APM/HPM Serial Interface Options - Tasker

LAPM/HPMS erial Interface OptionsOP01-501 LImplementationPM/ APM/HPM Optional DevicesAPM/HPMS erial Interface OptionsOP01-501 Release 5102/96 Copyright, Trademarks, and NoticesPrinted in Copyright 1995 by Honeywell 01 December 15, 1995 While this information is presented in good faith and believed to be accurate,Honeywell disclaims the implied warranties of merchantability and fitness for aparticular purpose and makes no express warranties except as may be stated in itswritten agreement with and for its no event is Honeywell liable to anyone for any indirect, special or consequentialdamages.

APM/HPM Serial Interface Options 1-3 2/96 1.2 Each Array point can contain up to 512 Booleans (Flags), or 16 Reals (Numerics), or 32 Integers (Numerics), or 64 byte-sized Integers (Numerics), or 64 ASCII Characters (Strings)

Tags:

  Serial, Interface, Options, Apm hpm serial interface options

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of APM/HPM Serial Interface Options - Tasker

1 LAPM/HPMS erial Interface OptionsOP01-501 LImplementationPM/ APM/HPM Optional DevicesAPM/HPMS erial Interface OptionsOP01-501 Release 5102/96 Copyright, Trademarks, and NoticesPrinted in Copyright 1995 by Honeywell 01 December 15, 1995 While this information is presented in good faith and believed to be accurate,Honeywell disclaims the implied warranties of merchantability and fitness for aparticular purpose and makes no express warranties except as may be stated in itswritten agreement with and for its no event is Honeywell liable to anyone for any indirect, special or consequentialdamages.

2 The information and specifications in this document are subject tochange without 3000 is a registered trademark of Honeywell brand or product names are trademarks of their respective /HPMS erial Interface Options2/96 About This PublicationThis publication describes Serial Interface Options for the Advanced Process Manager(APM) and the High-Performance Process Manager (HPM). Configuration and operationof the Serial Interface on either platform is essentially the same. This manual is intendedfor use with Release 500 - 510 is a reference manual for process engineers, control-system engineers, and applicationengineers who design and implement data-acquisition and control strategies forTDC 3000X systems with Local Control user should be familiar with the system control functions described in System ControlFunctions.

3 SW09-501 in the Implementation/Startup & Reconfiguration - 2 binder beforeusing this publication and the Array Point function described in the Advanced ProcessManager Control Functions and Algorithms manual, AP09-500 or the High-PerformanceProcess Manager Control Functions and Algorithms manual, descriptions of parameters mentioned in this publication can be found in theAdvanced Process Manager Parameters Reference Dictionary, AP09-540, or the High-Performance Process Manager Parameters Reference Dictionary, bars are used to indicate paragraphs, tables, or illustrations containing changesthat have been made to this manual effective with Release 510.

4 Pages revised only tocorrect minor typographical errors contain no change Serial Interface Options2/96 Table of ContentsAPM /HPMS erial Interface Optionsi2 Interface Interface Interface IOP Adapter Interface FTA Interface FTA to Power Adapter SI FTA EIA-232 SI FTA EIA-422/485 Bradley SI FTA EIA-232 Serial Interface Cable Specifications3 ARRAY POINT Interface Array Point Parameter Array Point Interface Array Point Array Point Specific Configuration SI Array Type/Size and Starting Modbus Modbus Interface Address Loopback Subsystem Interface by Exception Procedures and Interface Array and SI Array and Error CheckingTable of ContentsAPM /HPMS erial Interface Optionsii2 Interface Array Serial Serial Interface Model Serial Interface Serial Serial Interface Model Serial Interface Allen-Bradley Specific Interface Devices/Data Types Scan FeaturesINDEXAPM/HPM Serial Interface Options1-12/961 INTRODUCTIONS ection

5 1 This section introduces the external Serial Interface Options available for the Advanced ProcessManager or High-Performance Process Manager Array point. Additional information on the Arraypoint can be found in the Advanced Process Manager Control Functions & Algorithms manual orthe High-Performance Process Manager Control Functions & Algorithms OVERVIEWThe Advanced Process Manager (APM) and High-Performance Process Manager (HPM)provide a point type known as the Array point. An Array point provides access to twosources of data APM/HPM box global variables external data from/to Serial Interface devicesIn the first case, an Array point can define a section of the APM or HPM box variables asits own data.

6 This function is described in the Advanced Process Manager ControlFunctions and Algorithms manual and in the High-Performance Process Manager ControlFunctions & Algorithms the second case, when the Array point is configured for external I/O operation, datafrom a Serial Interface (SI) IOP can be scanned, imaged (read), and used as if it were localdata to the Array Serial Interface to external subsystem devices is the focus of this subsystem data is resident in the APM or HPM Array point, it can be used by otherAPM/HPM points.

7 Thus, Serial Interface data represents essentially virtual I/O to theAPM or HPM. Array point data can be accessed by other APM/HPM control points, aswell as by CL programs. Data can be communicated peer-to-peer to other UCN FTA module must have at least one corresponding Array point configured in order toinitiate Serial communications. Data collected through the SI module is available as localdata for use by Digital Composite points, Device Control points, CL programs, etc. Notethat, unlike other IOP types, an SI module has no slots.

8 Array Point Flags and Numerics are fully supported as I/O connections; however, theSerial Interface is primarily intended as an input vehicle and it can efficiently import largequantities of , the Serial Interface IOP firmware runs diagnostic routines. It monitors andreports any detected communications time-outs or errors between the IOP and Serial Interface Options1-22 Serial Interface DESCRIPTIONEach Serial Interface IOP connects to one or two FTA assemblies. There are 32 slots perSerial I/O card.

9 Sixteen slots can be configured to FTA-1 and 16 slots can be configuredto FTA-2 (see Figure 1-1). Plug-in modules adapt the FTAs for different communicationsprotocols and applications. Certified applications* include Modbus Interface (Modicon Modbus-RTU protocol with extensions for real numbersand string support): Modicon 984 programmable logic controller Other Honeywell-approved Modbus compatible devicesAllen-Bradley Interface : Allen-Bradley PLC-2, 3, and 5 programmable logic controllersOther standard applications are being developed.

10 Custom applications are also availablefrom Honeywell by Serial Interface Options1-32 Array point can contain up to 512 Booleans (Flags), or 16 Reals (Numerics), or 32 Integers (Numerics), or 64 byte-sized Integers (Numerics), or 64 ASCII Characters (Strings)ProcessManagerModule SI IOPP owerAdapterFTA 2 FTA 1 APM/HPMTo Field DevicesTo Field Devices(up to 80 SIArray points)16 Arrays16 ArraysFigure 1-1 Serial Interface to an Array Point12447 Communications to the field device is by EIA RS-232D or EIA RS-485 standards.