(ISO 9002 COMPANY)AutomaticVoltage RegulatingRelayEE 301 - TINSTRUCTION MANUALI nstruction ManualforAutomaticVoltage Regulating RelayType EE 301-TDOC No. : MK 05 - 702 / ISS. 1 EMCO ELECTRONICSW orksUnit No. 13, "Kedarnath", Tungareshwar Industrial Complex No. 1, Village sativali,Vasai(E), Dist : Thane - 401208. Tel.:(0250)2481783 / 1804, Fax : (0250)2481087,Email : mumbai@emcoelectronics .orgOffice302,Vasan Udyog Bhavan, Sanapati Bapapat marg, OPP. Phoenix mill / BIG BAZAARL ower Parel (W), Mumbai - 400 013. Tel.:(0250)2481783 / 1804, Fax : (0250)2481087E-mail : Wood Street, (1st Floor),Richmond Road, Bangalore - 560 025 OfficeTel : (080) 557 0215 Fax : +91-80-556 6606E-mail : DESCRIPTION1 IIISPECIFICATIONS2 IVFAMILIARIZATION WITH INDICATIONS / CONTROLS3 VOPERATION INSTRUCTIONS5 VIFUNCTIONAL DESCRIPTION OF VARIOUS MOD

Instruction Manual for Automatic Voltage Regulating Relay Type EE 301-T DOC No. : MK 05 - 702 / ISS. 1 EMCO ELECTRONICS WorksUnit No. 13, "Kedarnath", Tungareshwar Industrial Complex No. 1, …

Tags:

  Manual, Instructions, Automatic, Regulating, Early, Voltage, Automatic voltage regulating relay ee, Instruction manual for automatic voltage regulating relay

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of Automatic Voltage Regulating Relay EE 301 - T …

1 (ISO 9002 COMPANY)AutomaticVoltage RegulatingRelayEE 301 - TINSTRUCTION MANUALI nstruction ManualforAutomaticVoltage Regulating RelayType EE 301-TDOC No. : MK 05 - 702 / ISS. 1 EMCO ELECTRONICSW orksUnit No. 13, "Kedarnath", Tungareshwar Industrial Complex No. 1, Village sativali,Vasai(E), Dist : Thane - 401208. Tel.:(0250)2481783 / 1804, Fax : (0250)2481087,Email : mumbai@emcoelectronics .orgOffice302,Vasan Udyog Bhavan, Sanapati Bapapat marg, OPP. Phoenix mill / BIG BAZAARL ower Parel (W), Mumbai - 400 013. Tel.:(0250)2481783 / 1804, Fax : (0250)2481087E-mail : Wood Street, (1st Floor),Richmond Road, Bangalore - 560 025 OfficeTel : (080) 557 0215 Fax : +91-80-556 6606E-mail.

2 DESCRIPTION1 IIISPECIFICATIONS2 IVFAMILIARIZATION WITH INDICATIONS / CONTROLS3 VOPERATION INSTRUCTIONS5 VIFUNCTIONAL DESCRIPTION OF VARIOUS MODULES8 VIIFAULT FINDING PROCEDURE9 VIIIOPTION13 IXLIST OF DRAWING & RECOMMENDED SPARES17 XWARRANTY18 XIFAULT REPORT FORM19 IINTRODUCTIONEMCO s Solid State Voltage Regulating Relay Type EE 301- T is used for Regulating the secondaryvoltage of power transformer with on-load tap changer . The required dead-band settings are setby setting the Nominal value and L & R levels independently. The Time Delay setting on the frontpanel eliminates the Relay operations for momentary fluctuations of the regulated Voltage , thusreducing the number of operations of the tap the regulated Voltage falls below the specified Under Voltage limit, the control relays areautomatically blocked there is no Voltage correction, and a pair of Relay contacts is madeavailable for the regulated Voltage goes above the specified Over Voltage limit, the control relays areautomatically blocked there is no Voltage correction, and the same pair of Relay contacts (forUV)

3 Is made available for built-in Tap Position Indicator with 1KW step resistance can be provided optionally to indicatethe Tap No. of the Power Transformer upto a maximum of Relay uses all solid state circuitry which increases its reliability and life. The output, inputconnections are made through a terminal block. However all normal precautions/care in handling/storage should be observed as for a sensitive electronic DESCRIPTIONEMCO's Solid State Automatic Voltage Regulating Relay Type EE301-T is designed for maximumoperational simplicity. It regulates the secondary Voltage of power transformers with on-loadtapchangers.

