Transcription of AXPK-PLUS - Draka
1 ApplicationDesigned for replacement of AXPK and AXPK-PE. The outer sheath is self-extinguishing and halogen-free. Cable is mechanically as strong as PE sheathed cable. For fi xed installation indoors and outdoors, perfect for ploughing down. Suitable for cable ducts and house 4879, HD 603-5D S1, IEC 60502-1, IEC 60332-1 Cat. B, HD 308 S2:2002 Certificate/approvalFI, CERated voltageU0/U = 0,6/1 kVUm = 1,2 kVTemperature rangeHighest permissible conductor temperature: - in continuous operation ..90 C- in a short circuit (duration up to 5 s).
2 250 CLowest recommended temp. during laying .. 20 CConstructionConductor .. 16 mm2 solid round aluminium conductor;25 300 mm2 stranded, compacted and annealed sector shaped alu-minium conductorInsulation .. black XLPE compoundLaying up .. four insulated conductors stranded togetherSheath .. black halogen-free self-extinguishing PE compound;insulation and sheath are UV(1) resistible and they don't need extra protection against of coresPhase conductors .. brown, black, greyPEN conductor .. yellow-greenMarkingManufacturer, product name, date of manufacture, outer sheath material designation, meter )
3 UV ultraviolet radiationAXPK-PLUS1 kV power cable with XLPE insulated aluminium conductors and halogen-free outersheathThe technical specifications may change any time without prior Draka Keila of Prysmian Road 3176606 Keila, EstoniaPhone +372 674 7466 Fax +372 674 7468 Power cablesBasic cable data4G164G254G354G504G704G95 EAN code64 100+06 210 07-706 210 08-406 210 09-106 210 10-706 210 11-406 210 12-1 Construction dataExternal cable diameter (1)mm202123273034 Weight (1)aluminiumkg/km165265365495720995cable kg/km38050067083011701500 Delivery dataStandard delivery lengthm100010001000100010001000 DrumK12K14K16K16K18K20 Total weight (1)cable + drumkg470615865102514001840 Mechanical data (2)Minimum permissible bending radius during layingm0,240,260,280,310,360,41 Minimum permissible bending radius at final installation (3)
4 M0,170,190,200,230,260,29 Maximum permissible pulling force with a pulling gripkN0,91,52,13,04,25,7 Maximum permissible pulling force with a pulling eyekN3,25,07,010,014,019,0 Electrical data (2)Maximum DC resistance ofconductor 20 C /km1,911,200,8680,6410,4430,320 Maximum AC resistance ofconductor 70 C /km2,31,51,00,770,530,39 Current ratings (2)In groundconductor 70 CA78100125150185220In airconductor 70 CA6483105125155190conductor 90 CA75105130165205245 Short circuit currents (2)Maximum permissible short circuit current for 1 second (4)kA1,52,33,34,76,68,9 Basic cable data4G1204G1504G1854G2404G300 EAN code64 100+06 21013-806 210 14-506 210 15-26 210 16-9 Construction dataExternal cable diameter (1)mm3842475358 Weight (1)aluminiumkg/km12601550195025503190cab lekg/km19002300280037004600 Delivery dataStandard delivery lengthm1000500500500500 DrumK22K20K20K22K24 Total weight (1)cable + drumkg23101490174022602750 Mechanical data (2)
5 Minimum permissible bending radius during layingm0,460,510,570,640,70 Minimum permissible bending radius at final installation (3)m0,330,360,400,450,49 Maximum permissible pulling force with a pulling gripkN7,28,58,58,58,5 Maximum permissible pulling force with a pulling eyekN20,020,020,020,020,0 Electrical data (2)Maximum DC resistance ofconductor 20 C /km0,2530,2060,1640,1250,100 Maximum AC resistance ofconductor 70 C /km0,310,250,200,160,13 Current ratings (2)In groundconductor 70 CA255290330375430In airconductor 70 CA220250285330380conductor 90 CA280320365430480 Short circuit currents (2)Maximum permissible short circuit current for 1 second (4)kA11,314,117,422,628,31) Approximate ) See the basic assumptions at general information of ) Final installation with careful single )
6 Initial temperature of conductor before short circuit 90 C, final temperature of conductor after short circuit 250 kV power cable with XLPE insulated aluminium conductors and halogen-free outersheathThe technical specifications may change any time without prior Draka Keila of Prysmian Road 3176606 Keila, EstoniaPhone +372 674 7466 Fax +372 674 7468