Example: air traffic controller

ArmorBlock MaXum I/O and ArmorBlock I/O …

1792D and 1732 SeriesArmorBlockMaXum I/OandArmorBlockI/O SelectionGuide2 Publication 1792-SG001A-EN-P July 2004 ArmorBlock I/OOverviewArmorBlockSubsystemAbout ArmorBlock MaXum I/OThe 1792D ArmorBlock MaXum I/O family consists of stand-alone 24V dc I/Omodules which communicate via the DeviceNet network. The sealed IP 67 housingof these modules requires no enclosure. (Note that housing other than IP 67 mayrequire an enclosure.) I/O connectors are sealed M12 (micro) styles while thenetwork and auxiliary power connectors are sealed M12 or Mini styles. A wide rangeof diagnostics are standard as is DeviceLogix .The ArmorBlock family provides industrially hardened blocks of 24V dc digital I/Othat can be mounted directly on equipment near where sensors or actuators areplaced. The hardened feature of ArmorBlock allows you to install I/O without theadded cost of providing two CD versions of ArmorBlock MaXum provide complete point-level B ArmorBlock MaXum modules offer DeviceLogix technology.

7 Publication 1792-SG001A-EN-P⎯ July 2004 Step 1 - Select: I/O modules Selecting ArmorBlock I/O Modules ArmorBlock MaXum I/O ArmorBlock MaXum input modules are universal sinking/sourcing, while the output

Tags:

  Input, Module, Input module, Armorblock, And armorblock i o

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Transcription of ArmorBlock MaXum I/O and ArmorBlock I/O …

1 1792D and 1732 SeriesArmorBlockMaXum I/OandArmorBlockI/O SelectionGuide2 Publication 1792-SG001A-EN-P July 2004 ArmorBlock I/OOverviewArmorBlockSubsystemAbout ArmorBlock MaXum I/OThe 1792D ArmorBlock MaXum I/O family consists of stand-alone 24V dc I/Omodules which communicate via the DeviceNet network. The sealed IP 67 housingof these modules requires no enclosure. (Note that housing other than IP 67 mayrequire an enclosure.) I/O connectors are sealed M12 (micro) styles while thenetwork and auxiliary power connectors are sealed M12 or Mini styles. A wide rangeof diagnostics are standard as is DeviceLogix .The ArmorBlock family provides industrially hardened blocks of 24V dc digital I/Othat can be mounted directly on equipment near where sensors or actuators areplaced. The hardened feature of ArmorBlock allows you to install I/O without theadded cost of providing two CD versions of ArmorBlock MaXum provide complete point-level B ArmorBlock MaXum modules offer DeviceLogix technology.

2 DeviceLogixallows you to control outputs and manage status information locally, within the blockusing the DeviceLogix Editor, a function-block based tool that is a part of RSNetWorxfor MaXum has rotary node address switches that set the address yourequire. You set module parameters using RSNetWorx for DeviceNet or a similiarconfiguration MaXum is compatible with the KwikLink flat media system forcommunication on DeviceNet networks, but also provides connectivity to the roundmedia system as well. ArmorBlock MaXum builds upon the durability and features ofthe standard ArmorBlock I/O with additional diagnostic capabilities, cost savings, ArmorBlock modules contain I/O circuits, a built-in power supply, and a built-innetwork adapter in sealed housings to eliminate the need for enclosures. Ideal forapplications requiring highly distributed I/O blocks in locations close to sensors andactuators, they are compatible with PLC programmable controllers or SLC programmable controllers using DeviceNet scanners.

