Basic Power Supply 10 A - Rockwell Automation

Reference Manual Original Instructions Basic Power Supply 10 A. Catalog Number 1606-XLB240E. Important User Information Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards. Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice. If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. In no event will Rockwell Automation , Inc.

Rise time typ 60 ms at 24V, 10 A const. current load, 0 mF load capacitance, see Figure 4 typ 230 ms at 24V, 10 A const. current load, 5 mF load capacitance, see Figure 4 Turn-on overshoot max 200 mV see Figure 4 (1) The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.

Tags:

  Automation, Power, Supply, Rockwell automation, Rockwell, Power supply

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of Basic Power Supply 10 A - Rockwell Automation

1 Reference Manual Original Instructions Basic Power Supply 10 A. Catalog Number 1606-XLB240E. Important User Information Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards. Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice. If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. In no event will Rockwell Automation , Inc.

2 Be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation , Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation , Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation , Inc., is prohibited Throughout this manual, when necessary, we use notes to make you aware of safety considerations. WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.

3 ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence. IMPORTANT Identifies information that is critical for successful application and understanding of the product. Labels may also be on or inside the equipment to provide specific precautions. SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present. BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures. ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc Flash. Arc Flash will cause severe injury or death.

4 Wear proper Personal Protective Equipment (PPE). Follow ALL. Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE). Basic Power Supply 10 A. Table of Contents Topic Page Topic Page Additional Resources 3 Hold-Up Time 11. Terminology and Abbreviations 4 DC OK Relay Contact 11. Product Overview 5 Efficiency and Power Loss 12. Front Side and User Elements 6 Lifetime Expectancy and Mean Time Between 13. Failure (MTBF). Protection Features 6 Functional Diagram 13. Safety Features 7 EMC 14. Installation Notes 7 Application Notes 15. Terminals and Wiring 7 Specifications 15. Installation Notes 7 Environment 19. Input 8 Dielectric Strength 20. DC-Input 9 Standards Compliance and Certifications 22. Input Inrush Current 9 Approximate Dimensions and Weight 23. Output 10. Additional Resources These documents contain additional information concerning related products from Rockwell Automation .

5 Resource Description Switched Mode Power Supply Technical Data, publication Provides specifications and approximate dimensions 1606-TD002 for full line of switched mode Power supplies. Industrial Automation Wiring and Grounding Guidelines, Provides general guidelines for installing a Rockwell publication Automation industrial system. Product Certifications website, http:// Provides declarations of conformity, certificates, and other certification details. You can view or download publications at To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation sales representative. Rockwell Automation Publication 1606-RM056A-EN-P - December 2016 3. Basic Power Supply 10 A. Terminology and Abbreviations Term Definition 230V AC A figure with the unit (V AC) at the end is a momentary figure without any additional tolerances included.

6 50 Hz vs. 60 Hz As long as not otherwise stated, AC 100V and AC 230V parameters are valid at 50 Hz mains frequency. AC 120V parameters are valid for 60 Hz mains frequency. AC 230V A figure that is displayed with the AC or DC before the value represents a nominal voltage with standard tolerances included. for example: DC 12V describes a 12V battery, whether it is full ( ) or flat (10V). Earth, Ground This document uses the term earth which is the same as the term ground . PE and symbol PE is the abbreviation for Protective Earth and has the same meaning as the symbol. PELV Protection by extra-low voltage SELV Safety by extra-low voltage 4 Rockwell Automation Publication 1606-RM056A-EN-P - December 2016. Basic Power Supply 10 A. Product Overview 1606-XLB Basic Power Supplies are compact, industrial grade Power supplies that focus on the essential features needed in industrial applications.

7 The mechanically robust housing is made of a high-grade, reinforced molded material, which permits the units to be used in ambient temperatures up to 70 C (158 F). This Power Supply features a wide input voltage range, which makes it suitable for global use. The addition of a DC-OK signal makes the Power Supply ideal for many industry applications such as: process, Automation , and many other critical applications where preventive function monitoring can help to avoid long downtimes. The 1606-XLB240E Power Supply offers these features: Wide input range, AC 100 240V. Active PFC. Cost optimized without compromising quality or reliability. Small width of only 49 mm ( in.). Efficiency up to Full Power between -25 +55 C (-13 +131 F). DC-OK relay contact 1-year warranty Rockwell Automation Publication 1606-RM056A-EN-P - December 2016 5. Basic Power Supply 10 A. Front Side and User Elements Figure 1 - Front Side of DC-UPS.

8 Letter Description A Input terminals - (screw terminals). N, L - Line input PE - Protective earth input B Output terminals - (screw terminals, two pins per pole). + Positive output Negative (return) output C Output voltage potentiometer - Guaranteed adjustment range: 24 28V. Factory set: D DC-OK status indicator (green) On, when the output voltage is >18V. E DC-OK Relay Contact (push-in terminals). Protection Features Attribute 1606-XLB240E. Output protection Electronically protected against overload, no-load, and short circuits (1). Output overvoltage protection typ DC In case of an internal Power Supply max 32 V DC anomaly, a redundant circuit limits the maximum output voltage. In such a case, the output shuts down and stays down until the input voltage is turned off and on again for at least 1 minute or until the green status indicator went off. Degree of protection IP 20 EN/IEC 60529 Caution: For use in a controlled environment according to CSA No Over-temperature protection yes Output shut-down with automatic restart Input transient protection MOV (Metal Oxide Varistor).

9 Internal input fuse Included not user replaceable (1) If there is a protection event, audible noise can occur. 6 Rockwell Automation Publication 1606-RM056A-EN-P - December 2016. Basic Power Supply 10 A. Safety Features Attribute 1606-XLB240E. Input/output SELV IEC/EN 60950-1. separation PELV IEC/EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41. double or reinforced insulation Class of protection I PE (Protective Earth) connection required Isolation resistance > 5 MOhm input to output, 500V DC. Touch current typ mA 100V AC, 50 Hz, TN-,TT-mains/IT-mains (leakage current). typ mA 120V AC, 60 Hz, TN-,TT-mains/IT-mains typ mA 230V AC, 50 Hz, TN-,TT-mains/IT-mains < mA 110V AC, 50 Hz, TN-,TT-mains/IT-mains < mA 132V AC, 60 Hz, TN-,TT-mains/IT-mains < mA 264V AC, 50 Hz, TN-,TT-mains/IT-mains Installation Notes Use appropriate copper cables that are designed for minimum operating temperatures of: 75 C (167 F) for ambient up to 55 C (131 F) minimum.

10 90 C (194 F) for ambient up to 70 C (158 F) minimum. Follow national installation codes and installation regulations. Verify that all strands of a stranded wire enter the terminal connection. Do not use the Power Supply without a PE connection. Securely tighten unused terminal compartments. Ferrules are allowed. Terminals and Wiring The terminals are IP20 fingersafe constructed and suitable for field- and factory wiring. Attribute Input and Output DC-OK Signal Terminal type Screw terminals Push-in terminals Solid wire, max 6 mm2 mm2. Stranded wire, max 4 mm2 mm2. American Wire Gauge AWG 20-10 AWG 28-16. Wire diameter, max mm (including ferrules) mm (including ferrules). Wire stripping length 7 mm ( in.) 7mm ( in.). Screwdriver mm slotted or cross-head No 2 Not required Recommended tightening torque 1 N m, 9 lb in Not applicable Rockwell Automation Publication 1606-RM056A-EN-P - December 2016 7.