fuelling COMPONENTS LIMITED > Aljac fuelling COMPONENTS LIMITED Pitfield House, Station Approach, Shepperton. Middlesex. TW17 8AN. UK. Tel: 44 (0) 1932 269869. Fax: 44 (0) 1932 269230. email: Aljac 20 Litre Closed Circuit Sampler Operating and Maintenance Instructions Aljac fuelling Components Ltd Pitfield House Station Approach Shepperton Middlesex. TW17 8AN. UK Tel : 44 (0) 1932 269869 Fax : 44 (0) 1932 269230 Email : fuelling COMPONENTS LIMITED > 2 July 2011 Contents Introduction.

FUELLING COMPONENTS LIMITED > 3 Aljac 20 Litre Closed Circuit Sampler 1.0 Introduction: Since it’s introduction in 1982 the Aljac 4 Litre Closed Circuit Sampler has displaced the

Tags:

  Closed, Circuit, Sampler, Fuelling, Closed circuit sampler

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of Aljac 20 Litre Closed Circuit Sampler Operating and ...

1 fuelling COMPONENTS LIMITED > Aljac fuelling COMPONENTS LIMITED Pitfield House, Station Approach, Shepperton. Middlesex. TW17 8AN. UK. Tel: 44 (0) 1932 269869. Fax: 44 (0) 1932 269230. email: Aljac 20 Litre Closed Circuit Sampler Operating and Maintenance Instructions Aljac fuelling Components Ltd Pitfield House Station Approach Shepperton Middlesex. TW17 8AN. UK Tel : 44 (0) 1932 269869 Fax : 44 (0) 1932 269230 Email : fuelling COMPONENTS LIMITED > 2 July 2011 Contents Introduction.

2 Installation. Operating procedure. Internal cleaning. Maintenance. Assembly drawing. Recommended spares. External Shell Water Detector Fitting External Hydrokit Fitting Aljac Statement of Conformity fuelling COMPONENTS LIMITED > 3 Aljac 20 Litre Closed Circuit Sampler Introduction: Since it s introduction in 1982 the Aljac 4 Litre Closed Circuit Sampler has displaced the traditional open bucket or glass jar method of carrying out the clear and bright quality check on aviation fuel.

3 However, although a 4 Litre sample is ideal for refuelling vehicles where single point samples are taken via short small bore sample lines, a larger sample volume is needed where the pipework volume would be flushed into a bucket prior to the glass jar sample, or where composite samples are required. The sampling of multi compartment road tankers or rail tank cars, or medium capacity storage tanks are typical examples, so we developed our 20 Litre Closed Circuit Sampler (CCS) which retains all of the novel features of the 4 Litre unit. The Aljac 20 Litre Closed Circuit Sampler consists of a clear glass tube fitted to a white epoxy coated conical base to assist in the detection of dirt and water, and with a hinged vented cover.

4 The base incorporates a tangential inlet port to promote vortexing of the incoming fuel, and integral coupled Stainless Steel drain valve. When fuel is drawn into the CCS under pressure from the sample points the tangential inlet port promotes vortexing of the incoming fuel. This concentrates any contamination in the centre of the base, making detection very easy. After the fuel has been visually inspected the drain valve is opened to release the sample. Internal cleaning of the Aljac CCS is easily accomplished through the hinged lid. A number of options are also available. Hydrometer and thermometer pockets for density and temperature checks can be provided in conjunction with a removable inner lid.

5 It is also possible to carry out the Shell Water Detector or Exxon Hydrokit test on the fuel sample using an option which can either be fitted to the inner lid (internal), or to a self sealing valve in the inlet port (external). Below lists the different Sampler builds: Description Part Number NPT threads Basic Model 6007263001 Basic Model + Internal Velcon Hydrokit Fitting 6007263002 Basic Model + Internal Shell Water Detector Fitting 6007263003 Basic Model + Internal Velcon Hydrokit Fitting + Hydrometer and Thermometer Tubes 6007263004 Basic Model + Internal Shell Water Detector Fitting + Hydrometer and Thermometer Tubes 6007263005 Basic Model + Hydrometer and Thermometer Tubes 6007263016 Additional External Shell Water Detector Fitting 6007233214 Additional External Velcon Hydrokit Fitting 6007233206 7 Litre Sampler 6007263021 fuelling COMPONENTS LIMITED

6 > 4 Installation: WARNING: The end user must exercise caution when locating the Sampler ensuring the surrounding area does not have a potential source of ignition. 1. The Sampler has been designed to be part of a fuel system and is safe to install into a potentially explosive atmosphere however the end user must exercise caution in that the Sampler unit in its self may give rise to potentially explosive atmosphere categorized as zone 2 (Cat. 3) outside and zone 0 (Cat. 1) inside and therefore this should be taken into consideration by the end user when locating it and ensuring the surrounding area does not have a potential source of ignition. 2. The CCS Sampler has four M12 mounting holes on the base and is to be fixed into position using M12 x 25mm long screws.

7 3. Connecting the inlet of the CCS Sampler into the fuel system is carried out by using 20mm diameter pipework to maximise the flow rate. Connect the inlet port on the Sampler to the sample points on the fuel system. It is also recommended that a spring close valve is used on the inlet side of the CCS Sampler to allow for a controlled filling operation. 4. Connecting the outlet of the CCS Sampler into the fuel system is done by using 40mm inside diameter pipework. Connect the drain port (outlet) on the CCS Sampler to the hydrant dispenser dump tank, depot product recovery system, or storage tank. 5. It is recommended that CCS is located so that gravity drainage is possible. If gravity drainage is not possible then the installation will require a pump to drain the CCS Sampler .

8 6. Ensure that the CCS Sampler is electrically bonded to surrounding system. WARNING: When installing the CCS Sampler it is important that it is bonded and that any other fuel equipment in the fuel system is bonded through a main earth point. CAUTION: All installation work must be carried out using safe principles and adhere to site standards and regulations. fuelling COMPONENTS LIMITED > Operating Procedure. The following procedure is applicable to basic models, and to Samplers with internal fittings Shell Water Detector or Velcon Hydrokit, Hydrometer and Thermometer fittings.

9 1. First ensure that the Sampler is empty, and clean, containing no traces of solid contaminant or water. Ensure that the valve in the inlet line is Closed , the Sampler Outlet valve is Closed , and the Cover shut. 2. Open the Inlet Valve to permit the product sample to enter the Sampler , and carefully fill to within 20 mm from the top of the glass cylinder. Close the Inlet Valve. CAUTION: Operator must take care not to over fill the CCS Sampler as this could result in a fuel spillage. 3. Examine the appearance of the sample for solid contaminant or free water either in suspension or in the base of the Sampler . The tangential inlet design will set up a vortex in the fuel flow which will tend to concentrate any contaminant at the centre of the base.

10 If the sample has a satisfactory appearance, and the Sampler has internal fittings, proceed to the checks in 4) below. If there are no internal fittings proceed to 5). 4. Open the cover of the Sampler and check for water using the Shell Water Detector Capsule/Velcon Hydrokit equipment, inserting the syringe/test tube into the fitting in the Inner Lid of the Aljac unit. If required, measure the Density of the Jet Fuel using an Approved Hydrometer in the Internal Hydrometer Fitting in the Internal lid, and similarly the Temperature using an Approved Thermometer in the Internal Thermometer Fitting. When these measurements are complete, remove the instruments and close the cover of the Sampler .