3 Therefore, ArmorBlockmodules I/O values are accessible from the PLC or SLC programmable controller 1732 ArmorBlock I/O family consists of stand-alone 24V dc I/O modules, whichcommunicate via the DeviceNet or PROFIBUS networks. The sealed IP 67 housing ofthese modules requires no enclosure. (Note that housing other than IP 67 mayrequire an enclosure.) I/O connectors are sealed M8 (pico) or M12 (micro) styleswhile the network and auxiliary power connectors are sealed M12 1792-SG001A-EN-P July 2004 FeatureBenefitArmorBlockMaXum I/OArmorBlock I/ORotary node address switchesSet the module node address without using software No mounting restrictionsModule can be mounted horizontally or vertically AutobaudModule automatically matches system baud rate no crashing due toincorrect baud setting Selectable input filtersSelect off-to-on and on-to-off delays best suited for your application Self-configuring I/OEach I/O point can be an input or an output Universal PNP/NPN inputsUse either type of input without using different blocks Hard-wired.

4 Watchdog circuitPlaces outputs in known state in case of a block internal fault Electronic fusingProvides protection and easy resetting for input device sourcing voltage andoutputs plus saves on fuse costs Point level diagnostics including input open wire, output no load,and selectable output fault latchingProvides diagnostic information to a specific I/O point to aid in troubleshooting Auxiliary power detectionProvides troubleshooting information Resettable faulted I/OOperator choice of three programmable methods to reset faulted I/O Change-of-state operationImproves network throughput by reducing network bandwidth usage I/O heartbeat notificationLets the scanner know that the module is alive and ready to communicate KwikLink flat media configurationEasy installation and connection to the DeviceNet network Isolated auxiliary power with auxiliary power LEDM aintains power to the block when main power fails Extended temperature and vibration specificationsFacilitate direct mounting to monitored and/or controlled equipment Uses industry standard mini connectors to connect to the DeviceNet networkandoutput-circuit

5 Power supply and micro connectors for sensors or actuatorsEasy replacements without rewiring Complies with Open DeviceNet Vendor Association ( ) conformance testsoftwareAssures interoperability with other compliant devices and systems Sealed housing rated for NEMA 4X, 6P, and IP 67No additional enclosure cost; allows washdown in dirty environments DeviceLogixLocal logic control ArmorBlock I/OFeatures andBenefits Summary4 Publication 1792-SG001A-EN-P July 2004 Typical ConfigurationsArmorBlock MaXum Configuration with Standard DeviceNet Round Trunk CableRefer to the DeviceNet Media Design Installation Guide, publication DNET-UM072, forcomplete DeviceNet layout 1792-SG001A-EN-P July 2004 ArmorBlock MaXum Configuration with Flat DeviceNet Trunk Cable1732 ArmorBlock I/O on DeviceNet6 Publication 1792-SG001A-EN-P July 2004 Specifying anArmorBlock I/OSystemFollow these steps as you specify your ArmorBlock I/O system.

6 Step1 Select ArmorBlock I/O modules based on fielddevices location of the device number of points needed appropriate catalog number number of points available per module number of modules2 Power Supply Requirements3 Consider Diagnostics and Mounting Requirements diagnostics needed local control needed mounting dimensions cables4 Select SoftwareSee Page1792D Digital I/O 7 Cable bases91732D Digital I/O91732D Auxiliary Power131792D Requirements111792D Using DeviceNet Power for Outputs 131792D Sensor Source Current141792D Diagnostics161732 Diagnostics181792D Mounting191732 Mounting27 For information on flat cable for communication and power,see the Cables and Cordsets Functionality317 Publication 1792-SG001A-EN-P July 2004 Step 1 - Select: I/O modulesSelecting ArmorBlock I/OModulesArmorBlock MaXumI/OArmorBlock MaXum input modules are universal sinking/sourcing, while the outputmodules are sourcing (except the 1792D-OVT16E, which is a 16 sinking outputmodule).

