 External Connection Diagrams .. 14011 Sound data .. 142 Sound Power Spectrum .. 142 Sound Pressure Spectrum .. 14412 Installation.. 146 Service Space .. 146 Fixation and Foundation of Units .. 147 Refrigerant Pipe Selection .. 14813 Operation range .. 150 Operation Range .. 150 Outdoor Unit VRV III heat pump, small footprint combination RXYQ-P9 VRV Systems Outdoor Unit21 SpecificationsOutdoor UniVRV SystemsRXYQ-P9 VRV III heat pump, small footprint combinat1-1 Technical SpecificationsRXYQ5P9W1 BRXYQ8P9W1 BRXYQ10P9W1 BRXYQ12P9W1 BRXYQ14P9W1 BRXYQ16P9W1 BRXYQ18P9W1 BSystemOutdoor unit module 1 RXYQ5P9 RXYQ8P9 RXYQ10P9 RXYQ12P9 RXYQ14P9 RXYQ16P9 RXYQ18P9 Capacity rangeHP581012141618 Cooling (1) (1) (1) (1) (1) (1) (1)Heating (2) (2) (2) (2) (2) (2) (2)Capacity controlMethodInverter controlledSteps%~ 100 Power input - ,136,615,835,374,984,894,67 Maximum number of connectable indoor units10172126303439 Indoor index WhiteMaterialPainted galvanized steel plateDimensionsUnitHeightmm1,680 Widthmm6359301,240 Depthmm765 Packed unitHeightmm1,855 Widthmm7961,0551,365 Depthmm860 WeightUnitkg159187240316324 Packed exchangerLengthmm1,4831,7782,088 RowsQuantity54 Fin aream tubeplate holeQuantity0 Tube type 8 Hi-XSSFinTypeNon-symmetric waffle louvreTreatmentHydrophilic and corrosion resistantFanTypePropeller fanQuantity12 Air flow /min95171185196233239 External static directionVerticalFan motorQuantity12 ModelBrushless DC motorOutputW350750350750 Fan motor 2 Model-Brushless DC motorOutputW-350750 VRV Systems Outdoor Unit3 Outdoor Unit VRV III heat pump.
3 Small footprint combination RXYQ-P91 SpecificationsSound power pressure sealed scroll compressorSpeedrpm6,3007,9806,3007,980 OutputW2,8003,8001,2002,8003001,4003,000 Crankcase heaterW33 Compressor 2 Model-ON - OFFType-Hermetically sealed scroll compressorSpeedrpm-2,900 OutputW-4,500 Crankcase heaterW-33 Compressor 3 Model-ON - OFFType-Hermetically sealed scroll compressorSpeedrpm-2,900 OutputW-4,500 Crankcase heaterW-33 Operation rangeCoolingMin.~Max. ~ ~Max. CWB-20~ expansion valveCircuitsQuantity1 Total refrigerant charge in the oilTypeSynthetic (ether) oilCharged connectionsLiquidTypeBraze insulationBoth liquid and gas pipesPiping lengthOU - (14)Total piping lengthSystemActualm1,000 Level differenceOU - IUOutdoor unit in highest positionm50 Indoor unit in highest positionm40IU - methodReversed cycleDefrost controlSensor for outdoor heat exchanger temperatureSafety devicesItem01 High pressure switch02 Fan driver overload protector03 Overcurrent relay04 Inverter overload protector05PC board fusePEDC ategoryCategory (21) (21)5 (21) (21) (21) (21)
4 1-1 Technical SpecificationsRXYQ5P9W1 BRXYQ8P9W1 BRXYQ10P9W1 BRXYQ12P9W1 BRXYQ14P9W1 BRXYQ16P9W1 BRXYQ18P9W1B Outdoor Unit VRV III heat pump, small footprint combination RXYQ-P9 VRV Systems Outdoor Unit41 Specifications1-1 Technical SpecificationsRXYQ20P9W1 BRXYQ22P9W1 BRXYQ24P9W1 BRXYQ26P9W1 BRXYQ28P9W1 BRXYQ30P9W1 BSystemOutdoor unit module 1 RXYQ8P9 RXYQ10P9 RXYQ12P9 RXYQ8P9 RXYQ10P9 RXYQ12P9 Outdoor unit module 2 RXYQ12P9 RXYQ18P9 Capacity rangeHP202224262830 Cooling (1) (1) (1) (1) (1) (1)Heating (2) (2) (2) (2) (2) (2)Capacity controlMethodInverter controlledSteps%~ 100 Power input - number of connectable indoor units434752566064 Indoor index power pressure refrigerant charge in the than 100 (calculated charge less than 95)Piping connectionsLiquidTypeBraze lengthOU - (8)Total piping