4 The bandwidth control allows the dead-band to be set in terms of upper (LOWERVOLTS)and lower (RAISE VOLTS) Voltage limits around a particular nominal value with Time Delay control allows the regulator to respond only to Voltage fluctuations lasting forperiods greater than the selected time delay. Where the Voltage correction requires more than onetap change, the time delay is re-initiated before further tap changes. No special provisions arerequired to reset the time delay which resets automatically after the Voltage correction. Solid StateLamps (LEDs) indicate Voltage outside the preset limits and control Relay of the RAISE / LOWER Control Relay is automatically inhibited when the Voltage fallsbelow the specified undervoltage limit or goes above the Overvoltage limit.

5 One pair of normallyopen Relay contacts are provided to effect the tapchanger RAISE and LOWER operations and totrigger an alarm in case of Undervoltage / Overvoltage conditions. (Only one pair of contacts isavailable for either UV or OV)An alarm in the form of normally open contacts is provided in case of control failure AVR Relaycontinuously showing either 'L' or 'R' command for more than 15 minutes due to malfunctioning ofAVR/OLTC/ any built-in Tap Position Indicator with 1KW step resistance can be provided optionally to indicatethe Tap No. of the Power Transformer upto a maximum of AC + 15% 50Hz, 15 VAPT Supply.

6 110V AC 50Hz, and readable on displayNominal Value Setting (NVA)..Adjustable between 110V + 10% & readable on displayLOWER Volts between to 5V abovethe NVA and readable on displayRAISE Volts between to 5V below theNVA and readable on displayTime Delay ( Voltage Independent) TimeDelay adjustable from 10 to 120 SecsTime Delay resetting with voltagereturning to deadbandUndervoltage blocking at 80% of regulated at 85% of regulated valueOvervoltage Blocking at 132V & Restoration at 127 VControl pair of normally open potential free contacts ofrating 5A at 240V ACor 24V DC resistive load for eachLower, Raise, Control Fail & Undervoltage / Overvoltagecontrol relays (Only one pair of contacts is available foreither UV or OV)Control Pulse operation with approx.

7 2 secs on timeOperating C - 45 COverall X 160mm X 260mm (H X W X D) Kgs. (approx.) Tap Position Indicator , Max. 35 Taps with 1KW resistance2. Line drop compensator with resistive and reactive compensation of either polarity upto 20% and suitable for operation with 1A, 5VA current transformer3. Normally closed Auxiliary Supply Fail Relay Contacts4. User defined settings for PT Supply, Time Delay, Undervoltage & Overvoltage Blocking. User specified step resistance for TPI5. 4-20 mA TPI output for WITH VARIOUS INDICATIONS / CONTROLS :A.

8 INDICATIONS1. 4x7 Segment Display (AVR):Display lights when Auxiliary Supply is 'ON'.2. 2x7 Segment Display (TPI):Display lights when Auxiliary Supply is 'ON'.3. L Lamp: ON whenever the PT Voltage exceeds the 'LOWERVOLTS set R Lamp: ON whenever the PT Voltage falls below the RAISEVOLTS set UV / OV Lamp:'ON whenever the PT Voltage falls below the factoryset Undervoltage limit below 80% of the Nominalvoltage. This lamp will turn-off only when the PTvoltage raises above 85% of the Nominal Voltage lamp will also be ON , when the PT Voltage goesabove the factory set Overvoltage limit above lamp will turn-off only when the PT Voltage fallsbelow 'LR' Lamp:'ON' when Lower Relay is RR Lamp: ON when Raise Relay is 'CF' Lamp:'ON' when Control Fail Relay is energised, when thePT Voltage remains outside the bandwidth for more than15 TEST Lamp: ON when AVR is in TEST Power - ON.

9 This is a toggle switch which when ON suppliesAuxiliary Voltage to the 'R Set:This is a variable control varying from to belowNVA setting. This control sets the (lower limit of the PTvoltage below which if the Voltage reduces, thencorrective action will be taken by the instrument. Thesetting is to be read on 'NOM Set:This is a variable control to set the Nominal value ofPT Voltage varying between + 10% of 110V. This setting becomes the reference level around which L & Rsetting can be varied. The setting is to be read on 'L Set:This is variable control, varying from to NVA setting.)

10 This control sets the upper limit ofthe PT Voltage beyond which if the Voltage rises,corrective action will be taken by the setting is to be read on Time Delay:Corrective action takes place only after the TimeDelay as set by this control has elapsed and thePT Voltage continues to remain outside the setLower or Raise limits (but does not fall below theUV / OV limit).6. Test/Normal Switch for AVR:It selects the Test or Normal mode of operation. Inthe Test mode, PT Voltage is simulated internally& can be varied through the Test Control on thefront panel.