7 General ArmorBlock MaXum I/O SpecificationsEnclosure TypeRatingIP67 Mounting TypeOn-MachineOperating Temperature C ( F)Storage C ( F)Relative , Operating30 g peak acceleration, 11( 1) ms pulse widthShock, Non-Operating50 g peak acceleration, 11( 1) ms pulse widthVibrationTested 10 g @ Hz per IEC 68-2-6 CertificationsCSA, CE, C-Tick, DeviceNet When product is marked. See the Product Certification link at for declarations of Conformity, Certificates, andother certification 1792-SG001A-EN-P July 2004 ArmorBlock MaXumDigital I/O Each ArmorBlock MaXum I/O Block requires a cable base. Electronically protected outputs. M12 Quick-Disconnect terminations. Signal delay is selectable per input for <1ms (default), 2 ms, 4 ms, 8 ms, or 16 ms. The input circuit power source ( dc) is the same as the I/O block powersource, which comes through the DeviceNet input BlocksDigital Output BlocksDigital Combination BlocksCat.

8 DeviceNet Current specified with 12 sensors drawing 25 mA @ 24V dc. DeviceNet Current specified with 8 sensors drawing 25 mA @ 24V dc. DeviceNet Current specified with 4 sensors drawing 25 mA @ 24V dc. DeviceNet Current specified with 2 sensors drawing 25 mA @ 24V ofInputs12 Sink/Source8 Sink/Source8 Sink/Source4 Sink/Source4 Sink/Source2 Sink/Source8 SinkOperatingVoltage10V dc10V dc10V dc10V dc10V dc10V dc10V dcCurrent, Off-State input , mAOutputsNumber ofOutputs4 Source8 Source8 Source4 Source4 Source2 Source8 SourceOperatingVoltage10V dc10V dc10V dc10V dc10V dc10V dc10V dcCurrent, On-State Output, ANumber ofConnectors8884848 DiagnosticsConnector-levelConnector-leve lPoint-levelConnector-levelPoint-levelPo int-levelNoneDeviceNetCurrent (mA)570 mA 470 mA 470 mA 220 mA 220 mA 130 mA 470 mA Cat.

9 Of OutputsVoltage, On-StateOutput, , On-StateOutput, RangeCurrent, On-StateOutput, ofConnectorsDiagnosticsDeviceNet Current(mA)1792D-0B4D4 Source24V dc10V A4 Point-level80 mA1792D-0B8D8 Source24V dc10V A8 Point-level80 mA1792D-0VT16E16 Sink24V dc10V A8 None150 mACat. of InputsVoltage, On-StateInput, , On-StateInput, RangeCurrent, Off-StateInput, ofConnectorsDiagnosticsDeviceNet Current(mA)1792D-16 BVT0D16 Sink/Source24V dc10V mA8 Connector-level700 mA mAPoint-level650 mA 1792D-8 BVT0D8 Sink/Source24V dc10V mA4 Connector-level470 mA mA8 Point-level470 mA 1792D-4BV0D4 Sink/Source24V dc10V mA4 Point-level220 mA 1792D-2BV0D2 Sink/Source24V dc10V mA2 Point-level130 mA DeviceNet Current specified with 16 sensors drawing 25 mA @ 24V dc. DeviceNet Current specified with 8 sensors drawing 25 mA @ 24V dc. DeviceNet Current specified with 4 sensors drawing 25 mA @ 24V dc.

10 DeviceNet Current specified with 2 sensors drawing 25 mA @ 24V 1792-SG001A-EN-P July 2004 ArmorBlock MaXumCable BasesEach ArmorBlock MaXum I/O block, except for the 1792D-88HC high current block,requires a separate cable Compatible only with MaXum blocks with a maximum of 4 I/O MaXum I/O Cable Base with 12 mm round media connectors. Accepts standard drop cables fromround or flat media MaXum I/O Cable Base with 12 mm round media connectors and jumpered DeviceNet powerArmorBlock MaXum I/O Cable Base for KwikLink flat mediaArmorBlock MaXum I/O Cable Base with 18 mm round or flat media connectors and passthrough forDeviceNetArmorBlock MaXum I/O Cable Base with 18 mm round media connectors and jumpered DeviceNet powerArmorBlock MaXum I/O Cable Base with 18 mm round or flat media connectors, DeviceNet passthrough, andauxiliary power input connectionArmorBlock MaXum I/O Cable Base with 18 mm round or flat media connectors, DeviceNet passthrough.