lengthSystemActualm1,000 Level differenceOU - IUOutdoor unit in highest positionm50 Indoor unit in highest positionm40IU - methodReversed cycleDefrost controlSensor for outdoor heat exchanger (17) (17) (17) (17) (17)1-1 Technical SpecificationsRXYQ32P9W1 BRXYQ34P9W1 BRXYQ36P9W1 BSystemOutdoor unit module 1 RXYQ14P9 RXYQ16P9 RXYQ18P9 Outdoor unit module 2 RXYQ18P9 Capacity rangeHP323436 Cooling (1) (1) (1)Heating (2) (2) (2)Capacity controlMethodInverter controlledSteps%~ 100 Power input - number of connectable indoor units64 VRV Systems Outdoor Unit5 Outdoor Unit VRV III heat pump, small footprint combination RXYQ-P91 SpecificationsIndoor index ,0401,1051,170 Sound power pressure refrigerant charge in the than 100 (calculated charge less than 95)Piping connectionsLiquidTypeBraze lengthOU - (8)
5 Total piping lengthSystemActualm1,000 Level differenceOU - IUOutdoor unit in highest positionm50 Indoor unit in highest positionm40IU - methodReversed cycleDefrost controlSensor for outdoor heat exchanger (17) (17) (17)1-1 Technical SpecificationsRXYQ38P9W1 BRXYQ40P9W1 BRXYQ42P9W1 BRXYQ44P9W1 BRXYQ46P9W1 BRXYQ48P9W1 BRXYQ50P9W1 BRXYQ52P9W1 BRXYQ54P9W1 BSystemOutdoor unit module 1 RXYQ8P9 RXYQ10P9 RXYQ12P9 RXYQ8P9 RXYQ10P9 RXYQ12P9 RXYQ14P9 RXYQ16P9 RXYQ18P9 Outdoor unit module 2 RXYQ12P9 RXYQ18P9 Capacity rangeHP384042444648505254 Cooling (1) (1) (1) (1) (1) (1) (1) (1) (1)Heating (2) (2) (2) (2) (2) (2) (2) (2) (2)Capacity controlMethodInverter controlledSteps%~ 100 Power input - number of connectable indoor units64 Indoor index ,0001,0501,1001,1501,2001,2501,3001, ,2351,3001,3651,4301,4951,5601,6251,6901 ,755 Sound power pressure refrigerant charge in the than 100 (calculated charge less than 95)1-1 Technical SpecificationsRXYQ32P9W1 BRXYQ34P9W1 BRXYQ36P9W1B Outdoor Unit VRV III heat pump, small footprint combination RXYQ-P9 VRV Systems Outdoor Unit61 SpecificationsStandard Accessories : Connection pipes; Quantity : 4;Standard Accessories : Operation manual; Quantity : 1;Standard Accessories : Installation manual; Quantity : 1.
6 Piping connectionsLiquidTypeBraze lengthOU - (8)Total piping lengthSystemActualm1,000 Level differenceOU - IUOutdoor unit in highest positionm50 Indoor unit in highest positionm40IU - methodReversed cycleDefrost controlSensor for outdoor heat exchanger (17) (17) (17) (17) (17)1-2 Electrical SpecificationsRXYQ5P9W1 BRXYQ8P9W1 BRXYQ10P9W1 BRXYQ12P9W1 BRXYQ14P9W1 BRXYQ16P9W1 BRXYQ18P9W1 BPower supplyNameW1 Phase3N~FrequencyHz50 VoltageV400 Voltage running current (RLA) - - 50 HzStarting current (MSC) Ssc valuekVa-910838849873878 Minimum circuit amps (MCA) fuse amps (MFA)A162540 Total overcurrent amps (TOCA) load amps (FLA) connections - 50 HzFor power supplyQuantity5 RemarkEarth wire includedFor connection with indoorQuantity2 RemarkF1,F2 Power supply intakeBoth indoor and outdoor unit1-2 Electrical SpecificationsRXYQ20P9W1 BRXYQ22P9W1 BRXYQ24P9W1 BRXYQ26P9W1 BRXYQ28P9W1 BRXYQ30P9W1 BCurrentNominal running current (RLA) - - 50 HzStarting current (MSC) Ssc valuekVa1,7591,6871,6981,7881,7161,727 Minimum circuit amps (MCA) fuse amps (MFA)A5063 Total overcurrent amps (TOCA)A-Full load amps (FLA) Technical SpecificationsRXYQ38P9W1 BRXYQ40P9W1 BRXYQ42P9W1 BRXYQ44P9W1 BRXYQ46P9W1 BRXYQ48P9W1 BRXYQ50P9W1 BRXYQ52P9W1 BRXYQ54P9W1B VRV Systems Outdoor Unit7 Outdoor Unit VRV III heat pump, small footprint combination RXYQ-P91 Specifications Notes (1) Cooling: indoor temp.
