G Straight-Run Situations and Recommendationsg Installation Orientation Options for Various Fluid Conditionsg Overcoming Limited Straight-Run and Flow Obstructions Using Flow Conditionersg Optimizing Accuracy and Repeatability PerformanceBest Practices Engineering GuideInstallation Recommendations for FCI Single-Point, Thermal Dispersion Flow MetersOptimizing Flow Meter Installation Ensures Performance and Instrument AccuracyAll flow meter technologies have recommended installation and Engineering Practices to ensure they meet their published specifications and for optimal performance, accuracy and repeatability.

FCI Offers Multiple Solutions to Limited Straight-Run Conditions Straight-run is one of the most significant variables to consider in your flow meter installation to ensure accurate and repeatable flow measurement.

Tags:

  Guide, Measurement

Information

Domain:

Source:

Link to this page:

Please notify us if you found a problem with this document:

Other abuse

Advertisement

Transcription of Best Practices Engineering Guide - …

1 G Straight-Run Situations and Recommendationsg Installation Orientation Options for Various Fluid Conditionsg Overcoming Limited Straight-Run and Flow Obstructions Using Flow Conditionersg Optimizing Accuracy and Repeatability PerformanceBest Practices Engineering GuideInstallation Recommendations for FCI Single-Point, Thermal Dispersion Flow MetersOptimizing Flow Meter Installation Ensures Performance and Instrument AccuracyAll flow meter technologies have recommended installation and Engineering Practices to ensure they meet their published specifications and for optimal performance, accuracy and repeatability.

2 Flow meter users are frequently challenged with wide variations in their actual field conditions and installation constraints that are much different from the ideal conditions under which their flow meter was calibrated. In fact, the most common installation constraint for most all flow meter installations is inadequate straight-run. Flow meter users expect their flow meter suppliers to provide Engineering recommendations and solutions to overcome real world application conditions to obtain expected flow meter performance to specifications.

3 This Guide provides recommended Engineering Practices with diagrams and specifications for straight-run, installation orientation and depths, as well as use of flow conditioners as an Engineering solution for FCI single-point, thermal dispersion flow FCI s Free AVAL Tool for Proper Sizing and Instrument SelectionFCI s exclusive AVAL software tool is designed to make proper sizing and selection of thermal dispersion flow meters simple and effective. AVAL is always available and accessible by visiting FCI s website at and clicking on the AVAL process parameters, fluid compositions and installation constraints can limit ideal performance, FCI AVAL software will ensure you are fully aware of process conditions that can potentially produce installed uncertainty.

4 AVAL application evaluation software is a proprietary FCI service designed from years of fluid testing and installation experience. Using AVAL software, FCI models an installation with straight run variations and obstructions. When a complete evaluation is performed, an output report clearly defines expected installed accuracy or offers recommendations for improvement. FCI relates laboratory calibrations to true installed field performance. The configuration software matches specific process conditions and makes appropriate configuration recommendations for each flow meter Offers Multiple Solutions to Limited Straight-Run ConditionsStraight-run is one of the most significant variables to consider in your flow meter installation to ensure accurate and repeatable flow measurement .

5 Inadequate straight-run or the presence of flow disrupters are the most common real world constraints to proper flow meter 1 provides recommendations and Engineering Practices for commonly found conditions and line sizes to ensure an installation supports the meter s published specifications. When possible, installing the flow meter within these recommendations will assure proper performance with the least installed cost. Figure 2 shows samples of the effects on flow meter accuracy of the straight-runs specified in Figure 1 are not always possible, FCI offers four solutions which can be applied by themselves or in combination to overcome installation constraints.

6 G Vortab Flow Conditioners to Develop Flow Profile and Negate Obstructions with up to 70% Reduction in Straight-Run Needed g Customized Calibration Set-ups which Simulate the Actual Field Installation Conditions g In-situ Field Calibration Service and Instrument Adjustment g Multiple Sense Point Flow MetersFigure 1: Straight Run RecommendationsDefault Recommendation for Required Straight-runs with Undefined ObstructionsPipe Size Upstream Downstream< 6 inches [150 mm] 20 x Pipe ID 10 x Pipe ID 6 inches [150 mm] 15 x Pipe ID x Pipe IDwith Vortab flow conditioner 6 x Pipe ID 2 x Pipe IDRecommendation for 45 or 90 Elbows in PlanePipe Size Upstream Downstream< 6 inches [150 mm] 15 x Pipe ID x Pipe ID 6 inches [150 mm]

7 10 x Pipe ID 5 x Pipe IDwith Vortab flow conditioner 6 x Pipe ID 1 x Pipe IDRecommendation for 45 or 90 Elbows OUT of Plane (Swirl Effect)Pipe Size Upstream Downstream< 6 inches [150 mm] 20 x Pipe ID 10 x Pipe ID 6 inches [150 mm] 15 x Pipe ID 5 x Pipe IDwith Vortab flow conditioner 6 x Pipe ID 2 x Pipe IDRecommendation for Flow Controlling Valves Upstream or DownstreamPipe Size Upstream Downstream< 6 inches [150 mm] 20 x Pipe ID 10 x Pipe ID 6 inches [150 mm] 15 x Pipe ID 5 x Pipe IDwith Vortab flow conditioner 9 x Pipe ID 2 x Pipe IDRecommendation for Pipe Adaptor Upstream or DownstreamPipe Size Upstream Downstream< 6 inches [150 mm]

8 20 x Pipe ID 10 x Pipe ID 6 inches [150 mm] 15 x Pipe ID 5 x Pipe IDwith Vortab flow conditioner 9 x Pipe ID 2 x Pipe IDRecommendation for Pipe Reducers Upstream or DownstreamPipe Size Upstream Downstream< 6 inches [150 mm] 15 x Pipe ID 5 x Pipe ID 6 inches [150 mm] 10 x Pipe ID 3 x Pipe IDwith Vortab flow conditioner 6 x Pipe ID 1 x Pipe IDRecommendations shown are for general reference only as actual application conditions can vary and multiple effects are possible. FCI flow meter performance guarantees are only available following completed AVAL software-based application evaluations.

9 Contact your local FCI sales representative for a comprehensive 2: Sample of Effects on Accuracy with Flow Obstructions Before and After Installation Point of Single-Point, Insertion Flow MeterWith Pipe ID < 6 inches [150 mm]Distance From Flow Meter19D17D15D13D11D9D7D5D3D1D1D3D5D7D9 DObstruction Type:90 Elbow 0%0%<1%1%1%2%3%4%5%5%4%3%2%1%0%Two Elbows (with 4D between them)1%1%2%2%2%3%4%6%8%9%5%4%3%2%1%Gate Valve1%2%3%4%5%6%8%10%17%20%15%13%8%3%1% With Pipe ID 6 inches [150 mm]Distance From Flow Meter19D17D15D13D11D9D7D5D3D1D1D3D5D7D9 DObstruction Type.

10 90 Elbow 0%0%0%0%0%<1%2%3%4%5%4%2%<1%0%0%Two Elbows (with 4D between them)0%0%<1%2%2%2%4%5%6%8%4%3%<1%0%0%Gat e Valve0%0%<1%2%3%4%6%8%15%20%15%5%<1%0%0% Vortab Flow Conditioners Reduce Straight-RunIn installations with inadequate straight-run, Vortab flow conditioners provide a solution that will ensure flow meter performance in as little as just 7 diameters upstream. This patented technology is the flow conditioner most recommended by flow and process control experts to eliminate the flow swirl and profile distortions which adversely affect flow meter measuring accuracy.