7 27 CDB, 19 CWB; outdoor temp. 35 CDB; equivalent refrigerant piping: 5m; level difference: 0m; indoor unit fan speed: high. (2) Heating: indoor temp. 20 CDB; outdoor temp. 7 CDB, 6 CWB; equivalent refrigerant piping: 5m; level difference: 0m; indoor unit fan speed: high. (3) Sound power level is an absolute value that a sound source generates. (4) Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. (5) Sound values are theoretical values based on sound results of individual installed units. Possible deviations due to variety of installation patterns are not taken into account. (6) Sound values are measured in a semi-anechoic room. (7) PED unit category: Art3 3: excluded from scope of PED due to article 1, item of 97/23/EC (8) MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
8 (9) MSC means the maximum current during start up of the compressor (10) Maximum allowable voltage range variation between phases is 2%. (11) RLA is based on following conditions: indoor temp. 27 CDB, 19 CWB; outdoor temp. 35 CDB (12) Select wire size based on the value of MCA (13) TOCA means the total value of each OC set. (14) Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range connections - 50 HzFor power supplyQuantity5 RemarkEarth wire includedFor connection with indoorQuantity2 RemarkF1,F2 Power supply intakeBoth indoor and outdoor unit1-2 Electrical SpecificationsRXYQ32P9W1 BRXYQ34P9W1 BRXYQ36P9W1 BRXYQ38P9W1 BRXYQ40P9W1 BRXYQ42P9W1 BCurrentNominal running current (RLA) - - 50 HzStarting current (MSC) Ssc valuekVa1,7511,7562,6372,5652,576 Minimum circuit amps (MCA) fuse amps (MFA)A80100 Total overcurrent amps (TOCA)A-Full load amps (FLA) connections - 50 HzFor power supplyQuantity5 RemarkEarth wire includedFor connection with indoorQuantity2 RemarkF1,F2 Power supply intakeBoth indoor and outdoor unit1-2 Electrical SpecificationsRXYQ44P9W1 BRXYQ46P9W1 BRXYQ48P9W1 BRXYQ50P9W1 BRXYQ52P9W1 BRXYQ54P9W1 BCurrentNominal running current (RLA)
9 - - 50 HzStarting current (MSC) Ssc valuekVa2,6662,5942,6052,6292,634 Minimum circuit amps (MCA) fuse amps (MFA)A100125 Total overcurrent amps (TOCA)A-Full load amps (FLA) connections - 50 HzFor power supplyQuantity5 RemarkEarth wire includedFor connection with indoorQuantity2 RemarkF1,F2 Power supply intakeBoth indoor and outdoor unit1-2 Electrical SpecificationsRXYQ20P9W1 BRXYQ22P9W1 BRXYQ24P9W1 BRXYQ26P9W1 BRXYQ28P9W1 BRXYQ30P9W1B Outdoor Unit VRV III heat pump, small footprint combination RXYQ-P9 VRV Systems Outdoor Unit81 Specifications (15) Refer to refrigerant pipe selection or installation manual (16) In accordance with EN/IEC 61000-3-11, respectively EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys Zmax, respectively Ssc minimum Ssc value. (17) EN/IEC 61000-3-11: European/international Technical standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated 75A (18) EN/IEC 61000-3-12: European/international Technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current \> 16A and 75A per phase (19) Ssc: Short-circuit power (20) Zsys: system impedance (21) Calculations were done according to Japanese Standard JIS B8616:2006 (22) Sound level of a multi system is determined by the individual outdoor unit and installation condition.
10 (23) The refrigerant charge of the system must be less than 100kg. This means that if the calculated refrigerant charge is equal to or more than 95kg, you must divide the multiple outdoor system into smaller independent systems, each containing less than 95kg refrigerant charge. For factory charge, see unit nameplate. (24) The ESEER values published for air-cooled VRV systems allow a comparison with other air-cooled systems only; when comparing with air-cooled chillers, auxiliary power consumption of circulation pumps still needs to be added to the chiller performance. VRV Systems Outdoor Unit9 Outdoor Unit VRV III heat pump, small footprint combination RXYQ-P92 Electrical data2 - 1 Electrical Data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